14 Cabling Tables for Oracle Exadata X8M

These tables show the cable layouts for Oracle Exadata X8M-2 and X8M-8.

Note:

For ease of reading, the name "Oracle Exadata Rack" is used when information refers to both Oracle Exadata and Oracle Exadata Storage Expansion Rack.

14.1 Rack Layout Diagrams

The diagrams in this topic show the rack layout for Oracle Exadata X8M-2 and X8M-8.

The slot numbers for each component is shown in the following images.

The following image shows the front and rear views of the component positioning in Oracle Exadata X8M-2 Full Rack. The front view is shown on the left, and the rear view is shown on the right.

Figure 14-1 Rack Layout of Oracle Exadata X8M-2 Full Rack



The following image shows the front and rear views of the component positioning in Oracle Exadata X8M-8.

Figure 14-2 Rack Layout of Oracle Exadata X8M-8



14.2 Integrated Lights Out Manager (ILOM) Cabling Tables

This topic contains the tables for the ILOM network cabling.

The following tables are in this section:

  • Table 14-1 ILOM Cabling for Oracle Exadata X8M-2 Full Rack
  • Table 14-2 ILOM Cabling for Oracle Exadata X8M-8 Full Rack

In the following tables, Un denotes the unit height in the rack, where n is the number, such as U20. The cables used for ILOM are red in color.

The following table shows the cable connections from the ILOM port (NET MGT) on the servers to the Management Network Switch:

Table 14-1 ILOM Cabling for Oracle Exadata X8M-2 Full Rack

From Rack Unit Type of Equipment Management Network Switch Port

U39

Storage Server

2

U37

Storage Server

4

U35

Storage Server

6

U33

Storage Server

8

U31

Storage Server

10

U29

Storage Server

12

U27

Storage Server

14

U26

Database server

16

U25

Database server

18

U24

Database server

20

U23

Database server

22

U22 (NET MGT 0)

Leaf switch

45

U20 (NET MGT 0)

Leaf switch

46

U19

Database server

24

U18

Database server

26

U17

Database server

28

U16

Database server

30

U14

Storage Server

32

U12

Storage Server

34

U10

Storage Server

36

U8

Storage Server

38

U6

Storage Server

40

U4

Storage Server

42

U2

Storage Server

44

The following table shows the cable connections from the ILOM port on the servers to the Management Network Switch:

Table 14-2 ILOM Cabling for Oracle Exadata X8M-8 Full Rack

From Rack Unit Type of Equipment Management Network Switch Port

U41

Storage Server

2

U39

Storage Server

4

U37

Storage Server

6

U35

Storage Server

8

U33

Storage Server

10

U31

Storage Server

12

U29

Storage Server

14

U24

Database server

16

U16

Database server

18

U14

Storage Server

20

U12

Storage Server

22

U10

Storage Server

24

U8

Storage Server

26

U6

Storage Server

28

U4

Storage Server

30

U2

Storage Server

32

14.3 Administrative Ethernet Port Cabling Tables

This topic contains the tables for the administrative network cabling.

The Management Network Switch is located in rack unit 21 on Oracle Exadata X8M-2 racks and in rack unit 22 on Oracle Exadata X8M-8 racks.

In the following tables, Un denotes the unit height in the rack, where n is the number, such as U20. The cables used for the Management Network Switch are blue in color. The following tables are in this section:

  • Table 14-3 Administrative Network Cabling for Oracle Exadata X8M-2 Full Rack
  • Table 14-4 Administrative Network Cabling for Oracle Exadata X8M-8 Full Rack

The following table shows the cable connections from the Admin port in the rack components to the Management Network Switch:

Table 14-3 Administrative Network Cabling for Oracle Exadata X8M-2 Full Rack

From Rack Unit Type of Equipment Management Network Switch Port

U39

Storage Server

1

U37

Storage Server

3

U35

Storage Server

5

U33

Storage Server

7

U31

Storage Server

9

U29

Storage Server

11

U27

Storage Server

13

U26

Database server

15

U25

Database server

17

U24

Database server

19

U23

Database server

21

U22

RDMA Network Fabric Switch

45

U20

RDMA Network Fabric Switch

46

U19

Database server

23

U18

Database server

25

U17

Database server

27

U16

Database server

29

U14

Storage Server

31

U12

Storage Server

33

U10

Storage Server

35

U8

Storage Server

37

U6

Storage Server

39

U4

Storage Server

41

U2

Storage Server

43

U1

RDMA Network Fabric Switch

Note that the spine switch is not included by default on Oracle Exadata X8M-2 racks, but port 47 is still reserved on the Management Network Switch for the spine RDMA Network Fabric switch.

