14.5.2 Three Phase PDU Cabling for Oracle Exadata X9M-8 Full Rack

Three-phase cabling for the Oracle Exadata X9M-8 Full Rack routes from each power distribution unit (PDU) to the power supplies on each server or switch.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

Table 14-8 Three Phase PDU Cabling for Oracle Exadata X9M-8 Full Rack

Rack Slot PSU to PDU-A PDU-A Outlet PSU to PDU-B PDU-B Outlet Cable Length
U41 PS0 G5-5 PS1 G2-1 3 meters
U39 PS0 G5-4 PS1 G2-2 3 meters
U37 PS0 G5-2 PS1 G2-4 3 meters
U35 PS0 G2-4 PS1 G5-2 3 meters
U33 PS0 G3-6 PS1 G0-0 3 meters
U31 PS0 G4-6 PS1 G1-0 3 meters
U29 PS0 G4-4 PS1 G1-2 3 meters
U24 PS2 G3-7 PS3 G0-7 2 meters
U24 PS0 G4-7 PS1 G1-7 2 meters
U23 PS2 G3-1 PS1 G0-5 2 meters
U22 PS2 G3-0 PS1 G0-6 2 meters
U21 PS2 G2-5 PS1 G5-1 2 meters
U16 PS2 G2-7 PS3 G5-7 2 meters
U16 PS0 G1-7 PS1 G4-7 2 meters
U14 PS0 G2-6 PS1 G5-0 3 meters
U12 PS0 G1-0 PS1 G4-6 3 meters
U10 (with 2 DB servers) PS0 G0-6 PS1 G3-0 3 meters
U10 (with 3 DB servers) PS2 G5-7 PS3 G2-7 2 meters
U10 (with 3 DB servers) PS0 G0-7 PS1 G3-7 2 meters
U08 PS0 G0-5 PS1 G3-1 3 meters
U06 PS0 G1-1 PS1 G4-5 3 meters
U04 PS0 G0-2 PS1 G3-4 3 meters
U02 PS0 G0-1 PS1 G3-5 3 meters
U01 PS2 G0-0 PS1 G3-6 3 meters