Solaris Common Messages and Troubleshooting Guide

WARNING: FAN FAILURE check if fans are still spinning

Cause

A SPARCcenterTM 2000/2000E might get one of these error messages, WARNING: FAN FAILURE check if fans are still spinning or WARNING: FAN FAILURE still sensed, displayed on the console screen at any time, with a record of the event in /var/adm/messages.

Action

The error itself is descriptive and self-explanatory, and you might suspect that a hardware problem occurred with the system's blower or fan assembly located at the top-most rear of the system cabinet.

Upon further investigation you note that the blower is indeed spinning at a good rate. Given that, you should then check to see if the "AC Dist to Blower to Filter to Keyswitch Harness" plug/adapter is plugged in correctly. Two cable assemblies connect the blower assembly to the unit's power supply. One is the "power supply" cable and the other is the "AC Dist to Blower to Filter to Keyswitch Harness."

Once the harness is securely connected, you see another message, NOTICE: FAN RECOVERED, logged on the system's console screen, or, if missed, it is in /var/adm/messages.