Maintenance Access Requirements

The maintenance area must be large enough for ZDLRA Rack, and have the required access space.

The required space to remove the side panels is 675.64 mm (26.6 inches). Side panel access is not required for normal maintenance.

Front access space requirement is typically the length of the longest chassis supported in the rack, plus the distance the rails need to travel out to install and remove equipment from the front.

Rear access space requirement is the space needed for a person working behind the ZDLRA Rack.

Top access space requirement is for a person standing on a ladder to be able service components installed in the top of the rack.

Table 2-3 Maintenance Access Requirements for ZDLRA Rack (All Models)

Location Maintenance Access Requirement
Rear maintenance 914 mm (36 inches)
Front maintenance 1232 (48.5 inches)
Top maintenance 914 mm (36 inches)

Note: