1.2.16 General Environmental Requirements for Single Servers

The environmental requirements for single servers are shown in the following tables.

Table 1-15 Environmental Requirements for Oracle Exadata X10M Single Servers

Environmental Component Database Server X10M Database Server X10M - 3 TB RAM Configuration Exadata Storage Server X10M - High Capacity Exadata Storage Server X10M - Extreme Flash Exadata Storage Server X10M XT Server

Weight

23.6 kg (52 lbs)

24 kg (53 lbs)

33.6 kg (74 lbs)

27.2 kg (60 lbs)

30.8 kg (68 lbs)

Acoustic Noise

84 dB

86 dB

84 dB

82 dB

81 dB

Power

Maximum: 1.3 kW (1.3 kVA)

Typical: 0.9 kW (0.9 kVA) (varies based on application load)

Maximum: 1.5 kW (1.5 kVA)

Typical: 1 kW (1.1 kVA) (varies based on application load)

Maximum: 1 kW (1.1 kVA)

Typical: 0.7 kW (0.7 kVA) (varies based on application load)

Maximum: 1 kW (1 kVA)

Typical: 0.7 kW (0.7 kVA) (varies based on application load)

Maximum: 0.4 kW (0.5 kVA)

Typical: 0.3 kW (0.3 kVA) (varies based on application load)

Cooling

At max usage: 4,299 BTU/hour (4,536 kJ/hour)

At typical usage: 3,010 BTU/hour (3,175 kJ/hour

At max usage: 5,050 BTU/hour (5,328 kJ/hour)

At typical usage: 3,535 BTU/hour (3,729 kJ/hour

At max usage: 3,559 BTU/hour (3,755 kJ/hour)

At typical usage: 2,491 BTU/hour (2,628 kJ/hour)

At max usage: 3,337 BTU/hour (3,521 kJ/hour)

At typical usage: 2,336 BTU/hour (2,464 kJ/hour)

At max usage: 1,512 BTU/hour (1,595 kJ/hour)

At typical usage: 1,058 BTU/hour (1,116 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

At max usage: Approximately 199 CFM

At typical usage: Approximately 139 CFM

At max usage: Approximately 234 CFM

At typical usage: Approximately 164 CFM

At max usage: Approximately 165 CFM

At typical usage: Approximately 115 CFM

At max usage: Approximately 154 CFM

At typical usage: Approximately 108 CFM

At max usage: Approximately 70 CFM

At typical usage: Approximately 49 CFM

Table 1-16 Environmental Requirements for X9M-2 Single Servers

Environmental Component Database Server X9M-2 Exadata Storage Server X9M-2 - High Capacity Exadata Storage Server X9M-2 Eighth Rack - High Capacity Exadata Storage Server X9M-2 - Extreme Flash Exadata Storage Server X9M-2 XT Server

Weight

20.7 kg (45.6 lbs)

34.8 kg (76.7 lbs)

30.6 kg (67.5 lbs)

27.5 kg (60.6 lbs)

30.2 kg (66.7 lbs)

Acoustic Noise

79 dB

80 dB

80 dB

80 dB

80 dB

Power

Maximum: 0.9 kW (0.9 kVA)

Typical: 0.7 kW (0.7 kVA) (varies based on application load)

Maximum: 0.9 kW (0.9 kVA)

Typical: 0.5 kW (0.6 kVA) (varies based on application load)

Maximum: 0.6 kW (0.6 kVA)

Typical: 0.4 kW (0.4 kVA) (varies based on application load)

Maximum: 0.9 kW (0.9 kVA)

Typical: 0.6 kW (0.6 kVA) (varies based on application load)

Maximum: 0.5 kW (0.5 kVA)

Typical: 0.4 kW (0.4 kVA) (varies based on application load)

Cooling

At max usage: 3,153 BTU/hour (3,326 kJ/hour)

At typical usage: 2,207 BTU/hour (2,328 kJ/hour

At max usage: 2,883 BTU/hour (3,042 kJ/hour)

At typical usage: 2,018 BTU/hour (2,129 kJ/hour)

At max usage: 2,134 BTU/hour (2,251 kJ/hour)

