21 Cabling Tables for Oracle Exadata Storage Expansion Rack X10M

This section shows the cable layouts for Oracle Exadata Storage Expansion Rack X10M.

21.1 Rack Layout

This topic shows the rack layout for Oracle Exadata Storage Expansion Rack X10M.

The following diagram shows the component positioning in a fully populated Oracle Exadata Storage Expansion Rack X10M.

Figure 21-1 Rack Layout for Oracle Exadata Storage Expansion Rack X10M



Note:

  • The Exadata Storage Servers are oriented so that all cabling is rear-facing.

  • The network switches are oriented with rear-facing network ports.

21.2 Integrated Lights Out Manager (ILOM) Cabling

This topic shows the ILOM network cabling for Oracle Exadata Storage Expansion Rack X10M.

The ILOM port on the servers is labeled NET MGT, and connects to the Management Network Switch located in rack unit 21 on Oracle Exadata Storage Expansion Racks.

The following table shows the cable connections from the servers to the ILOM switch in Oracle Exadata Storage Expansion Rack X10M:

Table 21-1 ILOM Cabling for Oracle Exadata Storage Expansion Rack X10M

From Rack Unit Type of Equipment Gigabit Ethernet Port

U41

Storage Server

16

U39

Storage Server

2

U37

Storage Server

4

U35

Storage Server

6

U33

Storage Server

8

U31

Storage Server

10

U29

Storage Server

12

U27

Storage Server

14

U25

Storage Server

18

U23

Storage Server

22

U18

Storage Server

26

U16

Storage Server

30

U14

Storage Server

32

U12

Storage Server

34

U10

Storage Server

36

U8

Storage Server

38

U6

Storage Server

40

U4

Storage Server

42

U2

Storage Server

44

PDU-A

PDU

19

PDU-B

PDU

20

21.3 Administration Network Cabling

This topic shows the administration network cabling for the Oracle Exadata Storage Expansion Rack X10M.

The port on the storage servers is labeled NET0, and connects to the Management Network Switch located in rack unit 21 on Oracle Exadata Storage Expansion Racks.

The following table shows the cable connections from the rack components to the Management Network Switch in Oracle Exadata Storage Expansion Rack X10M

Table 21-2 Administration Network Cabling for Oracle Exadata Storage Expansion Rack X10M

From Rack Unit Type of Equipment Management Network Switch Port

U41

Storage Server

15

U39

Storage Server

1

U37

Storage Server

3

U35

Storage Server

5

U33

Storage Server

7

U31

Storage Server

9

U29

Storage Server

11

U27

Storage Server

13

U25

Storage Server

17

U23

Storage Server

21

U22

RDMA Network Fabric leaf switch

45

U20

RDMA Network Fabric leaf switch

46

U18

Storage Server

25

U16

Storage Server

29

U14

Storage Server

31

U12

Storage Server

33

U10

Storage Server

35

U8

Storage Server

37

U6

Storage Server

39

U4

Storage Server

41

U2

Storage Server

43

U1

RDMA Network Fabric spine switch

47

21.4 Single Phase Power Distribution Unit Cabling

This topic shows the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack X10M.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X10M.

Table 21-3 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X10M

Rack Slot PDU-A / PSU 0 PDU-B / PSU 1 Cable Length
U42 G5-6 G0-0 3 meters
U41 G4-6 G1-0 3 meters
U40 G4-2 G1-4 3 meters
U39 G4-4 G1-2 3 meters
U37 G1-5 G4-1 3 meters
U35 G3-1 G2-5 3 meters
U33 G1-3 G4-3 3 meters
U31 G3-3 G2-3 3 meters
U29 G4-0 G1-6 3 meters
U27 G5-2 G0-4 3 meters
U26 G0-6 G5-0 3 meters
U25 G3-0 G2-6 3 meters
U24 G4-1 G1-5 3 meters
U23 G5-0 G0-6 3 meters
U22 G1-6 G4-0 3 meters
U21 G0-4 G5-2 3 meters
U20 G0-3 G5-3 3 meters
U19 G3-2 G2-4 3 meters
U18 G2-5 G3-1 3 meters
U17 G1-2 G4-4 3 meters
U16 G1-4 G4-2 3 meters
U14 G5-3 G0-3 3 meters
U12 G5-4 G0-2 3 meters
U10 G2-3 G3-3 3 meters
U08 G2-4 G3-2 3 meters
U06 G2-6 G3-0 3 meters
U04 G0-2 G5-4 3 meters
U02 G0-5 G5-1 3 meters
U01 G4-3 G1-3 3 meters

21.5 Three Phase Power Distribution Unit Cabling

This topic shows the cabling routes from each three-phase power distribution unit (PDU) to the power supplies configured in Oracle Exadata Storage Expansion Rack X10M.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X10M.

