21 Cabling Tables for Oracle Exadata Storage Expansion Rack X10M
This section shows the cable layouts for Oracle Exadata Storage Expansion Rack X10M.
- Rack Layout
This topic shows the rack layout for Oracle Exadata Storage Expansion Rack X10M. - Integrated Lights Out Manager (ILOM) Cabling
This topic shows the ILOM network cabling for Oracle Exadata Storage Expansion Rack X10M. - Administration Network Cabling
This topic shows the administration network cabling for the Oracle Exadata Storage Expansion Rack X10M. - Single Phase Power Distribution Unit Cabling
This topic shows the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack X10M. - Three Phase Power Distribution Unit Cabling
This topic shows the cabling routes from each three-phase power distribution unit (PDU) to the power supplies configured in Oracle Exadata Storage Expansion Rack X10M. - RDMA Network Fabric Cabling
Use the following RDMA Network Fabric cabling information for Oracle Exadata Storage Expansion Rack X10M.
Parent topic: Cabling Information for Oracle Exadata Database Machine
21.1 Rack Layout
This topic shows the rack layout for Oracle Exadata Storage Expansion Rack X10M.
The following diagram shows the component positioning in a fully populated Oracle Exadata Storage Expansion Rack X10M.
Figure 21-1 Rack Layout for Oracle Exadata Storage Expansion Rack X10M
Note:
-
The Exadata Storage Servers are oriented so that all cabling is rear-facing.
-
The network switches are oriented with rear-facing network ports.
21.2 Integrated Lights Out Manager (ILOM) Cabling
This topic shows the ILOM network cabling for Oracle Exadata Storage Expansion Rack X10M.
The ILOM port on the servers is labeled NET MGT, and connects to the Management Network Switch located in rack unit 21 on Oracle Exadata Storage Expansion Racks.
The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack X10M:
Table 21-1 ILOM Cabling for Oracle Exadata Storage Expansion Rack X10M
From Rack Unit | Type of Equipment | Gigabit Ethernet Port |
---|---|---|
U41 |
Storage Server |
16 |
U39 |
Storage Server |
2 |
U37 |
Storage Server |
4 |
U35 |
Storage Server |
6 |
U33 |
Storage Server |
8 |
U31 |
Storage Server |
10 |
U29 |
Storage Server |
12 |
U27 |
Storage Server |
14 |
U25 |
Storage Server |
18 |
U23 |
Storage Server |
22 |
U18 |
Storage Server |
26 |
U16 |
Storage Server |
30 |
U14 |
Storage Server |
32 |
U12 |
Storage Server |
34 |
U10 |
Storage Server |
36 |
U8 |
Storage Server |
38 |
U6 |
Storage Server |
40 |
U4 |
Storage Server |
42 |
U2 |
Storage Server |
44 |
PDU-A |
PDU |
19 |
PDU-B |
PDU |
20 |
21.3 Administration Network Cabling
This topic shows the administration network cabling for the Oracle Exadata Storage Expansion Rack X10M.
The port on the storage servers is labeled NET0, and connects to the Management Network Switch located in rack unit 21 on Oracle Exadata Storage Expansion Racks.
The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Rack X10M
Table 21-2 Administration Network Cabling for Oracle Exadata Storage Expansion Rack X10M
From Rack Unit | Type of Equipment | Management Network Switch Port |
---|---|---|
U41 |
Storage Server |
15 |
U39 |
Storage Server |
1 |
U37 |
Storage Server |
3 |
U35 |
Storage Server |
5 |
U33 |
Storage Server |
7 |
U31 |
Storage Server |
9 |
U29 |
Storage Server |
11 |
U27 |
Storage Server |
13 |
U25 |
Storage Server |
17 |
U23 |
Storage Server |
21 |
U22 |
RDMA Network Fabric leaf switch |
45 |
U20 |
RDMA Network Fabric leaf switch |
46 |
U18 |
Storage Server |
25 |
U16 |
Storage Server |
29 |
U14 |
Storage Server |
31 |
U12 |
Storage Server |
33 |
U10 |
Storage Server |
35 |
U8 |
Storage Server |
37 |
U6 |
Storage Server |
39 |
U4 |
Storage Server |
41 |
U2 |
Storage Server |
43 |
U1 |
RDMA Network Fabric spine switch |
47 |
21.4 Single Phase Power Distribution Unit Cabling
This topic shows the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack X10M.
