General Environmental Requirements
The environmental requirements for Oracle Big Data Cloud at Customer depend on the model and the size of the system. The following tables provide an overview of the rack requirements. Measurements are approximate. The other sections in this chapter provide detailed information.
General Environmental Requirements for Oracle Big Data Cloud at Customer
The following table identifies the general environmental requirements for an Oracle Big Data Cloud at Customer rack.
Environmental Component | Starter Rack (6 Nodes) | Full Rack (18 Nodes) |
---|---|---|
Net Weight See also Flooring Requirements |
415 kg (915 lb) |
836 kg (1843 lb) |
Acoustic levels |
8.4 Bel |
8.5 Bel |
Power See also Electrical Power Requirements |
Maximum: 5.2 kW Typical: 3.6 kW |
Maximum: 13.0 kW Typical: 9.1 kW |
Cooling See also Temperature and Humidity Requirements and Ventilation and Cooling Requirements |
Maximum: 17,521 BTU/hour (18,485 kJ/hour) Typical: 12,265 BTU/hour (12,940 kJ/hour) |
Maximum: 44,136 BTU/hour (46,564 kJ/hour) Typical: 30,895 BTU/hour 32,594 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) See also Temperature and Humidity Requirements and Ventilation and Cooling Requirements |
Maximum: 811 CFM Typical: 568 CFM |
Maximum: 2043 CFM Typical: 1430 CFM |
IP addresses See also Understanding the Network Requirements. |
6 for the client Ethernet network |
18 for the client Ethernet network |
Network drops See also Understanding the Network Requirements. |
One network connection |
One network connection |
External connectivity See also Understanding the Network Requirements. |
2–6 x 10 Gbps Ethernet ports |
2–8 x 10 Gbps Ethernet ports |
Environmental Requirements for Oracle Big Data Cloud at Customer plus Infiniband Infrastructure
The following table identifies the general environmental requirements for an Oracle Big Data Cloud at Customer plus Infiniband Infrastructure.
Environmental Component | Each Node plus Infiniband Infrastructure |
---|---|
Height |
3.5 inches (87.6 mm) |
Width |
17.5 inches (445.0 mm) |
Depth |
29.0 inches (737.0 mm) |
Net Weight See also Flooring Requirements |
33.1 kg (73.0 lb) |
Power See also Electrical Power Requirements |
Maximum: 0.7 kW Typical: 0.5 kW (Typical power usage varies by application workload) |
Cooling See also Electrical Power Requirements and Ventilation and Cooling Requirements |
Maximum: 2,481 BTU/hour (2617 kJ/hour) Typical: 1,736 BTU/hour (1831 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) See also Electrical Power Requirements and Ventilation and Cooling Requirements |
Maximum: 115 CFM Typical: 80 CFM |