PDU Hardware Specifications

The PDUs used in a not-racked Oracle FS System installation must provide redundancy for both external AC power source and internal AC power distribution to the components. The PDUs must provide sufficient current to meet the sum of the requirements for the Oracle FS System components.

Oracle PDUs might be purchased for use with non-Oracle racks. The Oracle FS System component power cords have been designed to work with vertical style Oracle or third party PDUs. Non-Oracle PDUs must be compatible with Oracle component power cord lengths and plug types. Non-Oracle PDUs must be mounted in a manner such that the power cords provided by Oracle might be used and the PDUs do not obstruct the ability to replace field replaceable units (FRUs) and customer serviceable units (CRUs).

While planning rack-space, ensure that adequate space is also allocated for the PDUs, if using non-Oracle PDUs.

The following tables provide information on the various PDUs for the Oracle FS Systems, with the assumption that there are two PDUs in each rack.

Note: The term “Ph” stands for “phase” in the above tables.
Table 1 Low voltage dual phase PDU for Oracle Flash Storage Systems

Low Voltage

2Ph (2W + ground)

kVA size

10 kVA

Marketing part number

7104982

Phase

1 Phase

No grounded neutral conductors are provided in the two input cords.

Voltage input

2x [2Ph (2W+ground)], 208Vac, 50/60 Hz, maximum. 24A per phase

Can be connected to input sources in the range of 200V – 240V AC (nominal)

Number of input cords and plug type

2x NEMA L6-30P

Number of data center receptacles and type

2x NEMA L6-30R

Maximum input current for each cord

24A

Outlet receptacles (number/type)

42/C13 (seven for each outlet group)

6/C19 (one for each outlet group)

Outlet groups for each PDU

6

PDU power cord length

2 meters (6.6 feet)

PDU power cords are 4 m (13 ft) long, but only 2 m (6.6 ft) are usable outside of the cabinet.

Table 2 Low voltage three-phase PDU for Oracle Flash Storage Systems

Low Voltage

3Ph (3W + ground)

kVA size

15 kVA

Marketing part number

7104979

Phase

3

No grounded neutral conductors are provided in the input cords.

Voltage input

3Ph [(3W+ground)] 208Vac, 50/60 Hz, maximum. 40A per phase

Can be connected to Ph-Ph input sources in the range of 190V – 220V AC (nominal)

Number of input cords and plug type

1x IEC 309, 60A (Hubbell C460P9W or equivalent)

Number of data center receptacles and type

1x IEC 309, 60A (Hubbell 460R9S or equivalent)

Maximum input current for each cord

40A

Outlet receptacles (number/type)

42/C13 (seven for each outlet group)

6/C19 (one for each outlet group)

Outlet groups for each PDU

6

PDU power cord length

2 meters (6.6 feet)

PDU power cords are 4 meters (13 feet) long, but sections are connected for internal routing in the rack.

Table 3 High voltage single phase PDU for Oracle Flash Storage Systems

High Voltage

1Ph (2W + ground)

kVA size

10 kVA

Marketing part number

7104983

Phase

1

Voltage input

2x [2Ph. (2W+ground)] 230Vac, 50 Hz, maximum. 25A per phase

Can be connected to Ph-N input sources in the range of 220V – 240V AC (nominal)

Number of input cords and plug type

2x IEC 309, 32A (Hubbell 332P6S or equivalent)

Number of data center receptacles and type

2x IEC 309, 32A (Hubbell 332R6S or equivalent)

Maximum input current for each cord

25A

Outlet receptacles (number/type)

42/C13 (seven for each outlet group)

6/C19 (one for each outlet group)

Outlet groups for each PDU

6

PDU power cord length

2 meters (6.6 feet)

PDU power cords are 4 meters (13 feet) long, but sections are connected for internal routing in the rack.

Table 4 High voltage three-phase PDU for Oracle Flash Storage Systems

High Voltage

3Ph (5W + ground)

kVA size

15 kVA

Marketing part number

7104980

Phase

3

Voltage input

[3Ph. (4W+ground)] 230/400Vac, 50/60 Hz, maximum. 25A per phase

Can be connected to Ph-N input sources in the range of 220V – 240V AC (nominal)

Number of input cords and plug type

1x IEC 309, 32A (Hubbell 532P6S or equivalent)

Number of data center receptacles and type

1x IEC 309, 32A (Hubbell 532R6S or equivalent)

Maximum input current for each cord

25A

Outlet receptacles (number/type)

42/C13 (seven for each outlet group)

6/C19 (one for each outlet group)

Outlet groups for each PDU

6

PDU power cord length

2 meters (6.6 feet)

PDU power cords are 4 meters (13 feet) long, but sections are connected for internal routing in the rack.