4.58 chg-frm-pwr

Use this command to change the power threshold value in the Frame Power Threshold table for a specified frame.

The entries in the Frame Power Threshold table contain a Frame ID and the corresponding power threshold value.

Use the following commands to display the threshold and calculated maximum power consumption for the frames in the system.

  • The rtrv-frm-pwr command displays the current provisioned frame power threshold for each provisioned frame.
  • The rtrv-stp:display=power command displays the provisioned frame power threshold for each provisioned frame, and displays the maximum calculated power consumption for each frame, based on card population.
  • The rtrv-stp:display=power:frm=xxxx command displays the provisioned frame power threshold for the specified frame, the maximum calculated power consumption for the frame based on card population, and the maximum power consumption for each card in the frame and for a fan assembly for each shelf.

Note:

The frame-level power threshold value needs to be determined from the capacity in Amps of the fuse alarm panel (FAP) for the frame. Contact your site engineer to determine the FAP capacity.

Parameters

frm (mandatory)
Frame ID
Range:
cf00
Control frame
ef00
First extension frame
ef01
Second extension frame
ef02
Third extension frame
ef03
Fourth extension frame
ef04
Fifth extension frame
thrshld (mandatory)
Threshold. This parameter specifies the frame-level power threshold, in Amps. This value is compared with the current calculated maximum power consumption for the frame (use the rtrv-stp:display=power:frm= command to obtain the maximum power consumption value), and the appropriate alarms are raised if that power comsumption exceeds the threshold limit.

The value of the thrshld  parameter needs to be determined from the capacity of the fuse alarm panel (FAP) for the frame. Contact your site engineer to determine the frame FAP capacity.

Range:
30 - 65
Default:
30

Example

Change the frame power threshold value for the first extension frame.

chg-frm-pwr:frm=ef00:thrshld=58

Dependencies

The following values are valid for the frm parameter: cf00, ef00, ef01, ef02, ef03, ef04.

The valid range of values for the thrshld parameter is  30-65 Amps.

A power threshold value must already be provisioned for the specified frame.

The Frame Power Threshold table must be accessible.

Notes

The maximum calculated power for a frame is based on the cards that are populated in the system, and includes a fan tray assembly for every shelf (the system cannot detect the presence or absence of a fan tray, and assumes presence for the calculation). These values are typically much higher than the actual power being drawn; the values cannot be used as a gauge of the actual power consumption of the EAGLE.

Output

chg-frm-pwr:frm=ef00:thrshld=58

    tekelecstp 06-06-01 15:18:41 EST  EAGLE 35.0.0    
    FRAME POWER THRESHOLD table is (4 of 10) 40% full    
    CHG-FRM-PWR: MASP A – COMPLTD 
;