Three-Phase Power Distribution Unit Cabling Connections X8M

Table 17-3shows the cable connections from the power distribution units (PDUs) to the rack units in a Recovery Appliance X8M full rack. The destinations and the cable lengths are the same in racks with fewer storage servers. The cables terminate at PDU-A on the left and are routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four.

Table 16-4 Three-Phase PDU Cabling for the Recovery Appliance X8M Full Racks

Rack Unit(1) PDU-A PDU-B Cable Length

U41

G4-4

G1-2

2 meters

U39

G5-1

G0-5

2 meters

U37

G5-5

G0-1

2 meters

U35

G4-1

G1-5

2 meters

U33

G5-3

G0-3

2 meters

U31

G5-4

G0-2

2 meters

U29

G4-6

G1-0

2 meters

U27

G3-4

G2-2

2 meters

U25

G3-1

G2-5

2 meters

U23

G3-0

G2-6

2 meters

U22

G1-6

G4-0

2 meters

U21

G1-4

G4-2

2 meters

U20

G1-5

G4-1

2 meters

U18

G2-6

G3-0

2 meters

U17

G0-5

G5-1

2 meters

U16

G1-1

G4-5

2 meters

U14

G2-2

G3-4

2 meters

U12

G2-5

G3-1

2 meters

U10

G2-4

G3-2

2 meters

U8

G0-2

G5-4

2 meters

U6

G1-0

G4-6

2 meters

U4

G0-0

G5-6

2 meters

U2

G0-4

G5-2

2 meters

U1

G4-2

G1-4

2 meters

Footnote 1 Un is the unit location in the rack, where n is the number.