1.1 Space

Learn about the space and maintenance access requirements for Oracle Public Cloud Machine (OPCM).

All OPCM models use the same rack, and have the same space and maintenance access requirements.

The space and maintenance requirements are as follows:

Table 1-1 OPCM Space Requirements

Description Millimeters (mm) Inches (”)
Height 1998 mm 78.66”
Minimum ceiling height for the cabinet (measured from true or raised floor) 2300 mm + 914 mm (for top clearance) 90” + 36”
Width 600 mm with side panels 23.62”
Required space to remove the side panels 675. 64 mm 26.6”
Depth from front door handle to rear door handle 1200 mm 47.24”
Depth with doors removed 1112 mm 43.78”
Top, front, and rear maintenance access requirement 914 mm 36”

Note:

The space above the cabinet and its surroundings must not restrict the movement of cool air between the air conditioner and the cabinet, or the movement of hot air coming out of the top of the cabinet.

If deploying the ZS3 Storage Expansion rack, the space and maintenance requirements are as follows:

Table 1-2 OPCM ZS3 Storage Expansion Rack Space Requirements

Description Millimeters (mm) Inches (”)
Height 1998 mm 78.66”
Minimum ceiling height for the cabinet (measured from true or raised floor) 2300 mm + 914 mm (for top clearance) 90” + 36”
Width 600 mm with side panels 23.62”
Required space to remove the side panels 675. 64 mm 26.6”
Depth from front door handle to rear door handle 1200 mm 47.24”
Depth with doors removed 1112 mm 43.78”
Top, front, and rear maintenance access requirement 914 mm 36”

Note:

The space above the cabinet and its surroundings must not restrict the movement of cool air between the air conditioner and the cabinet, or the movement of hot air coming out of the top of the cabinet.

Additional Space Requirements

Oracle Advanced Support Gateway appliance is also required to deploy OPCM. The appliance requires the space of one rack unit to be mounted. See Oracle Advanced Support Gateway Documentation for more information.