47

The following table shows the cable connections from the Admin port in the rack components to the Management Network Switch:

Table 14-4 Administrative Network Cabling for Oracle Exadata X8M-8 Full Rack

From Rack Unit Type of Equipment Management Network Switch Port

U41

Storage Server

1

U39

Storage Server

3

U37

Storage Server

5

U35

Storage Server

7

U33

Storage Server

9

U31

Storage Server

11

U29

Storage Server

13

U24

Database server

15

U23

RDMA Network Fabric Switch

33

U21

RDMA Network Fabric Switch

34

U16

Database server

17

U14

Storage Server

19

U12

Storage Server

21

U10

Storage Server

23

U8

Storage Server

25

U6

Storage Server

27

U4

Storage Server

29

U2

Storage Server

31

U1

RDMA Network Fabric Switch

Note that the spine switch is not included by default on Oracle Exadata X8M-8 racks, but port 47 is still reserved on the Management Network Switch for the spine RDMA Network Fabric switch.

35

14.4 Single Phase Power Distribution Unit Cabling Tables

These tables show the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in an Oracle Exadata Database Machine X8M-2 and X8M-8.

14.4.1 Single Phase PDU Cabling for Oracle Exadata Database Machine X8M-2 Full Rack

Single phase cabling for the Oracle Exadata Database Machine X8M-2 Full Rack routes from each power distribution unit (PDU) to the power supplies.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

Table 14-5 Single Phase PDU Cabling for Oracle Exadata Database Machine X8M-2 Full Rack

Rack Unit PS PDU-A PDU-B/PS1 Cable Length

U42

PS0

G5-3

G0-3

2 meters

U41

PS0

G5-5

G0-1

2 meters

U40

PS0

G5-6

G0-0

2 meters

U39

PS0

G3-6

G2-0

2 meters

U37

PS0

G3-0

G2-6

2 meters

U35

PS0

G5-4

G0-2

2 meters

U33

PS0

G4-1

G1-5

2 meters

U31

PS0

G5-2

G0-4

2 meters

U29

PS0

G5-1

G0-5

2 meters

U27

PS0

G4-3

G1-3

2 meters

U26

PS0

G4-6

G1-0

2 meters

U25

PS0

G4-5

G1-1

2 meters

U24

PS0

G4-2

G1-4

2 meters

U23

PS0

G4-0

G1-6

2 meters

U22

PS2

G1-6

G4-0

2 meters

U21

PS2

G1-5

G4-1

2 meters

U20

PS2

G1-2

G4-4

2 meters

U19

PS0

G3-2

G2-4

2 meters

U18

PS0

G2-6

G3-0

2 meters

U17

PS0

G0-6

G5-0

2 meters

U16

PS0

G0-3

G5-3

2 meters

U14

PS0

G2-3

G3-3

2 meters

U12

PS0

G2-4

G3-2

2 meters

U10

PS0

G2-0

G3-6

2 meters

U8

PS0

G2-5

G3-1

2 meters

U6

PS0

G0-0

G5-6

2 meters

U4

PS0

G0-1

G5-5

2 meters

U2

PS0

G1-0

G4-6

2 meters

U1

PS2

G3-5

G2-1

3 meters

14.4.2 Single Phase PDU Cabling for Oracle Exadata Database Machine X8M-8 Full Rack

Single phase cabling for the Oracle Exadata Database Machine X8M-8 Full Rack routes from each power distribution unit (PDU) to the power supplies.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four. The PDU connections in the table below list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

Table 14-6 Single Phase PDU Cabling for Oracle Exadata Database Machine X8M-8 Full Rack

Rack Unit PS PDU-A PDU-B/PSU 1 Cable Length

U41

PS0

G3-5

G2-1

2 meters

U39

PS0

G5-4

G0-2

2 meters

U37

PS0

G5-2

G0-4

2 meters

U35

PS0

G5-0

G0-6

2 meters

U33

PS0

G3-4

G2-2

2 meters

U31

PS0

G4-3

G1-3

2 meters

U29

PS0

G3-6

G2-0

2 meters

U24

PS0

G2-7 (PS2)

G3-7 (PS3)

