General Environmental Requirements

The environmental requirements for Oracle Big Data Cloud at Customer depend on the model and the size of the system. The following tables provide an overview of the rack requirements. Measurements are approximate. The other sections in this chapter provide detailed information.

General Environmental Requirements for Oracle Big Data Cloud at Customer

The following table identifies the general environmental requirements for an Oracle Big Data Cloud at Customer rack.

Environmental Component Starter Rack (6 Nodes) Full Rack (18 Nodes)

Net Weight

See also Flooring Requirements

415 kg (915 lb)

836 kg (1843 lb)

Acoustic levels

8.4 Bel

8.5 Bel

Power

See also Electrical Power Requirements

Maximum: 5.2 kW

Typical: 3.6 kW

Maximum: 13.0 kW

Typical: 9.1 kW

Cooling

See also Temperature and Humidity Requirements and Ventilation and Cooling Requirements

Maximum: 17,521 BTU/hour (18,485 kJ/hour)

Typical: 12,265 BTU/hour (12,940 kJ/hour)

Maximum: 44,136 BTU/hour (46,564 kJ/hour)

Typical: 30,895 BTU/hour 32,594 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

See also Temperature and Humidity Requirements and Ventilation and Cooling Requirements

Maximum: 811 CFM

Typical: 568 CFM

Maximum: 2043 CFM

Typical: 1430 CFM

IP addresses

See also Understanding the Network Requirements.

6 for the client Ethernet network

18 for the client Ethernet network

Network drops

See also Understanding the Network Requirements.

One network connection

One network connection

External connectivity

See also Understanding the Network Requirements.

2–6 x 10 Gbps Ethernet ports

2–8 x 10 Gbps Ethernet ports

Environmental Requirements for Oracle Big Data Cloud at Customer plus Infiniband Infrastructure

The following table identifies the general environmental requirements for an Oracle Big Data Cloud at Customer plus Infiniband Infrastructure.

Environmental Component Each Node plus Infiniband Infrastructure

Height

3.5 inches (87.6 mm)

Width

17.5 inches (445.0 mm)

Depth

29.0 inches (737.0 mm)

Net Weight

See also Flooring Requirements

33.1 kg (73.0 lb)

Power

See also Electrical Power Requirements

Maximum: 0.7 kW

Typical: 0.5 kW

(Typical power usage varies by application workload)

Cooling

See also Electrical Power Requirements and Ventilation and Cooling Requirements

Maximum: 2,481 BTU/hour (2617 kJ/hour)

Typical: 1,736 BTU/hour (1831 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

See also Electrical Power Requirements and Ventilation and Cooling Requirements

Maximum: 115 CFM

Typical: 80 CFM