32316 - Server power feed error
- Alarm Group:
- PLAT
- Description:
- This alarm indicates that one of the power feeds to the server has failed. If this alarm occurs in conjunction with any Breaker Panel alarm, there might be a problem with the breaker panel.
- Severity:
- Major
- Instance:
- May include AlarmLocation, AlarmId, AlarmState, AlarmSeverity, and bindVarNamesValueStr
- HA Score:
- Normal
- Auto Clear Seconds:
- 0 (zero)
- OID:
- tpdPowerFeedError
- Alarm ID:
- TKSPLATMA17
Recovery:
- Verify that all the server power feed cables to the server that is reporting the error are securely connected.
- Check to see if the alarm has cleared
- If the alarm has been cleared, the problem is resolved.
- If the alarm has not been cleared, continue with the next step.
- Follow the power feed to its connection on the power source. Ensure that the power source is ON and that the power feed is properly secured.
- Check to see if the alarm has cleared
- If the alarm has been cleared, the problem is resolved.
- If the alarm has not been cleared, continue with the next step.
- If the power source is functioning properly and the wires are all secure, have an electrician check the voltage on the power feed.
- Check to see if the alarm has cleared
- If the alarm has been cleared, the problem is resolved.
- If the alarm has not been cleared, continue with the next step.
- If the problem has not been resolved, it is recommended to contact My Oracle Support (MOS).