1 meter

U24

PS0

G4-7

G1-7

1 meter

U23

PS2

G3-1

G2-5

2 meters

U22

PS2

G2-6

G3-0

2 meters

U21

PS2

G1-6

G4-0

2 meters

U16

PS0

G1-7 (PS2)

G4-7 (PS3)

1 meter

U16

PS0

G3-7

G2-7

1 meter

U14 (only 2 DB servers)

PS0

G2-0

G3-6

2 meters

U12 (only 2 DB servers)

PS0

G1-3

G4-3

2 meters

U10 (only 2 DB servers)

PS0

G1-0

G4-6

2 meters

U10 (3 DB servers)

PS0

G0-7 (PS2)

G5-7 (PS3)

1 meter

U10 (3 DB servers)

PS0

G5-7

G0-7

2 meters

U8

PS0

G0-6

G5-0

2 meters

U6

PS0

G0-4

G5-2

2 meters

U4

PS0

G0-3

G5-3

2 meters

U2

PS0

G0-1

G5-5

2 meters

U1

PS2

G4-0

G1-6

3 meters

14.5 Three-Phase Power Distribution Unit Cabling Tables

The following topics contains the tables for a three-phase power distribution unit (PDU) in Oracle Exadata X8M-2 and X8M-8.

14.5.1 Three-Phase PDU Cabling for Oracle Exadata Database Machine X8M-2 Full Rack

Three-phase cabling for the Oracle Exadata Database Machine X8M-2 Full Rack routes from each power distribution unit (PDU) to the power supplies configured in each rack.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

Table 14-7 Three Phase PDU Cabling for Oracle Exadata Database Machine X8M-2 Full Rack

Rack Unit PDU-A/PSU 0 PDU-B/PSU 1 Cable Length

U42

G5-4

G2-2

2 meters

U41

G5-2

G2-4

2 meters

U40

G5-1

G2-5

2 meters

U39

G5-6

G2-0

2 meters

U37

G3-5

G0-1

2 meters

U35

G3-0

G0-6

2 meters

U33

G5-5

G2-1

2 meters

U31

G5-3

G2-3

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-2

G0-4

2 meters

U26

G5-0

G2-6

2 meters

U25

G4-5

G1-1

2 meters

U24

G3-1

G0-5

2 meters

U23

G4-1

G1-5

2 meters

U22

G1-6

G4-0

2 meters

U21

G2-6

G5-0

2 meters

U20

G1-5

G4-1

2 meters

U19

G1-1

G4-5

2 meters

U18

G1-4

G4-2

2 meters

U17

G2-1

G5-5

2 meters

U16

G2-3

G5-3

2 meters

U14

G0-5

G3-1

2 meters

U12

G2-5

G5-1

2 meters

U10

G0-3

G3-3

2 meters

U8

G1-3

G4-3

2 meters

U6

G2-4

G5-2

2 meters

U4

G0-6

G3-0

2 meters

U2

G0-0

G3-6

2 meters

U1

G1-0

G4-6

3 meters

14.5.2 Three Phase PDU Cabling for Oracle Exadata Database Machine X8M-8 Full Rack

Three-phase cabling for the Oracle Exadata Database Machine X8M-8 Full Rack routes from each power distribution unit (PDU) to the power supplies configured in each rack.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

Table 14-8 Three Phase PDU Cabling for Oracle Exadata Database Machine X8M-8 Full Rack

Rack Unit PDU-A/PSU 0 PDU-B/PSU 1 Cable Length

U41

G5-5

G2-1

2 meters

U39

G5-4

G2-2

2 meters

U37

G5-2

G2-4

2 meters

U35

G5-1

G2-5

2 meters

U33

G5-0

G2-6

2 meters

U31

G4-6

G1-0

2 meters

U29

G4-4

G1-2

2 meters

U24

G3-7 (PS2)

G0-7 (PS3)

2 meters

U24

G4-7

G1-7

2 meters

U23

G3-1

G0-5

2 meters

U22

G3-0

G0-6

2 meters

U21

G2-5

G5-1

2 meters

U16

G2-7 (PS2)

G5-7 (PS3)

2 meters

U16

G1-7

G4-7

2 meters

U14 (only 2 DB servers)

G1-3

G4-3

2 meters

U12 (only 2 DB servers)

G1-0

G4-6

2 meters

U10 (only 2 DB servers)

G0-6

G3-0

2 meters

U10 (3 DB servers)

G5-7 (PS2)

G2-7 (PS3)

1 meter

U10 (3 DB servers)

G0-7

G3-7

1 meter

U8

G0-5

G3-1

2 meters

U6

G0-4

G3-2

2 meters

U4

G0-2

G3-4

2 meters

U2

G0-1

G3-5

2 meters

U1

G0-0

G3-6

3 meters

14.6 RDMA Network Fabric Network Cabling Tables

This section contains the tables for RDMA Network Fabric network cabling for Oracle Exadata X8M-2 and X8M-8 racks.

