1.7.1.5 High-Voltage 15 kVA Single Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan

Note:

The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.

Table 1-30 Specifications for each High-Voltage 15 kVA Single Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan

Specification Value
Number of Inputs 3 x 25A 1ph
Voltage 220 - 240 VAC
Frequency 50/60 Hz
Current 25A maximum (per input)
Power Rating 15 kVA
Output Current 72A (3 x 24A)
Outlets 42 x C13, 6 x C19
Outlet Groups 6
Group Protection (UL489 1-pole circuit breaker) 20A
Data Center Receptacle IEC309 32A 3 PIN 250 VAC IP44

Note:

The high-voltage 15 kVA single phase PDU is no longer available. The high-voltage 22kVA single phase PDU is the recommended replacement.