Power Guidelines

When preparing to install your Acme Packet 6300/6350:

  • Ensure that the installation location has access to adequate power and grounding. Separate circuits should be available for each of the two Acme Packet 6300/6350 power supplies.
  • The Acme Packet 6300/6350 may only be powered by AC or DC circuits at one time; mixed power supply configurations are unsupported.
  • Never use extension cords when powering an Acme Packet 6300/6350.
  • Use grounded, 3-conductor circuits.
  • A local earth ground must be available.
  • For DC, the installation must provide over current rated at 35A.
  • A service disconnect must be provided for each power supply that is clearly marked and is nearby the equipment.

    Note:

    Connect each of the Acme Packet 6300/6350 power supplies to a separate circuit. If both supplies are connected to outlets on the same circuit, the Acme Packet 6300/6350 will lose power to both supplies if that circuit loses power. In that case, the whole Acme Packet 6300/6350 would lose power.