32326 – Breaker panel monitoring error

Alarm Group: PLAT

Description: This alarm indicates a failure in the hardware and/or software that monitors the breaker panel. This could mean there is a problem with the file I/O libraries, the serial device drivers, or the serial hardware itself.

Note: When this alarm occurs, the system is unable to monitor the breaker panel for faults. Thus, if this alarm is detected, it is imperative that the breaker panel be carefully examined for the existence of faults. The LEDs on the breaker panel will be the only indication of the occurrence of either alarm:
  • 32324 – Breaker panel feed error
  • 32325 – Breaker panel breaker error

until the Breaker Panel Monitoring Error has been corrected.

Severity: Major

Instance: May include AlarmLocation, AlarmId, AlarmState, AlarmSeverity, and bindVarNamesValueStr

HA Score: Normal

Auto Clear Seconds: 0 (zero)

OID: tpdBrkPnlMntError

Recovery

  1. Verify that the same alarm is displayed by multiple servers:

    • If this alarm is displayed by only one server, the problem is most likely to be with the cable or the server itself. Look for other alarms that indicate a problem with the server and perform the recovery procedures for those alarms first.
    • If this alarm is displayed by multiple servers, go to the next step.

  2. Verify that both ends of the labeled serial cables are secured properly (for locations of serial cables, see the appropriate hardware manual).
  3. If the alarm has not been cleared, contact My Oracle Support (MOS).