The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X10M.
Table 21-3 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X10M
Rack Slot | PDU-A / PSU 0 | PDU-B / PSU 1 | Cable Length |
---|---|---|---|
U42 | G5-6 | G0-0 | 3 meters |
U41 | G4-6 | G1-0 | 3 meters |
U40 | G4-2 | G1-4 | 3 meters |
U39 | G4-4 | G1-2 | 3 meters |
U37 | G1-5 | G4-1 | 3 meters |
U35 | G3-1 | G2-5 | 3 meters |
U33 | G1-3 | G4-3 | 3 meters |
U31 | G3-3 | G2-3 | 3 meters |
U29 | G4-0 | G1-6 | 3 meters |
U27 | G5-2 | G0-4 | 3 meters |
U26 | G0-6 | G5-0 | 3 meters |
U25 | G3-0 | G2-6 | 3 meters |
U24 | G4-1 | G1-5 | 3 meters |
U23 | G5-0 | G0-6 | 3 meters |
U22 | G1-6 | G4-0 | 3 meters |
U21 | G0-4 | G5-2 | 3 meters |
U20 | G0-3 | G5-3 | 3 meters |
U19 | G3-2 | G2-4 | 3 meters |
U18 | G2-5 | G3-1 | 3 meters |
U17 | G1-2 | G4-4 | 3 meters |
U16 | G1-4 | G4-2 | 3 meters |
U14 | G5-3 | G0-3 | 3 meters |
U12 | G5-4 | G0-2 | 3 meters |
U10 | G2-3 | G3-3 | 3 meters |
U08 | G2-4 | G3-2 | 3 meters |
U06 | G2-6 | G3-0 | 3 meters |
U04 | G0-2 | G5-4 | 3 meters |
U02 | G0-5 | G5-1 | 3 meters |
U01 | G4-3 | G1-3 | 3 meters |
21.5 Three Phase Power Distribution Unit Cabling
This topic shows the cabling routes from each three-phase power distribution unit (PDU) to the power supplies configured in Oracle Exadata Storage Expansion Rack X10M.
The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X10M.
Table 21-4 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X10M
Rack Slot | PDU-A / PSU 0 | PDU-B / PSU 1 | Cable Length |
---|---|---|---|
U42 | G5-4 | G2-2 | 3 meters |
U41 | G5-2 | G2-4 | 3 meters |
U40 | G5-1 | G2-5 | 3 meters |
U39 | G4-6 | G1-0 | 3 meters |
U37 | G4-1 | G1-5 | 3 meters |
U35 | G4-5 | G1-1 | 3 meters |
U33 | G5-5 | G2-1 | 3 meters |
U31 | G4-2 | G1-4 | 3 meters |
U29 | G5-3 | G2-3 | 3 meters |
U27 | G3-2 | G0-4 | 3 meters |
U26 | G5-0 | G2-6 | 3 meters |
U25 | G3-0 | G0-6 | 3 meters |
U24 | G3-1 | G0-5 | 3 meters |
U23 | G3-5 | G0-1 | 3 meters |
U22 | G1-6 | G4-0 | 3 meters |
U21 | G2-6 | G5-0 | 3 meters |
U20 | G1-5 | G4-1 | 3 meters |
U19 | G1-1 | G4-5 | 3 meters |
U18 | G1-4 | G4-2 | 3 meters |
U17 | G2-1 | G5-5 | 3 meters |
U16 | G1-3 | G4-3 | 3 meters |
U14 | G0-5 | G3-1 | 3 meters |
U12 | G2-5 | G5-1 | 3 meters |
U10 | G0-3 | G3-3 | 3 meters |
U08 | G2-3 | G5-3 | 3 meters |
U06 | G2-4 | G5-2 | 3 meters |
U04 | G0-6 | G3-0 | 3 meters |
U02 | G0-0 | G3-6 | 3 meters |
U01 | G1-0 | G4-6 | 3 meters |
21.6 RDMA Network Fabric Cabling
Use the following RDMA Network Fabric cabling information for Oracle Exadata Storage Expansion Rack X10M.
