Flooring Requirements
Oracle allows the installation of the Private Cloud Appliance rack on solid flooring and on raised flooring (recommended). Review important flooring requirements before the system arrives at your site.
Use the information in this section along with the Data Center Room Checklist to prepare your site.
The site floor and the optional raised flooring must be able to support the total weight of the system as specified in Space Requirements. The following table lists the floor load requirements.
Description |
Requirement |
---|---|
Maximum allowable weight of installed rack equipment |
952.54 kg (2100 lbs) |
Maximum allowable weight of installed power distribution units |
52.16 kg (115 lbs) |
Maximum dynamic load (maximum allowable weight of installed equipment including power distribution units) |
1004.71 kg (2215 lbs) |