Electrical Power Requirements

The Oracle Private Cloud Appliance can operate effectively over a wide range of voltages and frequencies. However, it must have a reliable power source. Damage might occur if the ranges are exceeded. Electrical disturbances such as the following might damage the system:

  • Fluctuations caused by brownouts

  • Wide and rapid variations in input voltage levels or in input power frequency

  • Electrical storms

  • Faults in the distribution system, such as defective wiring

To protect your system from such disturbances, you should have a dedicated power distribution system, power-conditioning equipment, as well as lightning arresters or power cables to protect from electrical storms.

Each rack has two pre-installed power distribution units (PDUs). The PDUs accept different power sources. You must specify the type of PDU that is correct for your data center.

The following tables list PDU requirements.

Item 15kVA - type 6440A 15kVA - type 6441A 15kVA - type 6442A 22kVA - type 7100873 22kVA - type 7100874 24kVA - type 6444A 24kVA - type 6445A

Region

North and South America, Japan and Taiwan

EMEA and APAC (except Japan and Taiwan)

North and South America, Japan and Taiwan

North and South America, Japan and Taiwan

EMEA and APAC (except Japan and Taiwan)

North and South America, Japan and Taiwan

EMEA and APAC (except Japan and Taiwan)

Number of inputs

1

1

3

3

3

2

2

Source voltage

200-220V

220/380 - 240/415VAC

200-240V

200-240V

200-240V

200-220V

220/380 - 240/415VAC

Frequency

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

Max. line current

40A

21A

24A

36.8A

32A

34.6A

16A

Phase current

23A

21A

N/A

N/A

32A

20A

16A

Recommended circuit breaker

50A

25A

30A

50A

32A

50A

25A

Outlets

42 x C13 6 x C19

42 x C13 6 x C19

42 x C13 6 x C19

42 x C13 6 x C19

42 x C13 6 x C19

42 x C13 6 x C19

42 x C13 6 x C19

Outlet groups

6

6

6

6

6

6

6

Max. group current

20A

20A

20A

20A

20A

20A

18A

Output voltage

200-240V

220-240V

200-240V

200-240V

200-240V

220-240V

200-240V

Data center receptacle

3ph 3W + ground 60A IEC60309

3ph 4W + ground 32A IEC60309 5P 6h 400V

1ph 2W + ground 30A NEMA L6-30

1ph 2W + ground 50A Hubbell CS8265C

1ph 2W + ground 32A IEC60309 3P 6H 230V

3ph 3W + ground 60A IEC60309

3ph 4W + ground 32A IEC60309 5P 6h 400V

Table 2-1 PDU Specifications for Korea

Item 15 kVA - type 7600785 22KVA - type 7600788 24KVA - type 7600787

Region

South Korea only South Korea only South Korea only
Nominal Power Rating 15KVA 22KVA 24KVA

Number of inputs

1 3 2

Source voltage

220/380 - 240/415VAC 3Ø 220-240V 220/380 - 240/415VAC 3Ø

Frequency

50/60 Hz 50/60 Hz 50/60 Hz

Max. line current

21A 32A 18A

Phase current

21A 32A 18A

Recommended circuit breaker

25A 32A 25A

Outlets

42 x C13 6 x C19 42 x C13 6 x C19 42 x C13 6 x C19

Outlet groups

6 6 6

Max. group current

20A 16A 20A

Output voltage

220-240V 220-240V 220-240V

Data center receptacle

3ph 4W + ground 32A IEC60309 5P 6h 400V 1ph 2W + ground 32A IEC60309 3P 6H 230V 3ph 4W + ground 32A IEC60309 5P 6h 400V

Facility Power Requirements

Electrical work and installations must comply with applicable local, state, or national electrical codes. Contact your facilities manager or qualified electrician to determine what type of power is supplied to the building.

To prevent catastrophic failures, design the input power sources to ensure adequate power is provided to the power distribution units (PDUs). Use dedicated AC breaker panels for all power circuits that supply power to the PDU. When planning for power distribution requirements, balance the power load between available AC supply branch circuits. In the United States and Canada, ensure that the overall system AC input current load does not exceed 80 percent of the branch circuit AC current rating.

Provide a stable power source, such as an uninterruptable power supply (UPS) to reduce the possibility of component failures. If computer equipment is subjected to repeated power interruptions and fluctuations, then it's susceptible to a higher rate of component failure.

PDU power cords are 4 meters (13.12 feet) long, and 1 to 1.5 meters (3.3 to 4.9 feet) of the cord will be routed within the rack cabinet. The installation site AC power receptacle must be within 2 meters (6.6 feet) of the rack.

Circuit Breaker Requirements

Use dedicated AC breaker panels for all power circuits that supply power to the infrastructure rack PDUs. Electrical work and installations must comply with applicable local, state, or national electrical codes. infrastructure rack PDUs require electrical circuits to be grounded to the Earth.

Note:

Circuit breakers are supplied by the customer. One circuit breaker is required for each power cord.

Grounding Guidelines

The cabinets for the Oracle Private Cloud Appliance are shipped with grounding-type power cords (three-wire). Always connect the cords to grounded power outlets. Because different grounding methods are used, depending on location, check the grounding type, and refer to documentation, such as IEC documents, for the correct grounding method. Ensure that the facility administrator or qualified electrical engineer verifies the grounding method for the building, and performs the grounding work.