Table 21-5 RDMA Network Fabric Cabling for Oracle Exadata Storage Expansion Rack X10M Full Rack
From Rack Unit | Port | To RDMA Network Fabric Switch Rack Unit | Port | Description |
---|---|---|---|---|
U41 |
PCIe Slot 5, Port 2 |
U22 |
15 |
3 meters |
U41 |
PCIe Slot 5, Port 1 |
U20 |
15 |
3 meters |
U39 |
PCIe Slot 5, Port 2 |
U22 |
08 |
3 meters |
U39 |
PCIe Slot 5, Port 1 |
U20 |
08 |
3 meters |
U37 |
PCIe Slot 5, Port 2 |
U22 |
09 |
3 meters |
U37 |
PCIe Slot 5, Port 1 |
U20 |
09 |
3 meters |
U35 |
PCIe Slot 5, Port 2 |
U22 |
10 |
3 meters |
U35 |
PCIe Slot 5, Port 1 |
U20 |
10 |
3 meters |
U33 |
PCIe Slot 5, Port 2 |
U22 |
11 |
3 meters |
U33 |
PCIe Slot 5, Port 1 |
U20 |
11 |
3 meters |
U31 |
PCIe Slot 5, Port 2 |
U22 |
12 |
3 meters |
U31 |
PCIe Slot 5, Port 1 |
U20 |
12 |
3 meters |
U29 |
PCIe Slot 5, Port 2 |
U22 |
13 |
3 meters |
U29 |
PCIe Slot 5, Port 1 |
U20 |
13 |
3 meters |
U27 |
PCIe Slot 5, Port 2 |
U22 |
14 |
3 meters |
U27 |
PCIe Slot 5, Port 1 |
U20 |
14 |
3 meters |
U25 |
PCIe Slot 5, Port 2 |
U22 |
16 |
3 meters |
U25 |
PCIe Slot 5, Port 1 |
U20 |
16 |
3 meters |
U23 |
PCIe Slot 5, Port 2 |
U22 |
18 |
3 meters |
U23 |
PCIe Slot 5, Port 1 |
U20 |
18 |
3 meters |
U18 |
PCIe Slot 5, Port 2 |
U22 |
20 |
3 meters |
U18 |
PCIe Slot 5, Port 1 |
U20 |
20 |
3 meters |
U14 |
PCIe Slot 5, Port 2 |
U22 |
23 |
3 meters |
U14 |
PCIe Slot 5, Port 1 |
U20 |
23 |
3 meters |
U12 |
PCIe Slot 5, Port 2 |
U22 |
24 |
3 meters |
U12 |
PCIe Slot 5, Port 1 |
U20 |
24 |
3 meters |
U10 |
PCIe Slot 5, Port 2 |
U22 |
25 |
3 meters |
U10 |
PCIe Slot 5, Port 1 |
U20 |
25 |
3 meters |
U08 |
PCIe Slot 5, Port 2 |
U22 |
26 |
3 meters |
U08 |
PCIe Slot 5, Port 1 |
U20 |
26 |
3 meters |
U06 |
PCIe Slot 5, Port 2 |
U22 |
27 |
3 meters |
U06 |
PCIe Slot 5, Port 1 |
U20 |
27 |
3 meters |
U04 |
PCIe Slot 5, Port 2 |
U22 |
28 |
3 meters |
U04 |
PCIe Slot 5, Port 1 |
U20 |
28 |
3 meters |
U02 |
PCIe Slot 5, Port 2 |
U22 |
29 |
3 meters |
U02 |
PCIe Slot 5, Port 1 |
U20 |
29 |
3 meters |