At typical usage: 1,494 BTU/hour (1,576 kJ/hour)

At max usage: 2,907 BTU/hour (3,067 kJ/hour)

At typical usage: 2,035 BTU/hour (2,147 kJ/hour)

At max usage: 1,720 BTU/hour (1,814 kJ/hour)

At typical usage: 1,204 BTU/hour (1,270 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

At max usage: Approximately 146 CFM

At typical usage: Approximately 102 CFM

At max usage: Approximately 133 CFM

At typical usage: Approximately 93 CFM

At max usage: Approximately 99 CFM

At typical usage: Approximately 69 CFM

At max usage: Approximately 135 CFM

At typical usage: Approximately 94 CFM

At max usage: Approximately 80 CFM

At typical usage: Approximately 56 CFM

Table 1-17 Environmental Requirements for X8M-2 Single Servers

Environmental Component Database Server X8M-2 Exadata Storage Server X8M-2 - High Capacity Exadata Storage Server X8M-2 Eighth Rack - High Capacity Exadata Storage Server X8M-2 - Extreme Flash Exadata Storage Server X8M-2 XT Server

Weight

20.7 kg (45.6 lbs)

34.8 kg (76.7 lbs)

30.6 kg (67.5 lbs)

27.5 kg (60.6 lbs)

30.2 kg (66.7 lbs)

Acoustic Noise

77 dB

82 dB

82 dB

82 dB

82 dB

Power

Maximum: 0.7 kW (0.7 kVA)

Typical: 0.5 kW (0.5 kVA) (varies based on application load)

Maximum: 0.8 kW (0.8 kVA)

Typical: 0.5 kW (0.6 kVA) (varies based on application load)

Maximum: 0.6 kW (0.6 kVA)

Typical: 0.4 kW (0.4 kVA) (varies based on application load)

Maximum: 0.8 kW (0.8 kVA)

Typical: 0.6 kW (0.6 kVA) (varies based on application load)

Maximum: 0.5 kW (0.5 kVA)

Typical: 0.3 kW (0.3 kVA) (varies based on application load)

Cooling

At max usage: 2,409 BTU/hour (2,541 kJ/hour)

At typical usage: 1,686 BTU/hour (1,779 kJ/hour

At max usage: 2,631 BTU/hour (2,775 kJ/hour)

At typical usage: 1,842 BTU/hour (1,943 kJ/hour)

At max usage: 1,947 BTU/hour (2,054 kJ/hour)

At typical usage: 1,363 BTU/hour (1,438 kJ/hour)

At max usage: 2,730 BTU/hour (2,880 kJ/hour)

At typical usage: 1,911 BTU/hour (2,016 kJ/hour)

At max usage: 1570 BTU/hour (1,656 kJ/hour)

At typical usage: 1,099 BTU/hour (1,159 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

At max usage: Approximately 112 CFM

At typical usage: Approximately 78 CFM

At max usage: Approximately 122 CFM

At typical usage: Approximately 85 CFM

At max usage: Approximately 90 CFM

At typical usage: Approximately 63 CFM

At max usage: Approximately 126 CFM

At typical usage: Approximately 88 CFM

At max usage: Approximately 73 CFM

At typical usage: Approximately 51 CFM

Table 1-18 Environmental Requirements for X8-2 Single Servers

Environmental Component Database Server X8-2 Exadata Storage Server X8-2 - High Capacity Exadata Storage Server X8-2 Eighth Rack - High Capacity Exadata Storage Server X8-2 - Extreme Flash Exadata Storage Server X8-2 XT Server

Weight

20.7 kg (45.6 lbs)

34.8 kg (76.7 lbs)

30.6 kg (67.5 lbs)

27.5 kg (60.6 lbs)

30.2 kg (66.7 lbs)

Acoustic Noise

77 dB

82 dB

82 dB

82 dB

82 dB

Power

Maximum: 0.7 kW (0.7 kVA)

Typical: 0.5 kW (0.5 kVA) (varies based on application load)

Maximum: 0.7 kW (0.7 kVA)

