2.3 Flooring Requirements

Oracle recommends that the Exalogic machine be installed on raised flooring. The site floor and the raised flooring must be able to support the total weight of the Exalogic machine as specified in Environmental Requirements.

Table 2-3 lists the floor load requirements.

Table 2-3 Floor Load Requirements for Exalogic Machine

Description Requirement

Maximum allowable weight of installed rack equipment

952.54 kg (2100 lbs)

Maximum allowable weight of installed power distribution units

52.16 kg (115 lbs)

Maximum dynamic load (maximum allowable weight of installed equipment including PDUs)

1004.71 kg (2215 lbs)

Note:

Open tiles are required for electrical access.