Sun Enterprise 6500/5500/4500 Systems Reference Manual

Appendix A Specifications

Physical Specifications

Table A-1 Enterprise 6500/5500 Physical Specifications

 

U.S . 

Metric 

Height 

68.3 in 

173 cm 

Width 

30 in 

77 cm 

Depth 

39 in 

99 cm 

Weight 

835 lb, approx 

375 kg, approx 

Power cord 

15 ft 

4.6 m 

Table A-2 Enterprise 6500/5500 Clearance and Service Access

 

U.S. 

Metric 

Front 

4 ft 

122 cm 

Rear 

3 ft 

92 cm 

Left  

1 ft* 

31 cm 

Right 

1 ft * 

31 cm 

* Access only. There are no side clearance requirements during operation. 

Table A-3 Enterprise 6500/5500 Shipping Specifications

 

U.S. 

Metric 

Height 

75.3 in 

188 cm 

Width 

39 in 

99 cm 

Depth 

44.5 in 

113 cm 

Weight 

910 lb, approx 

415 kg, approx 

Table A-4 Enterprise 4500 Physical Specifications

 

U.S. 

Metric 

Height 

13.5 in 

34 cm 

Width 

19.7 in 

50 cm 

Depth 

22 in 

56 cm 

Weight 

150 lb, approx 

68 kg, approx 

Power cord 

6 ft 

1.8 m 

Table A-5 Enterprise 4500 Clearance and Service Access

 

U.S. 

Metric 

Front 

18 in 

47 cm 

Rear 

18 in 

47 cm 

Left  

6 in* 

16 cm* 

Right 

6 in* 

16 cm* 

*Although 6 in (16 cm) clearance is sufficient to prevent blocking the in and out airflow of a single system, to avoid exhaust air recirculation, a minimum space of 36 in (92 cm) is recommended between systems sitting side by side. 

Table A-6 Enterprise 4500 Shipping Specifications

 

U.S. 

Metric 

Height 

19.0 in 

48 cm 

Width 

23.8 in 

60 cm 

Depth 

26.8 in 

68 cm 

Weight 

160 lb, approx 

72 kg, approx 

Electrical Specifications

Table A-7 Enterprise 6500/5500 Electrical Specifications

Parameter 

 

Value 

Input current 

Voltage range 

200-240 Vac 

 

Current, maximum 

24A 

 

Current frequency range 

47-63 Hz 

Input power rating 

Total continuous power 

3500W (with 3 drive trays) 

Volt-Ampere rating 

 

3700 VA 

BTU rating 

 

12,000 BTU 

Power factor 

 

0.92 - 0.96 

Plug type 

U.S. 

NEMA L6-30P for 200-240 Vac 

 

International 

32A, single phase IEC 309, connected for 220-240 Vac 

Table A-8 Enterprise 4500 Electrical Specifications

Parameter 

 

Value 

Input current 

Voltage range 

100-120 Vac or 200-240 Vac 

 

Current, maximum 

12A  

 

Current frequency range 

47-63 Hz 

Input power rating 

Total continuous power 

1370W 

Volt-Ampere rating 

 

1440 VA 

BTU rating 

 

4680 BTU 

Power factor 

 

0.92 - 0.96 

Plug type 

U.S. 

NEMA 5-15P 

 

International 

10A, single phase IEC 320, connected for 220-240 Vac 

Environmental Requirements

Table A-9 Enterprise 6500/5500 Temperature, Humidity, and Altitude Limits

 

Operating 

Nonoperating 

Temperature 

41F to 95F (5C to 35C)* 

-4F to 140F (-20C to 60C) 

Humidity 

20% to 80% RH noncondensing, 27C max wb 

93% RH 

Altitude 

9,843 ft (3 km) 

39,370 ft (12 km) 

*Maximum operating temperature is 95F (35C) when using tape media. 

Table A-10 Enterprise 4500 Temperature, Humidity, and Altitude Limits

 

Operating 

Nonoperating 

Temperature 

41F to 104F (5C to 40C)* 

-4F to 140F (-20C to 60C) 

Humidity 

20% to 80% RH noncondensing, 27C max wb 

93% RH 

Altitude 

9,843 ft (3 km) 

39,370 ft (12 km) 

*Maximum operating temperature is 95F (35C) when using tape media.