Error Code | Error Description | Notes |
|---|---|---|
LP-001 | Too many fields | Expect 8 fields, 7 commas |
LP-002 | Too few fields | Expect 8 fields, 7 commas |
LP-003 | Invalid day type | The day type specified is not valid |
LP-004 | Invalid hour value | Should be integer type |
LP-005 | Invalid hour value | Should be 0 through 23 |
LP-006 | Invalid KW value | Should be floating type |
LP-007 | Invalid KVAR value | Should be floating type |
LP-008 | Duplicate Record | Duplicated hourly record found |
LP-009 | Invalid KVA rating or utilization factor | These values should be present in table pf_loads |
LP-010 | Transformer loading exceeds the rating based on specified threshold. | The threshold can be configured in the SRS rules, currently set to 200% |
LP-011 | Invalid Weather Zone | The weather zone associated to the load could not be located in the configuration. Please validate table PF_WEATHER_ZONE to ensure this zone is added properly. |
LP-012 | Invalid temperature value should be floating type. | Should be floating type. |
LP-013 | Load is mapped to a zone but the zone does not appear to be a valid weather zone. | A zone was configured for the load but this zone does not appear to be configured as a weather zone. It is instead setup for something else like an individual DER forecast or Demand Response Group. |
LP-014 | A Null Weather Zone value was provided. | The load was configured with a null weather zone value. Validate the zone associated to the load is present in table PF_WEATHER_ZONE and forecast date is present in table PF_WEATHER_ZONE_FORECAST. |
LP-015 | A Null kW value was provided | The CSV file contained a record that had a null value for kW. This data will not be processed and the sample counts will not be increased. This data will be thrown away and not loaded. |
LP-016 | Negative Load after DER adustment | The net meter adjustment was attempting to add back load from any DER contributions. The resultant kW value is still showing negative, which is not possible. |
LP--017 | Overloaded Transformer | When comparing the kVA rating of the device with the metering information for transformer is shown to be significantly overloaded. This overloaded threshold is configured with SRS rule PA_OverloadThreshold. |
LP-018 | Negative kVAr value | The kVAr contribution from the load was found to be negative. |
LP-019 | Invalid Date Format | The date format provided in the CSV file was found to be invalid. |
NM-001 | Dist Gen data could not be located | Dist Gen information could not be located for a dist gen associated with a net metered profile. |
NM-002 | Dist Gen has an invalid power source | Power source is invalid for a dist gen associated with a net metered profile. |
NM-003 | Dist Gen Invalid Weather Zone | Weather zone is invalid for a dist gen associated with a net metered profile. |
NM-004 | Dist Gen Profile is invalid | The profile associated to the dist gen could not be located. This is needed to perform net metered profile processing. |
NM-005 | Dist Gen output exceeds the connected transformers rating based on a specified threshold. | This rule uses the same SRS rule as used for LP-010 and can be configured in the SRS rules. The NM-005 error is looking purely at Dist Gen output in comparison to the rating of the transformer - excluding any loading information. |
NM-006 | Dist Gen is configured with a default dist gen factor | A specific profile factor could not be determined for the designated Dist Gen unit during the net meter processing. As a result, a default factor was applied instead. For example, if weather data for December 9, 2025, at 9:00 AM was unavailable to estimate the performance of a solar unit, a default value from the distGenDefault SRS Rule configuration would be used. |
NM-007 | Dist Gen output is not large enough to compensate for negative load | During the net metered profile analysis, a negative value was identified. Even after accounting for the output of the associated Distributed Energy Resources (DERs), the resulting value remained negative. For example, if a net metered load shows -4kW and a solar installation behind the same transformer is generating 3kW at that time, the resulting load would be -1kW. This typically raises concerns, as it may indicate issues such as incorrect DER sizing, faulty load metering, or errors in load mapping. |
NM-008 | Negative Metered load with no DER | A negative net metered load was found, but no DERs were found to be present below the load point. This would generally indicate a metering issue or DER association issue. |
MA-001 | Invalid meter to xfmr mapping | While forming the meter to transformer mapping, an invalid relationship was found. |
MA-002 | Too few fields | Based on the column configuration, the meter csv file had too few fields. |
MA-003 | Too many fields | Based on the column configuration, the meter csv file had too many fields. |
MA-004 | Could not find a valid mapping to an associated transformer | The meter to transformer mapping was found to be present but the transformer is invalid or does not exist within the model. |
MA-005 | Invalid hour value | Should be between 0 and 23. |
MA-006 | Invalid hour value | Should be integer type. |
MA-007 | Invalid day type | The day type specified is not valid (for example, 0 = Weekday, 1 = Weekend, and so on). |
MA-008 | Invalid kW value | Should be floating type. |
MA-009 | Invalid kVAr value | Should be floating type. |
MA-010 | Invalid date format |