4.3 Install Oracle Virtual Compute Appliance X3-2 in Its Allocated Space

4.3.1 Move Oracle Virtual Compute Appliance X3-2
4.3.2 Stabilize Oracle Virtual Compute Appliance X3-2
4.3.3 Stabilize Oracle Virtual Compute Appliance X3-2 Using Leveling Feet
4.3.4 Stabilize Oracle Virtual Compute Appliance X3-2 Using Mounting Brackets
4.3.5 Attach a Ground Cable (Optional)
4.3.6 Remove the F1-15 Director Switch Bracket

This section describes each phase of the hardware installation procedure for Oracle Virtual Compute Appliance X3-2.

4.3.1 Move Oracle Virtual Compute Appliance X3-2

The following procedure describes how to move Oracle Virtual Compute Appliance X3-2:

  1. Ensure that the rack doors are closed and secured.

  2. Ensure that the leveling and stabilizing feet on the rack are raised and out of the way.

  3. Push the system from the back of the rack to the installation site.

    Caution

    Never attempt to move Oracle Virtual Compute Appliance X3-2 by pushing on the rack side panels. Pushing on the rack side panels can tip over the rack. This action can cause serious personal injury or death as well as damage to the equipment.

    When moving Oracle Virtual Compute Appliance X3-2 to the installation site, the front casters do not pivot; you must steer the unit by moving the rear casters. You can safely maneuver the system by carefully pushing it. See Figure 4.2.

    It is preferred to use three people to move the rack: one person in front and two persons in back to help guide the rack. When transporting configured racks from one location to another, take care to move them slowly, 0.65 meters per second (2.13 feet per second) or slower.

    Carefully examine the transportation path. Avoid obstacles such as doorways or elevator thresholds that can cause abrupt stops or shocks. Go around obstacles by using ramps or lifts to enable smooth transport.

    Caution

    Never tip or rock Oracle Virtual Compute Appliance X3-2 because the rack can fall over.

    Figure 4.2 Carefully Push Oracle Virtual Compute Appliance X3-2 From the Back of the Rack

    Figure showing Oracle Virtual Compute Appliance X3-2 being pushed from the back of the rack.

  4. When the rack is at the installation site, verify that no components or connections have become dislodged or disconnected during transport. If necessary, re-attach components and cables properly.

4.3.2 Stabilize Oracle Virtual Compute Appliance X3-2

After moving Oracle Virtual Compute Appliance X3-2 to the installation site, stabilize the rack to ensure that it does not move or tip over. You can stabilize the rack permanently by extending the rack leveling feet, using mounting brackets, or both. After installation, use the leveling feet and the brackets to stabilize the system.

4.3.3 Stabilize Oracle Virtual Compute Appliance X3-2 Using Leveling Feet

The rack contains four leveling feet that can be lowered to stabilize the rack. The leveling feet can be used even when the rack is permanently secured to the floor. To adjust the leveling feet, do the following:

  1. Locate the four leveling feet at the bottom four corners of the rack. See Figure 4.3.

    Figure 4.3 Location of Leveling Feet on Rack

    This figure shows the location of the leveling feet on the rack.

    Table 4.2 Figure Legend

    Item

    Description

    1

    Distance from the edge of the mounting feet to the side of the rack is 33.75 mm (1.33 inches)

    2

    Width from the outside edges of the leveling feet is 532.5 mm (20.96 inches)

    3

    Width from the inside edges of the leveling feet is 429 mm (16.89 inches)

    4

    Distance from the edge of the feet to the front rack surface is 73.75 mm (2.90 inches)

    5

    Depth of the outside edges of the leveling feet is 1058.5 mm (41.67 inches)

    6

    Distance from the edge of the leveling feet to the rear rack surface is 32.5 mm (1.28 inches)

    7

    Distance from the center of front casters to the side of the rack is 86.7 mm (3.41 inches)

    8

    Width between the center of the front casters is 426.6 mm (16.80 inches)

    9

    Distance from the center of the rear casters to the rear of the rack is 173.7 mm (6.83 inches)

    10

    Depth between the front and rear casters is 828.6 mm (32.62 inches)

    11

    Distance between the rear casters and the rear of the rack is 162.4 mm (6.39 inches)

    12

    Distance from the center of rear casters to the side of the rack is 96.4 mm (3.80 inches)

    13

    Width between the center of the rear casters is 407.2 mm (16.03 inches)


  2. Using the SW 12-mm wrench, lower the leveling feet to the floor. See Figure 4.4.

    When lowered correctly, the four leveling feet should support the full weight of Oracle Virtual Compute Appliance X3-2.

    Figure 4.4 Securing the Rack Using the Leveling Feet

    This figure shows the rack being secured using the leveling feet.

4.3.4 Stabilize Oracle Virtual Compute Appliance X3-2 Using Mounting Brackets

The rack can be permanently mounted to the installation site floor using the same four mounting brackets that secured the rack to the shipping pallet. Use the front and rear brackets to stabilize the rack to the installation floor. Prepare the installation site by drilling four holes into the floor. Before permanently stabilizing the Oracle Virtual Compute Appliance X3-2 rack using the mounting brackets, drill the mounting holes.

  1. Obtain four bolts and washers to mount the system to the floor.

    The bolt holes in the mounting bracket have a 10-mm diameter.

    Oracle does not provide mounting bolts because different floors require different bolt types and strengths.

