Cabinet

7700 Cabinet Planning and Installation

Space Requirements

Tools

Physical Specifications

Service Access

Cooling

Electrical Specifications

Site Planning Checklists

Access Route

Data Center Environment

Facility Power

Logistics

Safety Items

Tasks

Cabinet Tasks

3.  Cabling

4.  Powering On and Configuring the System

Glossary

Index

Cabinet

7700 Cabinet Planning and Installation

Use the following system specifications to ensure that the installation site is ready for the new Sun ZFS Storage 7700 system. Pay particular attention to specifications to determine if power and air conditioning requirements are met by your datacenter.

To view component diagrams and specifications, refer to the 7700 Overview section of the Sun ZFS Storage 7x20 Service Manual at http://wikis.sun.com/display/fishworks.

Space Requirements

Caution - Three people are required to offload the cabinet: two at the front and one at the rear.

Image

The table below lists specifications for the shipping package.

Item
Description
U.S.
Metric
1
Height
85.25 in
216.5 cm
2
Depth
52.5 in
133.3 cm
3
Width
45.5 in
115.5 cm
4
Unloading distance
15 ft
4.45 m
Maximum weight, storage system cabinet
1,970 lb
894 kg

Caution - The shipping pallet is designed so that the cabinet can only be unloaded in one direction. Orient the shipping container so that the label RAMPS ATTACH THIS SIDE is facing the direction the cabinet should be offloaded from the pallet. When you roll the cabinet off the shipping pallet, you will need a total distance of at least 15 feet/4.5 meters for safe maneuvering, as shown above.

Tools

During unpacking, you will need these tools to unpack the shipping package:

These tools are included in the shipping package:

Physical Specifications

The following figure shows the system cabinet.

Image
Figure Legend
1
Fan trays
5
Power supplies
2
Leaf controller cards (LCCs)
6
Rack controller card (RCC)
3
Disk trays
7
Storage controllers
4
Disk drives

The following table lists physical specifications for the storage system main cabinet.

Description
U.S.
Metric
Width
23.5 in
60 cm
Depth (without doors)
43.0 in
109 cm
Depth (with front and rear doors)
46.0 in
117 cm
Height
79.5 in
202 cm
Maximum weight, storage system cabinet
1,740 lb
790 kg
Clearance, front or rear of system for service access
48 in
122 cm
Clearance, above system
18 in
46 cm
Service Access

All customer replaceable units (CRUs) are accessed from the front or back of the cabinet. There are no CRUs inside the cabinet.

Caution - Access to the inside of the cabinet is limited to Sun Service personnel only. There are no CRUs inside of the cabinet.

If the system is located in a row of cabinets and an internal FRU must be replaced, the system must be moved forward or backward out of the row for removal of the side panels. The front and rear clearance values in the table above account for this movement.

Cooling

The following table lists the specifications for the main cabinet.

Cooling Specifications
Operating
Non-Operating
Maximum Heat output, main system
5300 W (estimated)
Ambient temperature range
5 to 35C/41 to 95F
0 to 50C/32 to 122F
Humidity range
20 - 80% relative humidity
8 - 80% relative humidity
Altitude range
3 km/12,000 ft.
12 km/40,000 ft.

The airflow patterns in the storage system are as follows:

The following figure shows the airflow patterns in the storage system.

Image

Underfloor Cooling Scheme

The following illustration shows underfloor cooling of the cabinet and is described in the table.

Image
Figure Legend
1
Front of System
2
Allow underfloor cooling at front and back
3
Warm air is ventilated from the top. Allow 18" of clearance.

Overhead Cooling Scheme

The following illustration shows overhead cooling of the cabinet and is described in the table.

Image
Figure Legend
1
Front of System
2
Overhead cooling should be directed at both front and back of system.
3
Warm air is ventilated from the top. Allow 18" of clearance.

Overhead Cooling Hot/Cold Aisle

The following illustration shows overhead cooling for hot/cold aisle and is described in the table.

Image
Figure Legend
1
Front of System
2
Overhead cooling in the cold aisle should be directed at the front of the system.
3
Warm air is ventilated from the top. Allow 18" of clearance.
4
Hot aisle ambient temperature cannot exceed 35C (95F)
Electrical Specifications

The following table lists the specifications for the main cabinet.

Electrical Specifications
Value
AC voltage range
200-240 VAC, 50-60 Hz
AC current, maximum for main cabinet (5300 W)
26.5A total
Power Cords
Description
Storage controller 0
2 power cords, rated at 10 A each, N+1 redundancy
Storage controller 1
2 power cords, rated at 10 A each, N+1 redundancy
Main cabinet
6 power cords, rated at 16 A each, divided into 2 separate circuits of 3 cords. Each circuit provides N+1 redundancy

Caution - The electrical power to the system must be controlled by external breaker switches. Do not plug in any power cables. Only power on the system by following the instructions in the Powering On and Configuration section of the Sun ZFS Storage 7x20 Installation Guide available at http://wikis.sun.com/display/fishworks.

Two separate electrical sources are required for redundant operation of the storage system main cabinet, as shown in the following figure.

Image
Figure Legend
1
Storage cabinet and storage controller power cords
4
Power source A
2
Wall power outlets
5
Power source B
3
Circuit breakers or wall-mounted power switches

Site Planning Checklists

Access Route

Confirm that the unloading specifications for the shipping package in Space Requirements have been addressed.

