Site Requirements
This topic describes the site requirements for delivery, installation, and operation of Oracle Data Infrastructure Cloud@Customer.
The system is designed for rack installation and includes two servers and one storage shelf, with the option to add a second storage shelf for expansion in the future.
Space requirements
Plan rack space based on the physical dimensions of each component.
| Component | Height | Width | Depth |
|---|---|---|---|
| Server (each) | 86.9 mm (3.4 in.) | 445.0 mm (17.5 in.) | 775.0 mm (30.5 in.) |
| Storage shelf (each) | 175 mm (6.9 in.) | 483 mm (19.0 in.) | 630 mm (24.8 in.) |
The following are the supported configurations.
| Scenario | Included Components |
|---|---|
| Base system | Two servers + one storage shelf |
| Expanded system | Two servers + one storage shelf + optional second storage shelf |
Weight requirements
Use these weights for rack-loading and handling planning.
| Component | Weight |
|---|---|
| Server (each) | 23.8 kg (52.5 lb.) |
| Storage shelf (each) | 38 kg (84 lb.) |
Installation materials
Ensure your site has an appropriate receiving area and a clear path to move equipment to the installation location.
| Item | Included |
|---|---|
| Tool-less rack mounting slide rail kit | Yes |
| Cable management arm | Yes |
Electrical power requirements
Provide redundant AC power suitable for the system’s redundant power supplies.
| Component | Power supplies | Voltage | Input current | Frequency |
|---|---|---|---|---|
| Server (each) | Two 1400W, hot-swappable, redundant | 200 to 240 VAC (nominal) | 10.0A at 200–240 VAC (maximum) | 50/60 Hz (47–63 Hz range) |
| Storage shelf (each) | Two 580W, hot-swappable, redundant | 100 to 240 VAC (rated line voltage) | 8A at 100 VAC and 3A at 240 VAC (rated) | - |
Power consumption
Use the following values to size power for your chosen configuration.
| Component / Configuration | Power (Typical) | Power (Maximum) |
|---|---|---|
| Two-server high availability configuration (max memory) | 1534W | 2394W |
| Storage shelf (24 × 7.68 TB SSDs) | 276W | 449W |
Heat output
Use the following values to size cooling for your chosen configuration.
| Component / Configuration | Heat Output (Typical) | Heat Output (Maximum) |
|---|---|---|
| Two-server high availability configuration (max memory) | 5235 BTU/hr | 8168 BTU/hr |
| Storage shelf (24 × 7.68 TB SSDs) | 940 BTU/hr | 1529 BTU/hr |
Environment requirements
Maintain the environment (temperature, humidity and altitude) within these limits for reliable operation.
| Condition | Operating Requirement | Non-operating Requirement | Optimal Requirement |
|---|---|---|---|
| Temperature | 5°C to 35°C (41°F to 95°F) | -40°C to 68°C (-40°F to 154°F) | 21°C to 23°C (69.8°F to 73.4°F) |
| Relative Humidity | 10% to 90%, noncondensing | Up to 93%, noncondensing | - |
| Altitude | Up to 3000 meters (9840 feet) | Up to 12000 meters (39370 feet) | Higher than 900 meters, reduce maximum ambient operating temperature by 1°C per 300 meters, up to 3000 meters. |
In China markets, regulations might limit installations to a maximum altitude of 2,000 meters (6,562 feet).
Ventilation and airflow
Ensure your facility can remove the heat output listed earlier (BTU/hr). Cooling capacity should be planned based on:
- Two-server high availability heat output, plus
- One or two storage shelves, depending on your configuration and drive population.
Plan cooling using the heat-output values and your data center standards.
Acoustic noise
Check and comply with any local workplace noise exposure regulations and any site-specific requirements for hearing protection.
| Metric | Value | Notes |
|---|---|---|
| Acoustic noise (sound power) | 8.5 Bels | At 50% fan speed |