C In-Rack Cabling Tables for Oracle Big Data Appliance X3-2

The tables in this appendix show the in-rack cable connections for Sun Server X3-2L-based Oracle Big Data Appliance racks. This appendix contains the following sections:

C.1 Cable Color Coding

The cables used in Oracle Big Data Appliance are color-coded as follows:

  • Black: InfiniBand cables or AC power jumper cables

  • Red: Integrated Lights Out Management (Oracle ILOM) Ethernet management cables

  • Blue: Gigabit Ethernet management (eth0) cables

C.2 Oracle Big Data Appliance Rack Layout

The following figures show the front and rear layouts for three configurations of Oracle Big Data Appliance X3-2: full rack, starter rack, and starter rack with one expansion kit.

Figure C-1 shows the layout of a full rack for Oracle Big Data Appliance X3-2.

Figure C-1 Oracle Big Data Appliance X3-2 Full Rack Layout

Description of Figure C-1 follows
Description of "Figure C-1 Oracle Big Data Appliance X3-2 Full Rack Layout"

Figure C-2 shows the layout of a starter rack for Oracle Big Data Appliance X3-2.

Figure C-2 Oracle Big Data Appliance X3-2 Starter Rack Layout

Description of Figure C-2 follows
Description of "Figure C-2 Oracle Big Data Appliance X3-2 Starter Rack Layout"

Figure C-3 shows the layout of an Oracle Big Data Appliance X3-2 starter rack with one expansion.

Figure C-3 Oracle Big Data Appliance X3-2

Description of Figure C-3 follows
Description of "Figure C-3 Oracle Big Data Appliance X3-2 "

C.3 Administrative Gigabit Ethernet Cable Connections

Table C-1 shows the cable connections for the administrative Gigabit Ethernet network (Net 0). The Ethernet switch is located in rack unit 21. The cables are 10 feet long and black.

Table C-1 Administrative Gigabit Ethernet Cabling

From Rack UnitFoot 1  Component To Ethernet Port

U39

Server 18

1

U37

Server 17

3

U35

Server 16

5

U33

Server 15

7

U31

Server 14

9

U29

Server 13

11

U27

Server 12

13

U25

Server 11

17

U23

Server 10

21

U22

NM2-IB Switch

45

U20

NM2-IB Switch

46

U18

Server 9

25

U16

Server 8

29

U14

Server 7

31

U12

Server 6

33

U10

Server 5

35

U8

Server 4

37

U6

Server 3

39

U4

Server 2

41

U2

Server 1

43

U1

NM2-IB Switch

47


Footnote 1 Un is the unit location in the rack, where n is the number.

C.4 Oracle Integrated Lights Out Manager Cable Connections

Table C-2 shows the cable connections from the servers to the Oracle ILOM switch. The Oracle ILOM ports on the servers are labeled Net Mgt and connect to the Cisco Ethernet switch located in rack unit 21.

Table C-2 Oracle ILOM Cabling

From Rack UnitFoot 1  Component Ethernet Port Cable Length Cable Color

U39

Server 18

4

10 feet

Red

U37

Server 17

6

10 feet

Red

U35

Server 16

8

10 feet

Red

U33

Server 15

10

10 feet

Red

U31

Server 14

12

10 feet

Red

U29

Server 13

14

10 feet

Red

U27

Server 12

18

10 feet

Red

U25

Server 11

22

10 feet

Red

U23

Server 10

26

10 feet

Red

U18

Server 9

26

10 feet

Red

U16

Server 8

30

10 feet

Red

U14

Server 7

32

10 feet

Red

U12

Server 6

34

10 feet

Red

U10

Server 5

36

10 feet

Red

U8

Server 4

38

10 feet

Red

U6

Server 3

40

10 feet

Red

U4

Server 2

42

10 feet

Red

U2

Server 1

44

10 feet

Red

PDU-A

PDU-A

15

1 meter

White

PDU-B

PDU-B

20

1 meter

White

Not applicable

Service

48

10 feet

Blue


Footnote 1 Un is the unit location in the rack, where n is the number.

C.5 Single-Phase Power Distribution Unit Cable Connections

Table C-3 shows the connections for single-phase cabling from each power distribution unit (PDU) to the power supplies in the rack. The cables terminate at PDU-A on the left and are routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four.

Table C-3 Single-Phase PDU Cabling

Rack UnitFoot 1  PDU-A/PS-00 PDU-B/PS-01 Cable Length

U39

G5-6

G0-0

2 meters

U37

G5-3

G0-3

2 meters

U35

G5-0

G0-6

2 meters

U33

G4-6

G1-0

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-6

G2-0

2 meters

U25

G3-5

G2-1

2 meters

U23

G3-3

G2-3

2 meters

U24

G3-1

G2-5

2 meters

U23

Not applicable

G3-0

included

U22

G2-5

G3-1

1 meter

U21

G3-0

G2-6

2 meters

U20

G2-4

G3-2

2 meters

U18

G2-2

G3-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G3-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G0-0

G5-6

2 meters


Footnote 1 Un is the unit location in the rack, where n is the number.