Requirements
Yes
No
NA
Has the Sun ZFS Storage 7700 Appliance location been allocated?
Is the location vacant for the new equipment?
Does the floor layout meet the equipment maintenance access requirements?
Is there adequate space available for maintenance?
Is the floor to ceiling height a minimum of 103.25 in (8.6 feet)?
Have cabinet stabilization measures been considered? (Leveling feet?)
Do you need to obtain permission to remove floor tiles to accommodate service?
Does the raised floor satisfy the weight requirements for the new hardware?
Are there cable routing channels?
Are there cable routing cutouts?
Data Center Environment

Confirm that the cooling specifications for the cabinet in Cooling Requirements have been addressed.

Requirements
Yes
No
NA
Does the computer room air handling meet temperature and humidity requirements?
Does the installation floor layout satisfy the ventilation requirements?
Will the equipment be positioned so that the exhaust air of one rack does not enter the air inlet of another rack?
Do the computer room air conditioners provide sufficient airflow?
Is airflow adequate to prevent hotspots?
Can the computer room continuously satisfy environmental requirements?
Can more vented floor tiles be obtained if required?
Facility Power

Confirm that the power specifications for the cabinet in Electrical Specifications have been addressed.

Requirements
Yes
No
NA
Do you know the required operating voltages and electrical current levels of the device and peripherals? As an aggregate, the system will draw 48amps at 208 volts. This needs to be split across two separate power grids and divided into smaller circuits.
Are separate power sources available for the new equipment at the designated location?
Are power outlets available for the new equipment at the designated location?
Are enough power outlets provided? 10 L6-20 total. Six L6-20/C19 (cabinet) and four L6-20/C13 (controllers) split across two separate power grids.
Are the circuit breakers for the equipment suitable in terms of voltage and current-carrying capacities?
Does the power frequency meet the equipment specifications?
Logistics

Confirm that the logistical requirements for the cabinet in Unpacking and Moving the Cabinet have been addressed.

Requirements
Yes
No
NA
Do you have contact information for data center personnel?
Is there security or access control for the data center?
Are laptops, cell phones, and cameras allowed in the data center?
Does the building have a delivery dock?
Is there a delivery/unpacking/staging area?
Is the delivery inside?
If the delivery is not inside, is the site prepared for uncrating?
Is the unpacking/staging area protected from the elements?
Does the building have an adequate receiving area?
Will sufficient moving personnel be available to install the hardware?
Are you prepared for uncrating and trash removal?Is uncrating of cabinet and cabinet trash removal required?
Are there any restrictions on delivery truck length, width or height?
Does the customer allow cardboard boxes and/or other packing material in the computer room?
If no, do ground level deliveries require a truck with a side rail lift ?
Is there a time constraint on dock access? If yes, provide time constraints.
Is tail-lift required on Delivery Carrier to unload the equipment at delivery dock?
Is delivery only required to end-user's loading bay or is delivery inside required?
Will any lifters, ramps, steel plates, or floor covers be required to place the equipment in the computer room?
Is a list of special equipment requirements needed by the delivery carrier available? (Non-Floor Damaging Rollers, Transport Dollies, Pallet Jacks, or Fork Lifts)
Have any special delivery options (including inside delivery and/or waste removal) been communicated while placing the order?
Safety Items

For your protection, observe the following safety precautions when setting up your equipment:

Requirements
Yes
No
NA
Is there an emergency power shutoff? Where?
Is there a fire protection system in the data center room?
Is the computer room adequately equipped to extinguish a fire?
Is antistatic flooring installed?
Is the floor below the raised floor free of obstacles and blockages?

Tasks

Cabinet Tasks

Unpacking and Moving the Cabinet

The following instructions illustrate how to unpack and move the 7700 cabinet. As a prerequisite to this task, familiarize yourself with the 7420/7720 storage controller rear panel section of the Sun ZFS Storage 7x20 Service Manual at http://wikis.sun.com/display/fishworks.

  1. Use a forklift or pallet jack to move the shipping carton to a location that is as close to the installation site as possible.
  2. Ensure that you have enough space to remove the storage system from the shipping pallet. See the Space Requirements section for dimensions.
  3. Cut the straps that hold the carton onto the shipping pallet.
  4. Remove the top of the carton, and unlock the sides of the carton.Image
  5. Remove the carton sides, top, and accessories kit.Image
  6. Remove the ramps from the pallet as shown in the following illustration.Image
  7. Install the pallet ramps. Ensure that you lock the ramps to the pallet skids and that you lower the ramp bolts so that they rest on the floor.Image
  8. Open the cabinet doors, and remove the shipping restraints.Image
  9. Check that the leveling feet have not lowered during transportation.
  10. With at least two other people, move the cabinet off of the pallet. Ensure that the cabinet does not tilt to either side while you are moving the cabinet. Never move the cabinet alone.Image
  11. Standing at both ends of the cabinet, move the storage system to the installation site. Caution: all four casters swivel. When moving the cabinet down ramps, do not allow it to turn unexpectedly. The front or rear door must always face the direction of travel. The cabinet can tip over if the cabinet is moved sideways up or down a ramp. Three people are required to move the cabinet: one person should be at the front to guide the movement and two at the rear.Image
  12. Lower all four of the stabilization feet as shown in the illustration.Image
  13. Complete Powering on and Configuration section of the Sun ZFS Storage 7x20 Installation Guide available at http://wikis.sun.com/display/fishworks.