Low-Voltage 22 kVA Single Phase PDU for North America, South America, Japan and Taiwan
Note:
The following specifications are for a single PDU. Every ZDLRA Rack configuration contains two PDUs.Table 2-6 Specifications for each Low-Voltage 22 kVA Single Phase PDU for North America, South America, Japan and Taiwan
| Specification | Value |
|---|---|
| Number of Inputs | 3 |
| Source Voltage | 200-240V |
| Frequency | 50/60 Hz |
| Max Line Current | 36.8A |
| Phase Current | N/A |
| Nominal Power Rating | 22kVA |
| Recommended Circuit Breaker | 50A |
| Outlets | 42 x C13, 6 x C19 |
| Outlet Groups | 6 |
| Max Group Current | 20A |
| Output Voltage | 200-240V |
| Data Center Receptacle | 1ph 2W + ground 30A NEMA L6-30 |