C.6 Three-Phase Power Distribution Unit Cable Connections

Table C-4 describes three-phase cabling from each power distribution unit (PDU) to the power supplies in the rack. The cables are terminated to PDU-A on the left, are routed to the right to enter the cable management arm (CMA), and are bundled in groups of four.

Table C-4 Three-Phase PDU Cabling

Rack UnitFoot 1  PDU-A/PS-00 PDU-B/PS-01 Cable Length

U39

G5-6

G2-0

2 meters

U37

G5-3

G2-3

2 meters

U35

G5-0

G2-6

2 meters

U33

G4-6

G1-0

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-6

G0-0

2 meters

U25

G3-5

G0-1

2 meters

U23

G3-3

G0-3

2 meters

U24

G3-1

G0-5

2 meters

U23

Not applicable

G5-0

Included

U22

G2-5

G5-1

1 meter

U21

G3-0

G0-6

2 meters

U20

G2-4

G5-2

2 meters

U18

G2-2

G5-4

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G5-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G3-0

2 meters

U4

G0-4

G3-2

2 meters

U2

G0-2

G3-4

2 meters

U1

G0-0

G3-6

2 meters


Footnote 1 Un is the unit location in the rack, where n is the number.

C.7 In-Rack InfiniBand Switch-to-Switch Cable Connections

Table C-5 lists the location, ports, and cables for the InfiniBand connections from switch to switch.

Table C-5 InfiniBand Switch-to-Switch Cabling

From InfiniBand Switch Rack UnitFoot 1  Port To InfiniBand Switch Rack UnitFootref 1 Port Cable Length Description

U20

9B

U22

9A

2 meters

Leaf to leaf

U20

10B

U22

10A

2 meters

Leaf to leaf

U20

11B

U22

11A

2 meters

Leaf to leaf

U20

8A

U22

8A

2 meters

Leaf to leaf

U20

9A

U22

9B

2 meters

Leaf to leaf

U20

10A

U22

10B

2 meters

Leaf to leaf

U20

11A

U22

11B

2 meters

Leaf to leaf

U1

0B

U20

8B

3 meters

Spine to leaf

U1

1B

U22

8B

3 meters

Spine to leaf


Footnote 1 Un is the unit location in the rack, where n is the number.

Figure C-4 identifies the locations of the ports on a Sun Network QDR InfiniBand Gateway switch.

Figure C-4 Sun Network QDR InfiniBand Gateway Ports

Description of Figure C-4 follows
Description of "Figure C-4 Sun Network QDR InfiniBand Gateway Ports"

C.8 In-Rack InfiniBand Switch-to-Server Cable Connections

Table C-6 lists the location, ports, and cables for the InfiniBand connections from the leaf switches to the servers.

Table C-6 InfiniBand Switch-to-Server Cabling

From InfiniBand Switch Rack UnitFoot 1  Port To Rack UnitFootref 1 PortFoot 2  Cable Length

U22

0A

U39

PCIe 3 P1

3 meters

U22

0B

U37

PCIe 3 P1

3 meters

U22

1A

U35

PCIe 3 P1

3 meters

U22

1B

U33

PCIe 3 P1

3 meters

U22

2A

U31

PCIe 3 P1

3 meters

U22

2B

U29

PCIe 3 P1

3 meters

U22

3A

U27

PCIe 3 P1

3 meters

U22

3B

U25

PCIe 3 P1

2 meters

U22

4A

U23

PCIe 3 P1

2 meters

U20

0A

U39

PCIe 3 P2

3 meters

U20

0B

U37

PCIe 3 P2

3 meters

U20

1A

U35

PCIe 3 P2

3 meters

U20

1B

U33

PCIe 3 P2

3 meters

U20

2A

U31

PCIe 3 P2

3 meters

U20

2B

U29

PCIe 3 P2

3 meters

U20

3A

U27

PCIe 3 P2

3 meters

U20

3B

U25

PCIe 3 P2

2 meters

U20

4A

U23

PCIe 3 P2

2 meters

U20

4B

U18

PCIe 3 P1

2 meters

U20

12A

U16

PCIe 3 P1

2 meters

U20

12B

U14

PCIe 3 P1

3 meters

U20

13A

U12

PCIe 3 P1

3 meters

U20

13B

U10

PCIe 3 P1

3 meters

U20

14A

U8

PCIe 3 P1

3 meters

U20

14B

U6

PCIe 3 P1

3 meters

U20

15A

U4

PCIe 3 P1

3 meters

U20

15B

U2

PCIe 3 P1

3 meters

U22

4B

U18

PCIe 3 P2

2 meters

U22

12A

U16

PCIe 3 P2

2 meters

U22

12B

U14

PCIe 3 P2

3 meters

U22

13A

U12

PCIe 3 P2

3 meters

U22

13B

U10

PCIe 3 P2

3 meters

U22

14A

U8

PCIe 3 P2

3 meters

U22

14B

U6

PCIe 3 P2

3 meters

U22

15A

U4

PCIe 3 P2

3 meters

U22

15B

U2

PCIe 3 P2

3 meters


Footnote 1 Un is the unit location in the rack, where n is the number.

Footnote 2 Pn is the InfiniBand port, where n is the port number.