32507 - Server temperature warning

Alarm Group:
PLAT
Description:
This alarm indicates that the internal temperature within the server is outside of the normal operating range. A server Fan Failure may also exist along with the Server Temperature Warning.
Severity:
Minor
Instance:
May include AlarmLocation, AlarmId, AlarmState, AlarmSeverity, and bindVarNamesValueStr
HA Score:
Normal
Auto Clear Seconds:
0 (zero)
OID:
tpdServerTemperatureWarning
Alarm ID:
TKSPLATMI8

Recovery:

  1. Ensure that nothing is blocking the fan intake. Remove any blockage.
  2. Verify that the temperature in the room is normal. If it is too hot, lower the temperature in the room to an acceptable level.

    Note:

    Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. It may take about ten minutes after the room returns to an acceptable temperature before the alarm cleared.
  3. Run syscheck.
  4. Replace the filter (refer to the appropriate hardware manual).

    Note:

    Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. It may take about ten minutes after the filter is replaced before the alarm cleared.
  5. Run syscheck.
  6. If the problem has not been resolved, it is recommended to contact unresolvable-reference.htm#GUID-DD0927BD-FD0B-4CEB-86E9-98A33C12D4E0.