14.6.1 RDMA Network Fabric Network Cabling Tables for X8M-2 Racks

This topic contains the tables for RDMA Network Fabric network cabling for Oracle Exadata X8M-2 racks.

The RoCE Network Fabric switches are located in rack units 20 and 22 for Oracle Exadata X8M-2.

You can use the following tables for both flexible and fixed configurations. This first table contains RDMA Network Fabric cabling information for the database servers, each of which occupies 1RU. The second table covers the storage servers, each of which occupies 2RU. The last table contains the inter-switch cabling between the leaf switches.

Note:

Not all the slots shown in the tables below will be used in a single configuration. Match the rack component with the appropriate slot in the tables below to determine how to cable that particular component.

In the following tables, Un denotes the slot in the rack, where n is the number, such as U20. Pn denotes the RDMA Network Fabric port n, where n is port number, such as P1. The cables used for the RDMA Network Fabric switch are black in color. The following tables are in this section:

  • Table 14-9 RDMA Network Fabric Network Cabling for Oracle Exadata X8M-2 Database Servers
  • Table 14-10 RDMA Network Fabric Network Cabling for Oracle Exadata X8M-2 Storage Servers
  • Table 14-11 RDMA Network Fabric Inter-Switch Cabling for Oracle Exadata X8M-2

The following table lists the location, ports and cables for the RDMA Network Fabric connections for database servers in an Oracle Exadata X8M-2 rack.

Table 14-9 RDMA Network Fabric Network Cabling for Oracle Exadata Database Machine X8M-2 Database Servers

From Rack Unit Port To RDMA Network Fabric Switch Port Description

U39

PCIe 2, P2

U22

08

3 meters

U39

PCIe 2, P1

U20

08

3 meters

U37

PCIe 2, P2

U22

09

3 meters

U37

PCIe 2, P1

U20

09

3 meters

U35

PCIe 2, P2

U22

10

3 meters

U35

PCIe 2, P1

U20

10

3 meters

U33

PCIe 2, P2

U22

11

3 meters

U33

PCIe 2, P1

U20

11

3 meters

U31

PCIe 2, P2

U22

12

3 meters

U31

PCIe 2, P1

U20

12

3 meters

U29

PCIe 2, P2

U22

13

3 meters

U29

PCIe 2, P1

U20

13

3 meters

U27

PCIe 2, P2

U22

14

3 meters

U27

PCIe 2, P1

U20

14

3 meters

U26

PCIe 2, P2

U22

15

3 meters

U26

PCIe 2, P1

U20

15

3 meters

U25

PCIe 2, P2

U22

16

3 meters

U25

PCIe 2, P1

U20

16

3 meters

U24

PCIe 2, P2

U22

17

3 meters

U24

PCIe 2, P1

U20

17

3 meters

U23

PCIe 2, P2

U22

18

3 meters

U23

PCIe 2, P1

U20

18

3 meters

U19

PCIe 2, P2

U22

19

3 meters

U19

PCIe 2, P1

U20

19

3 meters

U18

PCIe 2, P2

U22

20

3 meters

U18

PCIe 2, P1

U20

20

3 meters

U17

PCIe 2, P2

U22

21

3 meters

U17

PCIe 2, P1

U20

21

3 meters

U16

PCIe 2, P2

U22

22

3 meters

U16

PCIe 2, P1

U20

22

3 meters

U14

PCIe 2, P2

U22

23

3 meters

U14

PCIe 2, P1

U20

23

3 meters

U12

PCIe 2, P2

U22

24

3 meters

U12

PCIe 2, P1

U20

24

3 meters

U10

PCIe 2, P2

U22

25

3 meters

U10

PCIe 2, P1

U20

25

3 meters

U08

PCIe 2, P2

U22

26

3 meters

U08

PCIe 2, P1

U20

26

3 meters

The following table lists the location, ports and cables for the RDMA Network Fabric connections for storage servers in an Oracle Exadata X8M-2 rack.

