5000000000000080 – Server temperature warning

Alarm Type: TPD

Description: This alarm indicates that the internal temperature within the server is outside of the normal operating range. A server Fan Failure may also exist along with the Server Temperature Warning.

Severity: Minor

OID: tpdTemperatureWarningNotify 1.3.6.1.4.1.323.5.3.18.3.1.3.8

Alarm ID: TKSPLATMI85000000000000080

Recovery

  1. Ensure that nothing is blocking the fan's intake. Remove any blockage.
  2. Verify that the temperature in the room is normal. If it is too hot, lower the temperature in the room to an acceptable level.

    Server Environmental Conditions
    Ambient Temperature

    Operating: 5 degrees C to 40 degrees C

    Exceptional Operating Limit: 0 degrees C to 50 degrees C

    Storage: -20 degrees C to 60 degrees C

    Relative Humidity

    Operating: 5% to 85% non-condensing

    Storage: 5% to 950% non-condensing

    Elevation

    Operating: -300m to +300m

    Storage: -300m to +1200m

    Heating, Ventilation, and Air Conditioning

    Capacity must compensate for up to 5100 BTUs/hr for each installed frame.

    Calculate HVAC capacity as follows:

    Determine the wattage of the installed equipment. Use the formula: watts x 3.143 = BTUs/hr

    Note: Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. The alarm may take up to five minutes to clear after conditions improve. It may take about ten minutes after the room returns to an acceptable temperature before syscheck shows the alarm cleared.

  3. Verify that the temperature in the room is normal. If it is too hot, lower the temperature in the room to an acceptable level.

    Note: Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. It may take about ten minutes after the room returns to an acceptable temperature before the alarm cleared.

  4. Replace the filter (refer to the appropriate hardware manual).

    Note: Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. It may take about ten minutes after the filter is replaced before the alarm cleared.