PowerVar Single Phase Desktop UPS - Estimated Run Times

The following tables show estimated run times based on the load in percent of the four approved single phase desktop UPS systems.

The amount of back-up time available is directly related to the VA rating of the UPS utilized. The closer you get to the rated capacity of the UPS, the less back-up time you will have. In addition, make sure to consider battery age.

The runtimes shown in the tables are estimates from PowerVar using new, fully charged batteries at an ambient temperature of 25°C. Depending on the operating environment, UPS batteries lose between 20% and 40% of their capacity after three years. A typical shutdown takes several minutes to perform; therefore, give careful consideration to UPS capacity vs. battery life.

Table 25-5 Estimated Load Times of ABCEG251-11 (Part Number 700247-092-PT)

Load Item 10% Load Time 20% Load Time 30% Load Time 40% Load Time 50% Load Time 60% Load Time 70% Load Time 80% Load Time 90% Load Time 100% Load Time

Volts

121

122

122

122

122

122

122

122

122

121

Amps

0.15

0.30

0.44

0.59

0.74

0.87

1.01

1.17

1.31

1.46

Watts

17.5

3

52.5

70

87.5

105

122

140

158

175

Run Time (Mins)

140

48

56

43

23

19

16

13

12

10

Table 25-6 Estimated Load Times of ABCEG401-11 (Part Number 700247-093-PT)

Load Item 10% Load Time 20% Load Time 30% Load Time 40% Load Time 50% Load Time 60% Load Time 70% Load Time 80% Load Time 90% Load Time 100% Load Time

Volts

122

121

120

121

122

121

121

121

120

119

Amps

0.24

0.46

0.70

0.92

1.15

1.40

1.63

1.88

2.10

2.36

Watts

28

5

84

112

140

168

196

224

252

280

Run Time (Mins)

65

30

28

19

15

13

11

8

7

6

Table 25-7 Estimated Load Times of ABCEG601-11 (Part Number 700247-094-PT)

Load Item 10% Load Time 20% Load Time 30% Load Time 40% Load Time 50% Load Time 60% Load Time 70% Load Time 80% Load Time 90% Load Time 100% Load Time

Volts

122

122

121

121

121

122

121

121

116

114

Amps

0.35

0.69

1.04

1.39

1.74

2.07

2.44

2.78

3.26

3.66

Watts

4

84

126

168

210

252

294

336

378

420

Run Time (Mins)

90

55

39

30

24

18

14

11

19

7

Table 25-8 Estimated Load Times of ABCEG800-11 (Part Number 700247-095-PT)

Load Item 10% Load Time 20% Load Time 30% Load Time 40% Load Time 50% Load Time 60% Load Time 70% Load Time 80% Load Time 90% Load Time 100% Load Time

Volts

118

119

118

118

117

119

118

118

118

120

Amps

0.44

0.87

1.32

1.76

2.21

2.63

3.08

3.52

3.94

4.36

Watts

5

110

165

224

280

335

395

450

500

560

Run Time (Mins)

77

46

32

23

17

14

11

10

8

6