Rack Compatibility

The rack into which you install Oracle Communications Server E6-2L must meet the requirements listed in the following table. Oracle Rack Cabinet 1242 and Sun Rack II are compatible with both servers. For information about the racks, see Preparing for Server Installation.

Item Requirement
Structure Four-post rack: (mounting at both front and back) Supported rack types: square hole (9.5 mm) and round hole (M6 or 1/4-20 threaded only).

Two-post racks are not compatible.

Rack horizontal opening and unit vertical pitch Conforms to ANSI/EIA 310-D-1992 or IEC 60297 standards.
Distance between front and back mounting planes Minimum 61 cm and maximum 91.5 cm (24 inches to 36 inches).
Clearance depth in front of front mounting plane Distance to front cabinet door is at least 2.54 cm (1 inch).
Clearance depth behind front mounting plane Distance to back cabinet door is at least 90 cm (35.43 inches) with the cable management arm, or 80 cm (31.5 inches) without the cable management arm.
Clearance width between front and back mounting planes Distance between structural supports and cable troughs is at least 45.6 cm (18 inches).
Minimum clearance for service access Clearance, front of server: 123.2 cm (48.5 inches)

Clearance, back of server: 91.4 cm (36 inches)

The following table contains Oracle Rack Cabinet 1242 rack specifications:

Requirement Specification
Usable rack units 42
Height 199.9 cm (78.74 inches)
Width (with side panels) 60 cm (23.62 inches)
Maximum dynamic load 1005 kg (2215 lbs)

Note:

Depth is measured from front door handle to back door handle.