High-Voltage 15 kVA Three Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
Note:
The following specifications are for a single PDU. Every ZDLRA Rack configuration contains two PDUs.Table 2-11 Specifications for each High-Voltage 15 kVA Three Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
| Specification | Value |
|---|---|
| Number of Inputs | 1 |
| Source Voltage | 220/380 - 240/415VAC 3Ø |
| Frequency | 50/60 Hz |
| Max Line Current | 21A |
| Phase Current | 21A |
| Nominal Power Rating | 15kVA |
| Recommended Circuit Breaker | 25A |
| Outlets | 42 x C13, 6 x C19 |
| Outlet Groups | 6 |
| Max Group Current | 20A |
| Output Voltage | 220-240V |
| Data Center Receptacle | 3ph 4W + ground 32A IEC60309 5P 6h 400V |