Learn about the electrical power specifications and requirements for OPCM and the optional ZS3 storage expansion rack.
Power Consumption
The following table describes the typical and maximum power consumption for OPCM:
Table 1-7 OPCM Power Consumption
Power Consumption | Model 288 | Model 576 | Model 1080 |
---|---|---|---|
Maximum | 7.732 kW, 7.887 kVA | 13.444 kW, 13.713 kVA | 23.520 kW, 23.990 kVA |
Typical | 5.412 kW, 5.521 kVA | 9.411 kW, 9.599 kVA | 16.464 kW, 16.793 kVA |
The following table describes the typical and maximum power consumption for the optional OPCM ZS3 storage expansion rack:
Table 1-8 OPCM ZS3 Storage Expansion Rack Power Consumption
Power Consumption | Model 268 | Model 536 |
---|---|---|
Maximum | 6.671kW | 13.342 kW |
Typical | 3.177 kW | 6.354 kW |
Power Distribution Units
Oracle Public Cloud Machine (OPCM) can operate effectively over a wide range of voltages and frequencies. However, it must have a reliable power source. Damage may occur if the ranges are exceeded. Electrical disturbances such as the following may damage an OPCM:
Fluctuations caused by brownouts
Wide and rapid variations in input voltage levels or in input power frequency
Electrical storms
Faults in the distribution system, such as defective wiring
To protect the system, dedicated power distribution system and power-conditioning equipment should be used. Lightning arresters or power cables should be used to protect from electrical storms.
Each rack has two pre-installed Power Distribution Units (PDUs). The PDUs accept different power sources. You must select the type of PDU that meets the requirements for your data center.
The following table lists the available PDUs for OPCM and OPCM ZS3 Storage Expansion depending on the model and your region:
Table 1-9 Available PDUs by Region and Model
OPCM Model | Region | Available PDUs |
---|---|---|
288 and 576 | Americas, Japan, and Taiwan |
|
1080 | Americas, Japan, and Taiwan |
|
ZS3 Storage Expansion 268 and 536 | Americas, Japan, and Taiwan |
|
288 and 576 | EMEA and rest of APAC |
|
1080 | EMEA and rest of APAC |
|
ZS3 Storage Expansion 268 and 536 | EMEA and rest of APAC |
|
The following table lists the PDU low voltage specifications:
Table 1-10 PDU Low Voltage Requirements
Specification | 15 kVA, 1 phase | 15 kVA, 3 phase | 22 kVA, 1 phase | 24 kVA, 3 phase |
---|---|---|---|---|
Phase |
1 ph |
3 ph |
1 ph |
3 ph |
Market Part Number |
6442A |
6440A |
7100873 |
XSR-24K-IEC309-4P |
Manufacturing Part Number |
597-0566-01 |
597-0564-01 |
7018123 |
594-5596-01 |
Voltage |
200-240 VAC 1ph |
200-240 VAC 3ph |
200-240 VAC 1ph |
200-240 VAC 3ph |
Amps Per PDU |
72A (3 × 24A) |
69A (3 × 23A) |
110.4 (3x36.8A) |
120A (6 × 20A) |
Outlets |
42 C13, 6 C19 |
42 C13, 6 C19 |
42 C13, 6 C19 |
42 C13, 6 C19 |
Number of Inputs |
3x30A, 1 ph |
1x60A, 3 ph |
3 x50A 1 ph |
2x60A, 3 ph |
Current |
24A max. per input |
40A max. per phase |
36.8A per input |
34.6A max. per phase |
Data Center Receptacle |
NEMA L6-30R |
IEC309-3P4W-IP67 (60A, 250V, AC, 3 ph) IEC309 60A 3ph 4 Wire Hubbell HBL460R/C9W or equivalent. |
Hubbell CS8265C |
IEC309-3P4W-IP67 (60A, 250V, AC, 3 ph) IEC309 60A 3ph 4 Wire Hubbell HBL460R/C9W or equivalent. |
Number of Outlets Per Rack |
6 |
2 |
6 |
4 |
The following table lists the PDU high voltage specifications:
Table 1-11 PDU High Voltage Requirements
Specification | 15 kVA, 3 phase | 22 kVA, 1 phase | 24 kVA, 3 phase |
---|---|---|---|
Phase |
3 ph |
1 ph |
3 ph |
Market Part Number |
6441A |
7100874 |
XSR-24K-IEC309-5P |
Manufacturing Part Number |
597-0565-01 |
7018124 |
594-5600-01 |
Voltage |
220/380-240/415 VAC 3ph |
200-240 VAC 1ph |
220/380-240/415 VAC 3ph |
Amps Per PDU |
62.7 A (3 × 20.9A) |
96A (3x32A) |
109A (6 × 18.1A) |
Outlets |
42 C13, 6 C19 |
42 C13, 6 C19 |
42 C13, 6 C19 |
Number of Inputs |
1x25A, 3 ph |
3 x 32A 1 ph |
2x25A, 3 ph |
Current |
24A max. per input |
32 A per input |
18 A max. per input |
Data Center Receptacle |
IEC 309-4P5W-IP44 (32A, 400V, AC, 3ph) IEC309 32A 3ph 5 Wire Hubbell HBL532R/C9W or equivalent. |
IEC 309-2P3W-IP44 (32A, 250V, AC, 3ph) IEC309 32A 1ph 3 Wire Hubbell HBL332R/C9W or equivalent |
IEC 309-4P5W-IP44(32A, 400V, AC, 3ph) IEC309 32A 3ph 5 Wire Hubbell HBL532R/C9W or equivalent. |
Number of Outlets Per Rack |
2 |
6 |
4 |