0163 - 1114-S Clock Failed

This message indicates the secondary BITS clock for the TDM card in slot 1114 has failed.

Example
RLGHNCXA21W 00-12-07 12:01:43 EST  EAGLE 35.0.0 
*   0014.0163  * CLOCK SYSTEM    1114-S clock failed

Alarm Level: Minor

Recovery

  1. Use the rept-stat-clk command to determine the current clock configuration.
    Example of the output:
    tekelecstp 00-04-23  13:34:15 EST  EAGLE 35.0.0
        CARD LOC= 1114 (Active   )    CARD LOC= 1116 (Isolated )
        PRIMARY BITS   = Active       PRIMARY BITS   = Fault
        SECONDARY BITS = Fault        SECONDARY BITS = Fault
                                      PST           SST       AST
        SYSTEM CLOCK                  IS-NR         ACTIVE    ALMINH 
        # Cards using CLK A = 9     # Cards with bad CLK A = 0
        # Cards using CLK B = 0     # Cards with bad CLK B = 9
        # Cards using CLK I = 0
        Command Completed.
  2. The primary BITS clock should be active.
    Reseat the TDM card in slot 1114.
  3. If the problem persists, replace the TDM card in slot 1114.
    Refer to the Maintenance Manual for card removal/replacement procedures.