  2. See Figure 4.5 to find the location and dimensions of the mounting brackets.

    Figure 4.5 Location of Mounting Brackets on Oracle Virtual Compute Appliance X3-2 Rack

    This figure shows the location of the mounting brackets on the Oracle Virtual Compute Appliance X3-2 rack.

    Table 4.3 Figure Legend

    Item

    Description

    1

    Mounting bracket location

    2

    Mounting bracket dimensions

    3

    Rack rear

    4

    Rack side

    5

    Rack front


  3. Position the Oracle Virtual Compute Appliance X3-2 rack over the drilled holes.

    Figure 4.6 shows the bottom view of the system, and the location for the mounting hole and floor cutout dimensions.

    Figure 4.6 Bottom View of Oracle Virtual Compute Appliance X3-2 Rack Showing Mounting Hole and Floor Cutout Dimensions

    This figure shows the bottom view of Oracle Virtual Compute Appliance X3-2 mounting hole and floor cutout dimensions.

    Table 4.4 Figure Legend

    Item

    Description

    1

    Distance from mounting bracket to the edge of the rack is 113 mm (4.45 inches)

    2

    Width between the centers of the mounting hole slots is 374 mm (14.72 inches)

    3

    Distance between mounting bracket to the edge of the rack is 113 mm (4.45 inches)

    4

    Distance between the centers of the front and rear mounting hole slots is 1120 mm (44.1 inches)

    5

    Depth of cable-routing floor cutout is 330 mm (13 inches)

    6

    Distance between the floor cutout and the edge of the rack is 160 mm (6.3 inches)

    7

    Width of cable-routing floor cutout is 280 mm (11 inches)


  4. (Optional) If you plan to route data or power distribution unit (PDU) power cords down through the bottom of the rack, you will need to cut a hole in the installation site floor. Cut a rectangular hole below the rear portion of the rack, between the two rear casters and behind the RETMA (Radio Electronics Television Manufacturers Association) rails.

    Figure 4.7 shows the base positions of the rack from the bottom.

    Figure 4.7 Base Position to Measure

    Figure showing the base positions of the rack from the bottom.

    Caution

    Do not create a hole where the rack casters or leveling feet brackets will be placed.

  5. Open the front and rear Oracle Virtual Compute Appliance X3-2 rack doors.

  6. Using a 6-mm hexagon Allen wrench key, install the mounting brackets to the rack. See Figure 4.8.

    Figure 4.8 Securing Oracle Virtual Compute Appliance X3-2 Using Mounting Brackets

    Figure showing Oracle Virtual Compute Appliance X3-2 being secured using mounting brackets.

  7. Using bolts and washers that are appropriate for your installation site, permanently mount your system to the floor using the four mounting brackets. See Figure 4.8.

    Note

    The bolts that are required for securing the Oracle Virtual Compute Appliance X3-2 rack to the floor vary depending on the installation location. Select bolts that are appropriate for your location.

  8. Firmly tighten all of the bolts that secure the mounting brackets to the Oracle Virtual Compute Appliance X3-2 rack side doors and to the floor.

4.3.5 Attach a Ground Cable (Optional)

Oracle Virtual Compute Appliance X3-2 power distribution units (PDUs) achieve earth ground through their power cords. Final chassis ground is achieved by way of the ground prong when you connect the power cord to a socket. For additional grounding, attach a chassis earth ground cable to the system. The additional ground point enables electrical current leakage to dissipate more efficiently.

Caution

The PDU power input lead cords and the ground cable must reference a common earth ground. If they do not, then a difference in ground potential can be introduced. If you are unsure of your facility's PDU receptacle grounding, then do not install a ground cable until you confirm that there is a proper PDU receptacle grounding. If a difference in ground potential is apparent, then you must take corrective action.

Note

A grounding cable is not shipped with Oracle Virtual Compute Appliance X3-2.

  1. Ensure that the installation site has properly grounded the power source in the data center. The facility PDU must have earth ground.

  2. Ensure that all grounding points, such as raised floors and power receptacles, reference the facility ground.

  3. During manufacturing, the ground cable attachment area might be a painted or coated surface. Ensure that direct, metal-to-metal contact is made for this installation.

  4. Attach the ground cable to one of the attachment points located at the bottom rear of the system frame. See Figure 4.9.

    The attachment point is an adjustable bolt that is inside the rear of the system cabinet on the right side.

    Figure 4.9 Earth Ground Attachment Bolt Location

    Figure showing the earth ground attachment location on the Oracle Virtual Compute Appliance X3-2 rack.

4.3.6 Remove the F1-15 Director Switch Bracket

Each F1-15 Director Switch is shipped with a bracket that secures the IO modules in their installed position. This shipping bracket is removed after the Oracle Virtual Compute Appliance X3-2 is installed and stabilized in its allocated space.

  1. Locate the shipping bracket at the rear of the F1-15 Director Switch.

  2. Pull the tabs on the left and right hand side towards the center to unlock the bracket.

    Figure 4.10 Unlocking and removing the bracket securing the IO modules in the F1-15 Director Switch

    This figure shows how the shipping bracket securing the IO modules in the F1-15 Director Switch is unlocked and removed.

  3. Carefully pull the bracket away from the F1-15 Director Switch and out of the rack.

  4. Repeat these steps to remove the shipping bracket on the second F1-15 Director Switch.