Rackmount Checklist
Complete the following checklist before you install the server into a rack.
| Rackmount Considerations | Yes | No | N/A | Comment |
|---|---|---|---|---|
|
Is the distance between the front and back mounting planes between a minimum of 610 mm and a maximum 915 mm (24 inches to 36 inches)? |
||||
|
Is the clearance depth in the front of the front mounting plane (distance to the front cabinet door) at least 25.4 mm (1 inch)? |
||||
|
Is the minimum clearance for service:
|
||||
|
Is the rack a four-post rack (mounting at both front and back)? Two-post racks are not compatible. |
||||
|
Do the horizontal opening and unit vertical pitch of the rack conform to ANSI/EIA 310-D-1992 or IEC 60297 standards? |
||||
|
Does the rack have RETMA rail support? |
||||
|
Does the rack support Oracle cable management arms (CMAs)? |
||||
|
Does the rack support installation of Oracle vented and solid filler panels? |
||||
|
Is there sufficient space for cable harnesses and the power distribution units (PDUs) in the rack, if required? |
||||
|
Can a label with the server serial number be printed and attached to the target rack? |
||||
|
Did you label the network cables that will connect to the server? |
||||
|
Does the rack support installation of standard Oracle PDUs? If not, then complete this checklist. |
||||
|
Can the customer provide an equivalent pair of PDUs? |
||||
|
Can the customer provide two PDUs with capacity of 110kVA per PDU? |
||||
|
Can the customer provide a single PDU and its circuits to support the power requirements in case a PDU fails? |
||||
|
Can the customer ensure that power loads are evenly distributed across all circuits of a single PDU? |