1.7.1.7 High-Voltage 15 kVA Three Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan

Note:

The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.

Table 1-32 Specifications for each High-Voltage 15 kVA Three Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan

Specification Value
Number of Inputs 1
Source Voltage 220/380 - 240/415VAC 3Ø
Frequency 50/60 Hz
Max Line Current 21A
Phase Current 21A
Nominal Power Rating 15kVA
Recommended Circuit Breaker 25A
Outlets 42 x C13, 6 x C19
Outlet Groups 6
Max Group Current 20A
Output Voltage 220-240V
Data Center Receptacle 3ph 4W + ground 32A IEC60309 5P 6h 400V