Typical: 0.5 kW (0.5 kVA) (varies based on application load)

Maximum: 0.5 kW (0.5 kVA)

Typical: 0.4 kW (0.4 kVA) (varies based on application load)

Maximum: 0.7 kW (0.7 kVA)

Typical: 0.5 kW (0.5 kVA) (varies based on application load)

Maximum: 0.5 kW (0.5 kVA)

Typical: 0.3 kW (0.3 kVA) (varies based on application load)

Cooling

At max usage: 2,409 BTU/hour (2,541 kJ/hour)

At typical usage: 1,686 BTU/hour (1,779 kJ/hour

At max usage: 2,317 BTU/hour (2,444 kJ/hour)

At typical usage: 1,622 BTU/hour (1,711 kJ/hour)

At max usage: 1,714 BTU/hour (1,809 kJ/hour)

At typical usage: 1,200 BTU/hour (1,266 kJ/hour)

At max usage: 2,283 BTU/hour (2,408 kJ/hour)

At typical usage: 1,598 BTU/hour (1,686 kJ/hour)

At max usage: 1570 BTU/hour (1,656 kJ/hour)

At typical usage: 1,099 BTU/hour (1,159 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

At max usage: Approximately 112 CFM

At typical usage: Approximately 78 CFM

At max usage: Approximately 107 CFM

At typical usage: Approximately 75 CFM

At max usage: Approximately 79 CFM

At typical usage: Approximately 56 CFM

At max usage: Approximately 106 CFM

At typical usage: Approximately 74 CFM

At max usage: Approximately 73 CFM

At typical usage: Approximately 51 CFM

Table 1-19 Environmental Requirements for X7-2 Single Servers

Environmental Component Exadata Storage Server X7-2 - Extreme Flash Exadata Storage Server X7-2 Eighth Rack - High Capacity Exadata Storage Server X7-2 - High Capacity Database Server X7-2

Weight

27.5 kg (61 lbs)

30.1 kg (66.3 lbs)

34.4 kg (76 lbs)

20.7 kg (46 lbs)

Acoustic Noise

82 dB(A)

79 dB(A)

82 dB(A)

77 dB(A)

Power

Maximum: 0.6 kW (0.6 kVA)

Typical: 0.4 kW (0.5 kVA) (varies based on application load)

Maximum: 0.5 kW (0.5 kVA)

Typical: 0.3 kW (0.3 kVA) (varies based on application load)

Maximum: 0.6 kW (0.6 kVA)

Typical: 0.4 kW (0.4 kVA) (varies based on application load)

Maximum: 0.8 kW (0.8 kVA)

Typical: 0.5 kW (0.6 kVA) (varies based on application load)

Cooling

Maximum: 2,167 BTU/hour (2,286 kJ/hour)

Typical: 1,600 BTU/hour (1,378 kJ/hour)

Maximum: 1,588 BTU/hour (1,676 kJ/hour)

Typical: 1,112 BTU/hour (1,173 kJ/hour)

Maximum: 2,146 BTU/hour (2,264 kJ/hour)

Typical: 1,502 BTU/hour (1,585 kJ/hour)

Maximum: 2,631 BTU/hour (2,775 kJ/hour)

Typical: 1,842 BTU/hour (1,943 kJ/hour

Air flow front-to-back (subject to actual data center environment)

Maximum: Approximately 100 CFM

Typical: Approximately 70 CFM

Maximum: Approximately 74 CFM

Typical: Approximately 51 CFM

Maximum: Approximately 99 CFM

Typical: Approximately 70 CFM

Maximum: Approximately 122 CFM

Typical: Approximately 85 CFM

Table 1-20 Environmental Requirements for X6-2 Single Servers

Environmental Component Exadata Storage Server X6-2 - Extreme Flash Exadata Storage Server X6-2 - High Capacity Database Server X6-2

Weight

28.1 kg (62 lbs)

33.1 kg (73 lbs)

20.4 kg (45 lbs)

Acoustic Noise

78 dB(A)

78 dB(A)

78 dB(A)

Power

Maximum: 0.6 kVA

Typical: 0.4 kVA (varies based on application load)