Table 14-10 RDMA Network Fabric Network Cabling for Oracle Exadata Database Machine X8M-2 Storage Servers

From Rack Unit Port To RDMA Network Fabric Switch Port Description

U41

PCIe 1, P2

U22

15

3 meters

U41

PCIe 1, P1

U20

15

3 meters

U39

PCIe 1, P2

U22

08

3 meters

U39

PCIe 1, P1

U20

08

3 meters

U37

PCIe 1, P2

U22

09

3 meters

U37

PCIe 1, P1

U20

09

3 meters

U35

PCIe 1, P2

U22

10

3 meters

U35

PCIe 1, P1

U20

10

3 meters

U33

PCIe 1, P2

U22

11

3 meters

U33

PCIe 1, P1

U20

11

3 meters

U31

PCIe 1, P2

U22

12

3 meters

U31

PCIe 1, P1

U20

12

3 meters

U29

PCIe 1, P2

U22

13

3 meters

U29

PCIe 1, P1

U20

13

3 meters

U27

PCIe 1, P2

U22

14

3 meters

U27

PCIe 1, P1

U20

14

3 meters

U25

PCIe 1, P2

U22

16

3 meters

U25

PCIe 1, P1

U20

16

3 meters

U23

PCIe 1, P2

U22

18

3 meters

U23

PCIe 1, P1

U20

18

3 meters

U18

PCIe 1, P2

U22

20

3 meters

U18

PCIe 1, P1

U20

20

3 meters

U14

PCIe 1, P2

U22

23

3 meters

U14

PCIe 1, P1

U20

23

3 meters

U12

PCIe 1, P2

U22

24

3 meters

U12

PCIe 1, P1

U20

24

3 meters

U10

PCIe 1, P2

U22

25

3 meters

U10

PCIe 1, P1

U20

25

3 meters

U08

PCIe 1, P2

U22

26

3 meters

U08

PCIe 1, P1

U20

26

3 meters

U06

PCIe 1, P2

U22

27

3 meters

U06

PCIe 1, P1

U20

27

3 meters

U04

PCIe 1, P2

U22

28

3 meters

U04

PCIe 1, P1

U20

28

3 meters

U02

PCIe 1, P2

U22

29

3 meters

U02

PCIe 1, P1

U20

29

3 meters

The following table lists the location, ports and cables for the RDMA Network Fabric connections for the leaf switches in an Oracle Exadata X8M-2 rack.

Table 14-11 RDMA Network Fabric Inter-Switch Cabling for Oracle Exadata Database Machine X8M-2

From Rack Unit Port To RDMA Network Fabric Switch Port Description

U20

04

U22

04

1 meter

U20

05

U22

05

1 meter

U20

06

U22

06

1 meter

U20

07

U22

07

1 meter

U20

30

U22

30

1 meter

U20

31

U22

31

1 meter

U20

32

U22

32

1 meter

U20

33

U22

33

1 meter

14.6.2 RDMA Network Fabric Network Cabling Tables for X8M-8 Racks

This topic contains the tables for RDMA Network Fabric network cabling for Oracle Exadata X8M-8 racks.

The RoCE Network Fabric switches are located in rack units 21 and 23 for Oracle Exadata X8M-8.

The following tables can be used for both flexible and fixed configurations. There are three sets of tables for each Exadata hardware model. One table is for storage servers, which have a 2-slot height (2RU). Another table is for the database servers, which require 5RU. The last table for each hardware model is for the inter-switch cabling, which provides the cabling information for the leaf switches.

Note:

Not all the slots shown in the tables below will be used in a single configuration. Match the rack component with the appropriate slot in the tables below to determine how to cable that particular component.

In the following tables, Un denotes the slot in the rack, where n is the number, such as U23. Pn denotes the RDMA Network Fabric port n, where n is port number, such as P1. The cables used for the RDMA Network Fabric switch are black in color. The following tables are in this section:

  • Table 14-12 RDMA Network Fabric Network Cabling for Oracle Exadata X8M-8 Database Servers
  • Table 14-13 RDMA Network Fabric Network Cabling for Oracle Exadata X8M-8 Storage Servers
  • Table 14-14 RDMA Network Fabric Inter-Switch Cabling for Oracle Exadata X8M-8

The following table lists the rack location, ports and cables for the RDMA Network Fabric connections for database servers in an Oracle Exadata X8M-8 rack.

