Alarm Type: TPD
Description: This alarm indicates that the internal temperature within the server is outside of the normal operating range. A server Fan Failure may also exist along with the Server Temperature Warning.
Severity: Minor
OID: tpdTemperatureWarningNotify 1.3.6.1.4.1.323.5.3.18.3.1.3.8
Alarm ID: TKSPLATMI85000000000000080
Recovery
Ambient Temperature | Operating: 5 degrees C to 40 degrees C Exceptional Operating Limit: 0 degrees C to 50 degrees C Storage: -20 degrees C to 60 degrees C |
Relative Humidity | Operating: 5% to 85% non-condensing Storage: 5% to 950% non-condensing |
Elevation | Operating: -300m to +300m Storage: -300m to +1200m |
Heating, Ventilation, and Air Conditioning | Capacity must compensate for up to 5100 BTUs/hr for each installed frame. Calculate HVAC capacity as follows: Determine the wattage of the installed equipment. Use the formula: watts x 3.143 = BTUs/hr |