15.4.2 Single Phase PDU Cabling for Oracle Exadata Database Machine X8M-8 Full Rack

Single phase cabling for the Oracle Exadata Database Machine X8M-8 Full Rack routes from each power distribution unit (PDU) to the power supplies.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four. The PDU connections in the table below list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

Table 15-6 Single Phase PDU Cabling for Oracle Exadata Database Machine X8M-8 Full Rack

Rack Unit PS PDU-A PDU-B/PSU 1 Cable Length

U41

PS0

G3-5

G2-1

2 meters

U39

PS0

G5-4

G0-2

2 meters

U37

PS0

G5-2

G0-4

2 meters

U35

PS0

G5-0

G0-6

2 meters

U33

PS0

G3-4

G2-2

2 meters

U31

PS0

G4-3

G1-3

2 meters

U29

PS0

G3-6

G2-0

2 meters

U24

PS0

G2-7 (PS2)

G3-7 (PS3)

1 meter

U24

PS0

G4-7

G1-7

1 meter

U23

PS2

G3-1

G2-5

2 meters

U22

PS2

G2-6

G3-0

2 meters

U21

PS2

G1-6

G4-0

2 meters

U16

PS0

G1-7 (PS2)

G4-7 (PS3)

1 meter

U16

PS0

G3-7

G2-7

1 meter

U14 (only 2 DB servers)

PS0

G2-0

G3-6

2 meters

U12 (only 2 DB servers)

PS0

G1-3

G4-3

2 meters

U10 (only 2 DB servers)

PS0

G1-0

G4-6

2 meters

U10 (3 DB servers)

PS0

G0-7 (PS2)

G5-7 (PS3)

1 meter

U10 (3 DB servers)

PS0

G5-7

G0-7

2 meters

U8

PS0

G0-6

G5-0

2 meters

U6

PS0

G0-4

G5-2

2 meters

U4

PS0

G0-3

G5-3

2 meters

U2

PS0

G0-1

G5-5

2 meters

U1

PS2

G4-0

G1-6

3 meters