32324 - Breaker panel feed error
- Alarm Group:
- PLAT
- Description:
- This alarm indicates that the
server
is not receiving information from the breaker panel relays.
- Severity:
- Major
- Instance:
- May include AlarmLocation, AlarmId, AlarmState,
AlarmSeverity, and bindVarNamesValueStr
- HA Score:
- Normal
- Auto Clear Seconds:
- 0 (zero)
- OID:
- tpdBrkPnlFeedError
- Alarm ID:
- TKSPLATMA25
Recovery:
-
Verify that the same alarm is displayed by multiple
servers:
- If this alarm is displayed by only one
server,
the problem is most likely to be with the cable or the
server
itself. Look for other alarms that indicate a problem with the
server
and perform the recovery procedures for those alarms first.
- If this alarm is displayed by multiple
servers,
go to the next step.
-
Verify that the cables that connect the
servers
to the breaker panel are not damaged and are securely fastened to both the
Alarm Interface ports on the breaker panel and to the serial ports on both
servers.
-
If the problem has not been resolved, it is
recommended to contact
My Oracle Support (MOS) to request that the breaker panel be replaced.