13.2 Administration Network Ethernet Port Cabling

This topic describes the administration network cabling in Oracle Exadata Database Machine X10M.

The Management Network Switch is located in rack unit 21 (U21) on Oracle Exadata Database Machine X10M racks. Each component in the rack connects to the Management Network Switch as described in the following table.

In the following table, UN denotes the rack unit location, where U42 is at the top of the rack and U1 is at the bottom of the rack.

Table 13-1 Administration Network Cabling for Oracle Exadata Database Machine X10M

From Rack Unit Equipment Type Network Port To Management Network Switch Port

U41

Storage Server

NET 0

15

U41

Storage Server

NET MGT (ILOM)

16

U39

Storage Server or Database Server

NET 0

1

U39

Storage Server or Database Server

NET MGT (ILOM)

2

U37

Storage Server or Database Server

NET 0

3

U37

Storage Server or Database Server

NET MGT (ILOM)

4

U35

Storage Server or Database Server

NET 0

5

U35

Storage Server or Database Server

NET MGT (ILOM)

6

U33

Storage Server or Database Server

NET 0

7

U33

Storage Server or Database Server

NET MGT (ILOM)

8

U31

Storage Server or Database Server

NET 0

9

U31

Storage Server or Database Server

NET MGT (ILOM)

10

U29

Storage Server or Database Server

NET 0

11

U29

Storage Server or Database Server

NET MGT (ILOM)

12

U27

Storage Server or Database Server

NET 0

13

U27

Storage Server or Database Server

NET MGT (ILOM)

14

U25

Storage Server or Database Server

NET 0

17

U25

Storage Server or Database Server

NET MGT (ILOM)

18

U23

Storage Server or Database Server

NET 0

21

U23

Storage Server or Database Server

NET MGT (ILOM)

22

U22

RDMA Network Fabric Leaf Switch

NET MGT 0

45

U20

RDMA Network Fabric Leaf Switch

NET MGT 0

46

U18

Storage Server or Database Server

NET 0

25

U18

Storage Server or Database Server

NET MGT (ILOM)

26

U16

Storage Server or Database Server

NET 0

29

U16

Storage Server or Database Server

NET MGT (ILOM)

30

U14

Storage Server or Database Server

NET 0

31

U14

Storage Server or Database Server

NET MGT (ILOM)

32

U12

Storage Server or Database Server

NET 0

33

U12

Storage Server or Database Server

NET MGT (ILOM)

34

U10

Storage Server or Database Server

NET 0

35

U10

Storage Server or Database Server

NET MGT (ILOM)

36

U8

Storage Server or Database Server

NET 0

37

U8

Storage Server or Database Server

NET MGT (ILOM)

38

U6

Storage Server

NET 0

39

U6

Storage Server

NET MGT (ILOM)

40

U4

Storage Server

NET 0

41

U4

Storage Server

NET MGT (ILOM)

42

U2

Storage Server

NET 0

43

U2

Storage Server

NET MGT (ILOM)

44

U1

RDMA Network Spine Switch

NET MGT 0

47

PDU-A

Power Distribution Unit (PDU)

NET MGT

19

PDU-B

Power Distribution Unit (PDU)

NET MGT

23