Unmeasured Devices and Network-Wide Estimates
DSE produces estimates for the entire network model, including devices without direct measurements. This is achieved by enforcing Kirchhoff’s laws using penalty terms:
• Node balance (KCL) and branch consistency (KVL) are enforced via pseudo measurements and zero-injection constraints that enter the objective with configurable weights.
• Pseudo measurements use DSE_PSEUDO_WEIGHT’s relative and absolute error settings to form their base sigma(ref) and weight, providing soft constraints where telemetry is sparse.
• Zero-injection nodes (expected injection is zero) are enforced using DSE_ZEROINJ_WEIGHT to set just the absolute error, which controls the strength of the zero-injection penalty. This setting can greatly impact stability/convergence.
• High-admittance pass-through devices: Branches whose admittance is greater than or equal to DSE_HIGH_ADMITTANCE_TOL are treated as low-impedance pass-through devices. DSE reconstructs their branch currents from the currents entering the connected nodes rather than multiplying voltage by the large branch admittance. This improves numerical stability for devices such as switches and busbars. DSE also adds a voltage-equivalence residual that constrains the voltages on the two sides of each pass-through device to be equal. Rule value 2 of DSE_HIGH_ADMITTANCE_TOL configures the absolute error for this residual.
These penalties ensure observability and stabilize the solution, allowing states (voltages, angles, flows) at unmeasured points to be inferred consistently with the PF model and available SCADA data.
 
Viewing State Estimation and Voltage Profiles in the Device Details Balloon
In Flex Operations, the Device Details balloon Power Flow Results tab includes an Open Voltage Profile button () that traces and displays a voltage profile using available power flow and SCADA values and can be used even when DSE is not licensed or the selected source has no DSE results.
When DSE is licensed and the selected source has DSE results, the Device Details balloon also includes a DSE tab. Select Summary from the View drop‑down list to compare power flow, DSE, and measurement values by phase in a compact table. Select Detailed from the View drop‑down list to view each result type in a separate row, including whether the measurement was used or marked bad, its post-bad-data handled state and confidence level, and the percentage differences between power flow, DSE, and measurement values.
Use the Open State Estimation Results button () to open the State Estimation Results tab filtered to the selected device. Use the Open State Estimation Sources button () to open the Sources tab for the device's source. The Open Voltage Profile button () is also available from the DSE tab when DSE results exist. The bottom of the DSE tab displays the source solution status and solution time.
The Java Web Workspace Device Details balloon continues to provide its DSE voltage display option. The dse_what diagnostic command provides a text representation of DSE source and result information.
Viewing a Voltage Profile
The Flex Operations Voltage Profile tool traces from a selected device and displays available power flow, DSE, and SCADA voltage magnitudes along the upstream and downstream network paths. To open the tool, click the Open Voltage Profile button () on the Device Details balloon's Power Flow tab. The tool can be run with power flow results even when DSE is not licensed or no DSE results are available. When DSE results exist, you can also open it from the balloon's DSE tab or from a selected row in the State Estimation Results tab.
Use Direction to display Both, Upstream, or Downstream trace results. Use Phase Filter to include Branches with any available phases or only the three-phase Trunk. Select PF, DSE, and SCADA to control the displayed data sources. Use Voltage Base to display values in P.U or on a 120V base.
The Graph tab combines the selected phases and data sources. The Multi-Graph tab displays separate Phase A, Phase B, Phase C, and Phase Avg graphs. The Table tab lists direction, signed distance from the trace device, device handle, and the available phase and average values for each data source.
Use Refresh Profile to rerun the trace, Jump To Trace Device to position the map at the original trace device, Trace From Selection to retrace from the selected table row, and View On Map to position the map at the selected result.