1.2.2 General Environmental Requirements for Oracle Exadata X5-2

The environmental requirements for Oracle Exadata X5-2 depend on the size of the system. The following table shows the general environmental requirements for Oracle Exadata X5-2.

Table 1-1 Environmental Requirements for Oracle Exadata X5-2

Environmental Component Oracle Exadata X5-2 Full Rack Oracle Exadata X5-2 Half Rack Oracle Exadata X5-2 Quarter Rack Oracle Exadata X5-2 Eighth Rack

Weight

See Also: Flooring Requirements

  • Extreme Flash drives: 804.9 kg (1774 lbs)

  • High capacity drives: 874.8 kg (1928 lbs))

  • Extreme Flash drives: 525.9 kg (1160 lbs)

  • High capacity drives: 560.9 kg (1236 lbs)

  • Extreme Flash drives: 366.3 kg (808 lbs)

  • High capacity drives: 381.2 kg (841 lbs)

  • Extreme Flash drives: 366.3 kg (808 lbs)

  • High capacity drives: 381.2 kg (841 lbs)

Acoustic levels

86 db(A)

85 db(A)

83 db(A)

83 db(A)

Power

See Also: Electrical Power Requirements

  • Extreme Flash drives

    Maximum: 15.7 kVA

    Typical: 11.0 kVA (varies based on application load)

  • High capacity drives

    Maximum: 15.6 kVA

    Typical: 10.9 kVA (varies based on application load)

  • Extreme Flash drives

    Maximum: 8.5 kVA

    Typical: 5.9 kVA (varies based on application load)

  • High capacity drives

    Maximum: 8.4 kVA

    Typical: 5.9 kVA (varies based on application load)

  • Extreme Flash drives

    Maximum: 4.2 kVA

    Typical: 3.0 kVA (varies based on application load)

  • High capacity drives

    Maximum: 4.2 kVA

    Typical: 2.9kVA (varies based on application load)

  • Extreme Flash drives

    Maximum: 3.5 kVA

    Typical: 2.4 kVA (varies based on application load)

  • High capacity drives

    Maximum: 34 kVA

    Typical: 2.4 kVA (varies based on application load)

Cooling

See Also: Temperature and Humidity Requirements, and Ventilation and Cooling Requirements

  • Extreme Flash drives

    Maximum: 52,578 BTU/hour (55,469 kJ/hour)

    Typical: 36,804 BTU/hour (38,829 kJ/hour)

  • High capacity drives

    Maximum: 52,052 BTU/hour (54,915 kJ/hour)

    Typical: 36,437 BTU/hour (38,441 kJ/hour)

  • Extreme Flash drives

    Maximum: 28,396 BTU/hour (29,958 kJ/hour)

    Typical: 19,877 BTU/hour (20,970 kJ/hour)

  • High capacity drives

    Maximum: 28,133 BTU/hour (29,680 kJ/hour)

    Typical: 19,693 BTU/hour (20,776 kJ/hour)

  • Extreme Flash drives

    Maximum: 14,195 BTU/hour (14,975 kJ/hour)

    Typical: 9,936 BTU/hour (10,483 kJ/hour)

  • High capacity drives

    Maximum: 14,082 BTU/hour (14,856 kJ/hour)

    Typical: 9,857 BTU/hour (10,399 kJ/hour)

  • Extreme Flash drives

    Maximum: 11,674 BTU/hour (12,317 kJ/hour)

    Typical: 8,172 BTU/hour (8,622 kJ/hour)

  • High capacity drives

    Maximum: 11,530 BTU/hour (12,164 kJ/hour)

    Typical: 8,071 BTU/hour (8,515 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

See Also: Temperature and Humidity Requirements, and Ventilation and Cooling Requirements

  • Extreme Flash drives

    Maximum: Approximately 2,434 CFM

    Typical: Approximately 1,704 CFM

  • High capacity drives

    Maximum: Approximately 2,410 CFM

    Typical: Approximately 1,687 CFM

  • Extreme Flash drives

    Maximum: Approximately 1,315 CFM

    Typical: Approximately 920 CFM

  • High capacity drives

    Maximum: Approximately 1,302 CFM

    Typical: Approximately 912 CFM

  • Extreme Flash drives

    Maximum: Approximately 657 CFM

    Typical: Approximately 460 CFM

  • High capacity drives

    Maximum: Approximately 652 CFM

    Typical: Approximately 456 CFM

  • Extreme Flash drives

    Maximum: Approximately 540 CFM

    Typical: Approximately 378 CFM

  • High capacity drives

    Maximum: Approximately 534 CFM

    Typical: Approximately 374 CFM

IP Addresses

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

68 for Ethernet network, assuming single cluster

Up to 36 for RDMA Network Fabric

38 for Ethernet network, assuming single cluster

Up to 18 for RDMA Network Fabric

22 for Ethernet network, assuming single cluster

Up to 8 for RDMA Network Fabric

22 for Ethernet network, assuming single cluster

Up to 8 for RDMA Network Fabric

Network drops

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

Minimum of 11 network drops

Minimum of 7 network drops

Minimum of 5 network drops

Minimum of 5 network drops

External connectivity

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

18 x 1 GbE/10 GbE Ethernet ports

16 x 10 GbE Ethernet ports

At least 12 RDMA Network Fabric ports

12 x 1 GbE/10 GbE Ethernet ports

8 x 10 GbE Ethernet ports

At least 12 RDMA Network Fabric ports

6 x 1 GbE/10 GbE Ethernet ports

4 x 10 GbE Ethernet ports

At least 12 RDMA Network Fabric ports

6 x 1 GbE/10 GbE Ethernet ports

4 x 10 GbE Ethernet ports

At least 12 RDMA Network Fabric ports