Calculate Total Power Consumption

For environmental or economical reasons, you might want to determine the total power consumption (Watts), CO2 emission values, and British Thermal Units (Btu/hr) for the library and drives.

The following table lists the idle and maximum watts consumed by various library components.

Components Quantity Idle Watts Max Watts

Base Library (required)

Includes: card cage, 1 robot, 1 CAP, operator panel

1

301

518

Redundant Robotics (optional)

1

48

154

Additional CAPs (optional)

Each

10

14

Drive Module/Cartridge Module

Each

3

5

Access Module

Each

9

29

T10000A/B/C

Each

61

93

T10000D

Each

64

127

LTO

Each

30

46

Calculate Total Watts, CO2 Emissions, and Btu/hr

To calculate the total power consumption in Watts for the library, add up all the applicable wattage values for the library configuration.

To calculate kilograms of CO2 emissions per day, multiply watts by the CO2 emissions constant. Use the constant that is applicable for your country (0.02497 for US).

To convert electrical values to Btu/hr, multiply the number of watts by 3.412 (1 W = 3.412 Btu/hr).

Table 1-1 Power Consumption Example 1

Component Quantity Watts

SL4000 Base

1

518

LTO8 Tape Drives

16

736

Library Total

--

1,254

  • Emissions: 1,254W x 0.02497 = 31.3 Kg of CO2
  • Power consumption: 1,254W x 3.412 = 4,279 Btu/hr

Table 1-2 Power Consumption Example 2

Component Quantity Watts

SL4000 Base

1

518

T10000D Tape Drives

8

1,016

Drive Module

1

5

T10000C Tape Drives

8

744

Cartridge Module

1

5

CAPs (3 at 10 Watts each)

3

30

Library Total

--

2,318

  • Emissions: 2,318W x 0.02497 = 57.9 Kg of CO2
  • Power consumption: 2,318W x 3.412 = 7,909 Btu/hr