Always replace the
failed power supply with the same type model of power supply.
Remove the replacement power supply from its packaging, and place it on an
antistatic mat.
Align the replacement power supply with the empty power supply slot.
Slide the power supply into the slot until it is fully seated.
You will hear an audible click when the power supply fully seats.
Reconnect the power cord to the power supply.
Verify that the amber Fault-Service Required LED on the replaced power supply
and the Fault-Service Required LEDs are not lit on the front and back
panels.
Note:
After you have replaced Power
Supply 0, you might need to reset the Oracle ILOM service processor (SP) to
propagate the key identity properties (KIP) data to the new power supply. For
instructions on resetting the SP, refer to the Oracle ILOM
Administrator's Guide for Configuration and Maintenance Firmware Release
5.1.x at Servers Documentation - Systems Management.
Power Supply 1 does not contain KIP data, and therefore does not require an SP
reset after replacement.
If you disconnected the two CMA left-side connectors, reconnect the
connectors.
Refer to Install the Cable Management Arm
(Optional) in Oracle Servers X9-2 and X9-2L
Installation Guide at Oracle Server X9-2L Documentation