Environmental Requirements
This section describes the environmental specifications for the server.
Caution:
Set conditions to the optimal temperature and humidity ranges to minimize the chance of downtime due to component failure. Operating the servers for extended periods at or near the operating range limits, or installing them in an environment where they remain at or near nonoperating range limits could significantly increase hardware component failure.
Specification | Operating | Nonoperating |
---|---|---|
Ambient temperature (does not apply to removable media) |
Maximum ambient operating temperature is derated by 1 degree C per every 300 meters elevation beyond 900 meters, up to a maximum altitude of 3,000 meters elevation. |
–40˚F to 154˚F (–40˚C to 68˚C) |
Relative humidity |
|
Up to 93% noncondensing 95˚F (35˚C) maximum wet bulb |
Altitude |
Maximum 9,840 feet (3,000 meters) at 95˚F (35˚C) Note: In China markets, regulations might limit installations to a maximum altitude of 6,562 feet (2,000 meters). |
Maximum 39,370 feet (12,000 meters) |
Acoustic Noise |
|
Not applicable |
Vibration |
IEC 60068-2-6 Test FC |
IEC 60068-2-6 Test FC |
Shock |
3 Gs, 11 ms half-sine IEC 60068-2-27 Test Ea |
Roll-off: 1.25-inch roll-off free fall, front to back rolling directions Threshold: 13 mm threshold height at 0.65 m/s impact velocity ETE-1010-02 Rev A |