For your protection, observe the following safety precautions when setting up your equipment:

  • Follow all cautions and instructions marked on the equipment.

  • Ensure that the voltage and frequency of your power source match the voltage and frequency inscribed on the equipment’s electrical rating label.

  • Never push objects of any kind through openings in the equipment. Dangerous voltages may be present. Conductive foreign objects could produce a short circuit that could cause fire, electric shock, or damage to your equipment.

  • This product is intended for restricted access whereby access is controlled through the use of a means of security (for example, key, lock, tool, badge access) and personnel authorized for access have been instructed on the reasons for the restrictions and any precautions that need to be taken.

  • Do not directly connect this product to outdoor metallic communications cables. Always connect the product to outdoor metallic communications cables using a protection device that is designed for direct connection to outdoor metallic communications cables (such as a switch or router), or use optical non-metallic communications cables upon leaving the building.

  • Do not directly connect this product to outdoor power cables.

    • For AC Power, connect the product only to an indoor power distribution system that uses current-limiting circuit breakers for AC power.

    • For DC Power, connect the product only to earthed power systems that are completely contained within one building.

  • Required or recommended use of hearing protection devices in the workplace vary among global regions. Check your local regulations for noise level exposure limits in the workplace that apply to your installation of Oracle equipment and appropriate use of personal protection equipment.

Symbols

The following symbols may appear in this book or on your Oracle product:

Caution

Caution

Caution: There is a risk of personal injury and equipment damage. Follow the instructions provided in the Oracle product documentation or displayed on the product.

Caution

Caution: Hot surface. Avoid contact. Surfaces are hot and may cause personal injury if touched.

Caution

Caution: Hazardous voltages are present. To reduce the risk of electric shock and danger to personal health, follow the instructions.

Depending on the type of power switch your device has, one of the following symbols may be used:

Caution

On: Applies AC power to the system.

Caution

Off: Removes AC power from the system.

Caution

Standby: The On/Standby switch is in the standby position.

Modifications to Equipment

Do not make mechanical or electrical modifications to the equipment. Oracle is not responsible for regulatory compliance of a modified Oracle product.

Placement of an Oracle Product

Restricted Access Area – Equipment is intended for installation in a Restricted Access Area.

Caution:

Do not block or cover the openings of your Oracle product. Never place an Oracle product near a radiator or heat register. Failure to follow these guidelines can cause overheating and affect the reliability of your Oracle product.

SELV/ES1 Compliance

Safety status of I/O connections comply to SELV/ES1 requirements.

Power Cord Connection

Caution:

High touch current. Earth connection essential before connecting supply. These symbols indicating high touch current may be displayed on your Oracle system.

Power Cord Connection symbol

Caution:

Oracle products are designed to work with power systems having a grounded neutral (grounded return for DC-powered products). To reduce the risk of electric shock, do not plug Oracle products into any other type of power system. Contact your facilities manager or a qualified electrician if you are not sure what type of power is supplied to your building.

Caution:

Not all power cords have the same current ratings. Do not use the power cord provided with your equipment for any other products or use. Household extension cords do not have overload protection and are not meant for use with computer systems. Do not use household extension cords with your Oracle product.

The following caution applies only to devices with a Standby power switch:

Caution:

The power switch of this product functions as a standby type device only. The power cord serves as the primary disconnect device for the system. Be sure to plug the power cord into a grounded power outlet that is nearby the system and is readily accessible. Do not connect the power cord when the power supply has been removed from the system chassis.

The following caution applies only to devices with multiple power cords:

Caution:

For products with multiple power cords, all power cords must be disconnected to completely remove power from the system.

Graphic showing the multiple power cords cautionary icon

and/or


Graphic showing the multiple power cords cautionary icon

Battery Warning

Caution:

There is danger of explosion if batteries are mishandled or incorrectly replaced. On systems with replaceable batteries, replace only with the same manufacturer and type or equivalent type recommended by the manufacturer per the instructions provided in the product service manual. Do not disassemble batteries or attempt to recharge them outside the system. Do not dispose of batteries in fire. Dispose of batteries properly in accordance with the manufacturer’s instructions and local regulations. Note that on Oracle CPU boards, there is a lithium battery molded into the real-time clock. These batteries are not customer replaceable parts.

Caution:

For product installed in California, USA: This product may contain a time-of-day battery which may contain perchlorate where special handling may apply. See http://www.dtsc.ca.gov/hazardouswaste/perchlorate .

Energy Storage Module Caution

Caution:

There is a danger of shock or equipment damage if energy storage modules are mishandled or incorrectly replaced. When replacing the energy storage modules, use only replacement modules that have been provided by Oracle, following the instructions provided in the product service manual. Do not disassemble modules or attempt to recharge them outside of the system. Do not dispose of the modules; instead, return them to Oracle in accordance with Oracle procedures for the product.

System Unit Cover

You must remove the cover of your Oracle computer system unit to add cards, memory, or internal storage devices. Be sure to replace the cover before powering on your computer system.

Caution:

Do not operate Oracle products without the cover in place. Failure to take this precaution may result in personal injury and system damage.

Rack System Instructions

The following or similar rack-mount instructions are included with the installation instructions:

  • Elevated Operating Ambient – If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer.

  • Reduced Air Flow – Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised.

  • Mechanical Loading – Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading.

  • Circuit Overloading – Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.

  • Reliable Earthing – Reliable earthing of rack-mounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (for example, use of power strips).

  • Stability Hazard – The rack may tip over causing serious personal injury. Before extending the rack to the installation position, read the installation instructions. Do not put any load on the slide-rail mounted equipment in the installation position. Do not leave the slide-rail mounted equipment in the installation position.

Caution:

Slide/rail mounted equipment must not be used as a shelf or workspace.

Graphic showing the rack mount caution symbol.

Rack System Warnings

The following warnings apply to Racks and Rack Mounted systems.

Caution:

For safety, equipment should always be loaded from the bottom up. That is, install the equipment that will be mounted in the lowest part of the rack first, then the next higher systems, etc.

Caution:

To prevent the rack from tipping during equipment installation, the anti-tilt bar on the rack must be deployed.

Caution:

To prevent extreme operating temperature within the rack insure that the maximum temperature does not exceed the product's ambient rated temperatures.

Caution:

To prevent extreme operating temperatures due to reduced airflow consideration should be made to the amount of air flow that is required for a safe operation of the equipment.

Caution:

Take adequate precautions when moving a rack or library that contains rack-installed equipment. The weight of some rack equipment may have altered the rack or library center of gravity and could cause an overbalance/tip condition during a move.

Caution:

For tape libraries, ensure that the equipment to be installed in the rack has UL Listing, CSA or C-UL Certification, and is CE marked.

Laser Compliance Notice

Your Oracle product may contain Class 1M Laser Transceivers or a Class 1 Laser, as defined by IEC 60825-1.

Caution:

Use of controls or adjustments or performance of procedures other than those specified in Oracle product documentation may result in hazardous radiation exposure. Do not view laser beam directly with optical instruments.

CD and DVD Devices

The following caution applies to CD, DVD, and other optical devices.

Caution:

Use of controls, adjustments, or the performance of procedures other than those specified herein may result in hazardous radiation exposure.

Mechanical Hazard Markings

Caution:

To reduce the risk of contact with voltages, energy or mechanical parts at hazardous levels, do not place hands behind or through openings displaying either of the symbols below.

Do not place hands behind or through openings symbols

Caution:

Hazardous moving parts. Keep away from moving fan blades.
Fan hazard icon.