SRS Rules
The following SRS Rules must be configured when using the FLEX SCADA module:
• RT_IGNORE_TIMESTAMP
• Defines whether changes with older timestamps should be discarded. If set to Yes then the changes will not be discarded.
This rule must be set to Yes
• RT_FLEX_SCADA
• This rule must be set to Yes for RTAdapter to correctly process analog values from Flex SCADA.
• scadaFepIds
• This rule defines the list of supported SCADA ids for Flex SCADA. Multiple rows can be configured and the rule_value_1 field must be set to the name of a SCADA id (for example, RTAdapter, IccpAdapter).
• If the SCADA id is not configured in this rule then Flex SCADA will ignore control requests for any device associated with that SCADA id.
• scadaFepInterface
• Defines the SCADA interface to use. Currently only supports one interface.
This must be set to LecInterface
• scadaFepDisconnectPeriod
• The time in seconds after which a FEP with no active connection to an LEC instance will be marked as failed.
• scadaRtuDisconnectPeriod
• The time in seconds after which an IED with no active connection to the device in the field will be marked as failed.