Power Supply Alarms

The following table lists the voltage, power, and current alarms.

Alarm Alarm Severity Cause(s)
Power Supply X Vout Under Voltage Fault! EMERGENCY The voltage output dropped below the typical voltage by more than 30%.
Power Supply X Vout Over Voltage Fault! EMERGENCY The voltage output exceeded the typical voltage level by more than 30%.
Power Supply X Pout Over Power Warning! MINOR The power output exceeded the typical power by more than 10%.
Power Supply X Pout Over Power Fault! EMERGENCY The power output exceeded the typical power by more than 30%.
Power Supply X Iout Over Current Warning! MINOR The current output exceeds the typical current by more than 10%.
Power Supply X Iout Over Current Fault! EMERGENCY The current output exceeds the typical current by more than 30%.
Power Supply X Pin Over Power Warning! MINOR The power input exceeds the typical power input by more than 10%.
Power Supply X Iin Over Current Warning! MINOR The current input exceeds the typical current input by more than 10%.
Power Supply X Iin Over Current Fault! EMERGENCY The current input exceeds the typical current input by more than 30%.
Power Supply X Vin Under Voltage Fault! EMERGENCY The voltage input dropped below the typical voltage input by more than 30%.
Power Supply X Vin Under Voltage Warning! MINOR The voltage input dropped below the typical voltage input by more than 10%.
Power Supply X Vin Over Voltage Warning! MINOR The voltage input exceeded the typical voltage input by more than 10%.