Table 14-12 RDMA Network Fabric Network Cabling for Oracle Exadata Database Machine X8M-8 Database Servers

From Rack Unit Port To RDMA Network Fabric Switch Port Description

U24

PCIe 5, P2

U23

15

3 meters

U24

PCIe 5, P1

U21

15

3 meters

U24

PCIe 7, P2

U23

16

3 meters

U24

PCIe 7, P1

U21

16

3 meters

U24

PCIe 9, P2

U23

17

3 meters

U24

PCIe 9, P1

U21

17

3 meters

U24

PCIe 11, P2

U23

18

3 meters

U24

PCIe 11, P1

U21

18

3 meters

U16

PCIe 5, P2

U23

19

3 meters

U16

PCIe 5, P1

U21

19

3 meters

U16

PCIe 7, P2

U23

20

3 meters

U16

PCIe 7, P1

U21

20

3 meters

U16

PCIe 9, P2

U23

21

3 meters

U16

PCIe 9, P1

U21

21

3 meters

U16

PCIe 11, P2

U23

22

3 meters

U16

PCIe 11, P1

U21

22

3 meters

U10

PCIe 5, P2

U23

23

3 meters

U10

PCIe 5, P1

U21

23

3 meters

U10

PCIe 7, P2

U23

24

3 meters

U10

PCIe 7, P1

U21

24

3 meters

U10

PCIe 9, P2

U23

25

3 meters

U10

PCIe 9, P1

U21

25

3 meters

U10

PCIe 11, P2

U23

30 or 8

Note: Port 8 is the target only in a configuration with 3 database servers and 11 storage servers. Otherwise, port 30 is the target.

3 meters

U10

PCIe 11, P1

U21

30 or 8

Note: Port 8 is the target only in a configuration with 3 database servers and 11 storage servers. Otherwise, port 30 is the target.

3 meters

The following table lists the location, ports and cables for the RDMA Network Fabric connections for storage servers in an Oracle Exadata X8M-8 rack.

Table 14-13 RDMA Network Fabric Network Cabling for Oracle Exadata Database Machine X8M-8 Storage Servers

From Rack Unit Port To RDMA Network Fabric Switch Port Description

U41

PCIe 1, P2

U23

08

3 meters

U41

PCIe 1, P1

U21

08

3 meters

U39

PCIe 1, P2

U23

09

3 meters

U39

PCIe 1, P1

U21

09

3 meters

U37

PCIe 1, P2

U23

10

3 meters

U37

PCIe 1, P1

U21

10

3 meters

U35

PCIe 1, P2

U23

11

3 meters

U35

PCIe 1, P1

U21

11

3 meters

U33

PCIe 1, P2

U23

12

3 meters

U33

PCIe 1, P1

U21

12

3 meters

U31

PCIe 1, P2

U23

13

3 meters

U31

PCIe 1, P1

U21

13

3 meters

U29

PCIe 1, P2

U23

14

3 meters

U29

PCIe 1, P1

U21

14

3 meters

U14

PCIe 1, P2

U23

23

3 meters

U14

PCIe 1, P1

U21

23

3 meters

U12

PCIe 1, P2

U23

24

3 meters

U12

PCIe 1, P1

U21

24

3 meters

U10

PCIe 1, P2

U23

25

3 meters

U10

PCIe 1, P1

U21

25

3 meters

U08

PCIe 1, P2

U23

26

3 meters

U08

PCIe 1, P1

U21

26

3 meters

U06

PCIe 1, P2

U23

27

3 meters

U06

PCIe 1, P1

U21

27

3 meters

U04

PCIe 1, P2

U23

28

3 meters

U04

PCIe 1, P1

U21

28

3 meters

U02

PCIe 1, P2

U23

29

3 meters

U02

PCIe 1, P1

U21

29

3 meters

The following table lists the location, ports and cables for the RDMA Network Fabric connections for the leaf switches in an Oracle Exadata X8M-8 rack.

Table 14-14 RDMA Network Fabric Inter-Switch Cabling for Oracle Exadata Database Machine X8M-8

From Rack Unit Port To RDMA Network Fabric Switch Port Description

U21

04

U23

04

1 meter

U21

05

U23

05

1 meter

U21

06

U23

06

1 meter

U21

07

U23

07

1 meter

U21

30 or 34

Note: Port 34 is used only in a configuration with 3 database servers and 11 storage servers. Otherwise, port 30 is used.

U23

30 or 34

Note: Port 34 is used only in a configuration with 3 database servers and 11 storage servers. Otherwise, port 30 is used.

1 meter

U21

31

U23

31

1 meter

U21

32

U23

32

1 meter

U21

33

U23

33

1 meter