Distribution Management System (DMS)
Distribution State Estimation: Phase 2
This feature enhances Distribution State Estimation by detecting inaccurate or bad measurements, discarding them from the calculation, and preprocessing the remaining valid measurements to produce more accurate power-flow results.
Users are able to identify inaccurate measurements directly in the Viewer, where they would be highlighted for investigation and corrective action.
Voltage Profile
This feature enables users to view the voltage profile for any circuit or selected portion of the network model. Users can analyze voltage by individual phase or as the average across all three phases, along with Supervisory Control and Data Acquisition (SCADA) voltage measurements and the ability to jump from any point in the profile to the linked device on the map.
Configurable Backfeed Threshold Percentage for Feeder Load Management (FLM)
This feature helps operators focus on reverse-power-flow conditions that are significant enough to require attention. This feature improves Power Flow and FLM handling of backfeed violations. Operators can:
• Configure the backfeed threshold
• Generate warnings and violations only when reverse power flow exceeds the configured threshold.
• Focus operational attention on significant backfeed conditions that could affect transformers and other critical assets.
Planned Switching into Forecast
This feature enables FLM forecasts, studies, and DERMS temporal analyses to account for applicable planned switching operations when evaluating future network conditions. Operators are able to see which planned operations influenced an FLM result and launch related studies using the same switching context. The enhancements improve the consistency, performance, and operational usefulness of analysis as network topology changes over time.
Emergency Voltage Reduction (EVR)
This feature introduces an Emergency Voltage Reduction application. Operators can:
• Reduce voltage across a selected zone or region using SCADA-controlled load tap changers (LTCs) and voltage regulators, without relying on Power Flow calculations or the network model.
• Enter the required voltage reduction percentage and include or exclude eligible devices.
• Apply optional bandwidth and low-limit overrides, with warnings when a target setpoint falls outside an acceptable voltage range.
• Generate a switching sheet, execute EVR immediately, or schedule it within a defined time window.
• Save EVR cases and restore devices either to their nominal configuration or to the pre-EVR values captured before execution.
Rotational Load Shedding and Restoration
This feature modernizes the Load Shed and Restoration application. Operators can:
• Use fixed or rotational load-shedding workflows.
• Choose Emergency mode, which uses SCADA data and SCADA-enabled load blocks, or Advanced mode, which uses Power Flow data and can include both SCADA and manually configured blocks.
• Import, create, edit, and delete load groups and devices within a group.
• Define target load-reduction criteria and search for eligible blocks by Dynamic Priority, Initial Priority, or megawatts (MW).
• Schedule fixed and rotational plans using configured times, days, effective dates, and rotational intervals.
• Save, reopen, modify, and apply fixed or rotational load-shedding saved cases, including their criteria, selected groups and feeders, schedules, and plan details.