Table 21-4 Three Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X10M

Rack Slot PDU-A / PSU 0 PDU-B / PSU 1 Cable Length
U42 G5-4 G2-2 3 meters
U41 G5-2 G2-4 3 meters
U40 G5-1 G2-5 3 meters
U39 G4-6 G1-0 3 meters
U37 G4-1 G1-5 3 meters
U35 G4-5 G1-1 3 meters
U33 G5-5 G2-1 3 meters
U31 G4-2 G1-4 3 meters
U29 G5-3 G2-3 3 meters
U27 G3-2 G0-4 3 meters
U26 G5-0 G2-6 3 meters
U25 G3-0 G0-6 3 meters
U24 G3-1 G0-5 3 meters
U23 G3-5 G0-1 3 meters
U22 G1-6 G4-0 3 meters
U21 G2-6 G5-0 3 meters
U20 G1-5 G4-1 3 meters
U19 G1-1 G4-5 3 meters
U18 G1-4 G4-2 3 meters
U17 G2-1 G5-5 3 meters
U16 G1-3 G4-3 3 meters
U14 G0-5 G3-1 3 meters
U12 G2-5 G5-1 3 meters
U10 G0-3 G3-3 3 meters
U08 G2-3 G5-3 3 meters
U06 G2-4 G5-2 3 meters
U04 G0-6 G3-0 3 meters
U02 G0-0 G3-6 3 meters
U01 G1-0 G4-6 3 meters

21.6 RDMA Network Fabric Cabling

Use the following RDMA Network Fabric cabling information for Oracle Exadata Storage Expansion Rack X10M.

Table 21-5 RDMA Network Fabric Cabling for Oracle Exadata Storage Expansion Rack X10M Full Rack

From Rack Unit Port To RDMA Network Fabric Switch Rack Unit Port Description

U41

PCIe Slot 5, Port 2

U22

15

3 meters

U41

PCIe Slot 5, Port 1

U20

15

3 meters

U39

PCIe Slot 5, Port 2

U22

08

3 meters

U39

PCIe Slot 5, Port 1

U20

08

3 meters

U37

PCIe Slot 5, Port 2

U22

09

3 meters

U37

PCIe Slot 5, Port 1

U20

09

3 meters

U35

PCIe Slot 5, Port 2

U22

10

3 meters

U35

PCIe Slot 5, Port 1

U20

10

3 meters

U33

PCIe Slot 5, Port 2

U22

11

3 meters

U33

PCIe Slot 5, Port 1

U20

11

3 meters

U31

PCIe Slot 5, Port 2

U22

12

3 meters

U31

PCIe Slot 5, Port 1

U20

12

3 meters

U29

PCIe Slot 5, Port 2

U22

13

3 meters

U29

PCIe Slot 5, Port 1

U20

13

3 meters

U27

PCIe Slot 5, Port 2

U22

14

3 meters

U27

PCIe Slot 5, Port 1

U20

14

3 meters

U25

PCIe Slot 5, Port 2

U22

16

3 meters

U25

PCIe Slot 5, Port 1

U20

16

3 meters

U23

PCIe Slot 5, Port 2

U22

18

3 meters

U23

PCIe Slot 5, Port 1

U20

18

3 meters

U18

PCIe Slot 5, Port 2

U22

20

3 meters

U18

PCIe Slot 5, Port 1

U20

20

3 meters

U14

PCIe Slot 5, Port 2

U22

23

3 meters

U14

PCIe Slot 5, Port 1

U20

23

3 meters

U12

PCIe Slot 5, Port 2

U22

24

3 meters

U12

PCIe Slot 5, Port 1

U20

24

3 meters

U10

PCIe Slot 5, Port 2

U22

25

3 meters

U10

PCIe Slot 5, Port 1

U20

25

3 meters

U08

PCIe Slot 5, Port 2

U22

26

3 meters

U08

PCIe Slot 5, Port 1

U20

26

3 meters

U06

PCIe Slot 5, Port 2

U22

27

3 meters

U06

PCIe Slot 5, Port 1

U20

27

3 meters

U04

PCIe Slot 5, Port 2

U22

28

3 meters

U04

PCIe Slot 5, Port 1

U20

28

3 meters

U02

PCIe Slot 5, Port 2

U22

29

3 meters

U02

PCIe Slot 5, Port 1

U20

29

3 meters