C H A P T E R  5

Cabinet Specifications

This chapter includes shipping, physical, and power sequencer specifications for Sun cabinets.

Topics in this chapter include:


Sun Cabinet Shipping Crate Specifications


TABLE 5-1 Physical Specifications for Crated Cabinets

Sun StorEdge Expansion Cabinet

Sun Fire Cabinet

Sun Rack 900

Height

80 in

203 cm

80 in

203 cm

80 in

203 cm

Width

42 in

107 cm

43 in

109 cm

43 in

109 cm

Depth

47 in

120 cm

47 in

120 cm

48 in

122 cm

Weight

524 lb

238 kg

558 lb

253 kg

530 lb

240 kg



Sun Cabinet Physical Specifications


TABLE 5-2 Physical Specifications for Cabinets in Operation

Sun StorEdge Expansion Cabinet

Sun Fire Cabinet

Sun Rack 900

Height

73.5 in

186.7 cm

75 in

191 cm

73.75 in

187 cm

Width

24 in

61 cm

24 in

61 cm

23.6 in

60 cm

Nominal Rack Opening

17.72 in

45 cm

17.72 in

45 cm

17.72 in

45 cm

Depth

36 in

91 cm

36 in

91 cm

35.4 in

90 cm

Weight[1]

350 lb

159 kg

325 lb

147 kg

400 lb

181 kg

Load Capacity[2]

1300 lb

589 kg

1200 lb

544 kg

1200 lb

544 kg

Usable Rack Units

36

32

38



Cabinet Power Sequencer Specifications


TABLE 5-3 Cabinet Power Sequencer Specifications

Sun StorEdge Expansion Cabinet

Sun Fire Cabinet

Sun Rack 900

AC Voltage Rating

200 to 240 VAC

200 to 240 VAC

200 to 240 VAC

Frequency Range

47 to 63 Hz

47 to 63 Hz

47 to 63 Hz

Max Current

24A @ 240 VAC

24A @ 240 VAC

32A @ 208 VAC

Max Power Capacity[3]

5.7 kW

5.7 kW

7.6 kW

Required Power Receptacles

2-NEMA L6-30R
(U.S.)

 

2-IEC309 32A
(International)

NEMA L6-30R
(U.S.)

 

IEC309 32A
(International)

4-NEMA L6-20R
(U.S.)

 

4-IEC309 16A
(International)


 


1 (TableFootnote) This specification is the weight of the cabinet and two power sequencers only. The total weight of the cabinet also includes the servers and other equipment it houses.
2 (TableFootnote) This capacity is for a fully configured cabinet.
3 (TableFootnote) This is the theoretical maximum power capacity of the cabinet. This number should not be used
to calculate power and cooling requirements for your installation. Use the combined power
consumption figures of the equipment installed in the cabinet instead.