Maximum: 0.6 kVA

Typical: 0.4 kVA (varies based on application load)

Maximum: 0.665 kW (0.678 kVA)

Typical: 0.466 kW (0.475 kVA) (varies based on application load)

Cooling

Maximum: 1,866 BTU/hour (1,969 kJ/hour)

Typical: 1,307 BTU/hour (1,378 kJ/hour)

Maximum: 2,006 BTU/hour (2,117 kJ/hour)

Typical: 1,404 BTU/hour (1,482 kJ/hour)

Maximum: 2,269 BTU/hour (2,394 kJ/hour)

Typical: 1,588 BTU/hour (1,676 kJ/hour

Air flow front-to-back (subject to actual data center environment)

Maximum: Approximately 86 CFM

Typical: Approximately 60 CFM

Maximum: Approximately 93 CFM

Typical: Approximately 65 CFM

Maximum: Approximately 105 CFM

Typical: Approximately 74 CFM

Table 1-21 Environmental Requirements for X5-2 Single Servers

Environmental Component Exadata Storage Server X5-2 - Extreme Flash Exadata Storage Server X5-2 - High Capacity Database Server X5-2

Weight

28.1 kg (62 lbs)

33.1 kg (73 lbs)

20.4 kg (45 lbs)

Acoustic Noise

78 dB(A)

78 dB(A)

78 dB(A)

Power

Maximum: 0.6 kVA

Typical: 0.4 kVA (varies based on application load)

Maximum: 0.6 kVA

Typical: 0.4 kVA (varies based on application load)

Maximum: 0.7 kVA

Typical: 0.5 kVA (varies based on application load)

Cooling

Maximum: 2,037 BTU/hour (2,149 kJ/hour)

Typical: 1,426 BTU/hour (1,504 kJ/hour)

Maximum: 2,000 BTU/hour (2,109 kJ/hour)

Typical: 1,400 BTU/hour (1,477 kJ/hour)

Maximum: 2,481 BTU/hour (2,617 kJ/hour)

Typical: 1,736 BTU/hour (1,832 kJ/hour

Air flow front-to-back (subject to actual data center environment)

Maximum: Approximately 94 CFM

Typical: Approximately 66 CFM

Maximum: Approximately 93 CFM

Typical: Approximately 65 CFM

Maximum: Approximately 115 CFM

Typical: Approximately 80 CFM

Table 1-22 Environmental Requirements for 8-Socket Servers, Model X4-8 and Later

Environmental Component Database Server X8M-8 and X9M-8 Database Server X7-8 and X8-8 Database Server X5-8 and X6-8 Database Server X4-8

Weight

90.2 kg (198.8 lbs) 90.2 kg (198.8 lbs)

93.4 kg (206 lbs)

93.4 kg (206 lbs)

Acoustic Noise

87 dB 87 dB

81 dB(A)

81 dB(A)

Power

Maximum: 3.6 kVA

Typical: 2.5 kVA (varies based on application load)

Maximum: 3.6 kVA

Typical: 2.5 kVA (varies based on application load)

Maximum: 3.5 kVA

Typical: 2.4 kVA (varies based on application load)

Maximum: 3.7 kVA

Typical: 2.6 kVA (varies based on application load)

Cooling

Maximum: 11,953 BTU/hour (12,610 kJ/hour)

Typical: 8,367 BTU/hour (8,827 kJ/hour)

Maximum: 11,942 BTU/hour (12,599 kJ/hour)

Typical: 8,360 BTU/hour (8,820 kJ/hour)

Maximum: 11,601 BTU/hour (12,239 kJ/hour)

Typical: 8,121 BTU/hour (8,568 kJ/hour)

Maximum: 12,284 BTU/hour (12,959 kJ/hour)

Typical: 8,599 BTU/hour (9,072 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

Maximum: Approximately 553 CFM

Typical: Approximately 387 CFM

Maximum: Approximately 553 CFM

Typical: Approximately 387 CFM

Maximum: Approximately 537 CFM

Typical: Approximately 376 CFM

Maximum: Approximately 569 CFM

Typical: Approximately 398 CFM