Understanding Capacitor Controls
A capacitor can have up to three controls that determine when it switches ON or OFF:
• Emergency Control (control_e): The control with the highest priority.
• Normal Control 1 (control_1): The first normal control.
• Normal Control 2 (control_2): The second normal control.
Control Types
The following capacitor control types are supported:
Control Type
Description
0
Fixed
1
Voltage Regulated
2
Time Switched
3
Temperature Switched
4
Current Switched
5
VAR Switched
6
Power Factor Switched
7
Fixed Manual (Reserved for OPF)
8
Season Switched
Control Evaluation
If emergency limits are violated, the capacitor immediately switches ON or OFF according to the emergency thresholds. When Voltage Regulated control is used as the emergency control, the capacitor turns ON below the ON threshold and turns OFF above the OFF threshold.
When the measured value lies between the emergency thresholds, the capacitor state is determined by the two normal controls, the configured AND/OR logic, and Local Voltage Control (LVC). Normal controls are evaluated only when LVC is enabled.
• AND logic: The capacitor turns ON when both normal controls are ON and turns OFF when both are OFF. If the controls have different ON/OFF results, the capacitor remains in its current state (indeterminate).
• OR logic: The capacitor turns ON when Normal Control 1 is ON and turns OFF when both normal controls are OFF.
Understanding Time Based Control
Time-based control (Type 2) switches a capacitor ON and OFF according to a predefined day and time schedule. The schedule can follow predictable daily or weekly load patterns.
The time schedule uses the following parameters:
• control_type_1: A value of 2 enables Time Switched control.
• ON_DAY: The day on which the capacitor turns ON. Values 0 to 6 represent Sunday through Saturday; 7 represents all days.
• OFF_DAY: The day on which the capacitor turns OFF. Values 0 to 6 represent Sunday through Saturday.
• control_1_on: The ON time in HHMM format, where HH is the hour from 00 to 23 and MM is the minute from 00 to 59.
• control_1_off: The OFF time in HHMM format.
• TimeVarOffDays: The days on which the capacitor remains OFF. This setting applies to both continuous weekly and specific day-based schedules.
Note: If TimeVarOffDays is 127, the capacitor will never turn ON when time-based control is configured.
Continuous Weekly Logic
When ON_DAY and OFF_DAY are not configured, the capacitor evaluates the ON and OFF times every day of the week. The weekday portion of the schedule is treated as any day. TimeVarOffDays remains the only day-based filter.
Specific Day Based Logic
When both ON_DAY and OFF_DAY are configured, the capacitor turns ON at the specified ON_DAY and control_1_on time and turns OFF at the specified OFF_DAY and control_1_off time. TimeVarOffDays continues to apply.
Time Based Control Examples
The following examples show a daily schedule and a schedule with specific ON and OFF days:
Parameter
Daily schedule
Specific day schedule
control_type_1
2
2
TimeVarOffDays
0
0
ON_DAY
Not set
2
OFF_DAY
Not set
3
control_1_on
0200
0200
control_1_off
1500
1500
 
• Daily schedule: The capacitor operates every day from 02:00 to 15:00. TimeVarOffDays can be used to block specific days.
• Specific day schedule: The capacitor operates from Tuesday at 02:00 until Wednesday at 15:00.
Understanding Season Based Control
Season-based control (Type 8) allows a capacitor to operate within a defined date range during the year. This control supports seasonal load variations, such as increased demand during summer or winter.
The seasonal schedule uses the following parameters:
• control_type_2: A value of 8 enables Season Switched control.
• control_2_on: The start date in MMDD format, where MM is the month and DD is the day.
• control_2_off: The end date in MMDD format.
• TimeVarOffDays: The days on which the capacitor remains OFF within the season.
The capacitor switches ON at the configured start date and OFF at the configured end date.
Season Based Control Example
Parameter
Value
control_type_2
8
control_2_on
0301
control_2_off
0401
 
With this configuration, the capacitor operates between March 1 and April 1.