C H A P T E R  5

System Specifications

This chapter includes shipping, physical, configuration, electrical, environmental, rackmounting, and cabinet specifications for the following Sun systems:


Shipping Crate Specifications

Dimensions and weights are estimates based on fully configured systems, and are dependent on specific system configurations.

 

TABLE 5-1 Shipping Crate Specifications for Sun Systems

250

280R

V480

V880

V440

V890

Height

35.75 in

90.80 cm

17.25 in

43.80 cm

23.75 in

60.90 cm

43.69 in

110.97 cm

21.13 in

53.65 cm

43.69 in

110.97 cm

Width

18 in

45.72 cm

23.63 in

60.02 cm

24 in

60.96 cm

25 in

63.50 cm

24 in

60.96 cm

25 in

63.50 cm

Depth

34 in

86.36 cm

37 in

93.98 cm

31.50 in

80.01 cm

37.50 in

95.25 cm

32.25 in

81.91cm

37.50 in

95.25 cm

Weight

150 lb

68.04 kg

100 lb

45.37kg

150 lb

68.04 kg

320 lb

145 kg

120 lb

54.45 kg

320 lb

145 kg

On Pallet

Yes

No

Yes

Yes

Yes

Yes



Physical Specifications

 

TABLE 5-2 Physical Specifications for Sun Systems

250

280R

V480

V880

V440

V890

Height

18.1 in

46.0 cm

6.95 in

17.65 cm

8.75 in

22.23 cm

28.1 in

71.4 cm

6.85 in

17.40 cm

28.1 in

71.4 cm

Width

10.3 in

26.2 cm

17.25 in

43.81 cm

17.5 in

44.6 cm

18.9 in (tower)

48.0 cm (tower)

17.25 in (rack)

43.81 cm (rack)

17.48 in

44.40 cm

18.9 in (tower)

48.0 cm (tower)

17.25 in (rack)

43.81 cm (rack)

Depth[1]

28.8 in

73.2 cm

29.12 in

73.80cm

24 in

61 cm

32.9 in

83.6 cm

25 in

63.5 cm

32.9 in

83.6 cm

Weight[2]

118 lb

53 kg

73 lb

33 kg

97 lb

44 kg

288 lb

131 kg

82 lb

37 kg

288 lb

131 kg

Power Cord Length

8.2 ft

2.5 m

6.56 ft

1.99 m

8.2 ft

2.5 m

8.2 ft[3]

2.5 m

8.2 ft

2.5 m

8.2 ft[4]

2.5 m



Base System Configurations

These are examples of possible base system configurations and do not represent all configurations available. There are many other components that are included within the systems that qualify them as minimum, typical, and maximum configurations. For complete system configuration information, see your Sun account manager or Sun authorized sales representative.

 

TABLE 5-3 Base Configurations for Sun Systems

Minimum

Typical

Maximum

250

1 400-MHz CPU
512-Mbyte memory
1 36-Gbyte drive
1 DVD drive
1 PCI card

2 400-MHz CPUs
1-Gbyte memory
2 36-Gbyte drives
1 DVD drive
2 PCI cards

2 400-MHZ CPUs
2-Gbyte memory
6 36-Gbyte drives
1 DVD drive
4 PCI cards

280R

1 1.2-GHz CPU
1-Gbyte memory
1 73-Gbyte drive
1 DVD drive
1 PCI card

2 1.2-GHz CPUs
2-Gbyte memory
2 73-Gbyte drives
1 DVD
2 PCI cards

2 1.2-GHz CPUs
8-Gbyte memory
2 73-Gbyte drives
1 DVD
4 PCI cards

V480

2 1.05-GHz CPUs
4-Gbyte memory
2 36-Gbyte drives
1 DVD drive
1 PCI card

4 1.05-GHz CPUs
8-Gbyte memory
2 36-Gbyte drives
1 DVD drive
3 PCI cards

4 1.05-GHz CPUs
16-Gbyte memory
2 36-Gbyte drives
1 DVD drive
6 PCI cards

V880

2 1.05-GHz CPUs
4-Gbyte memory
6 73-Gbyte drives
1 DVD drive
1 PCI card

4 1.05-GHz CPUs
8-Gbyte memory
6 73-Gbyte drives
1 DVD drive
5 PCI cards

8 1.05-GHz CPUs
32-Gbyte memory
12 73-Gbyte drives
1 DVD drive
9 PCI cards

V440

2 1.062-GHz CPUs
4-Gbyte memory
4 36-Gbyte drives
1 DVD drive
1 PCI card

4 1.062-GHz CPUs
8-Gbyte memory
4 36-Gbyte drives
1 DVD drive
3 PCI cards

4 1.28-GHz CPUs
16-Gbyte memory
4 36-Gbyte drives
1 DVD drive
6 PCI cards

V890

4 1.2-GHz CPUs
16-Gbyte memory
6 73-Gbyte drives
1 DVD drive
1 PCI card

4 1.2-GHz CPUs
16-Gbyte memory
6 73-Gbyte drives
1 DVD drive
1 PCI card

8 1.2-GHz CPUs
32-Gbyte memory
6 73-Gbyte drives
1 DVD drive
3 PCI cards



Electrical Specifications

 

TABLE 5-4 Electrical Specifications for Sun Systems

250

280R

V480

V880

V440

V890

Nominal Frequencies

50 or 60 Hz

50 or 60 Hz  

50 or 60 Hz

50 or 60 Hz

50 or 60 Hz

50 or 60 Hz

Nominal Voltage Range

100 to 240 VAC
auto ranging

100 to 240
VAC
auto ranging

100 to 240
VAC
auto ranging

100 to 240
VAC
auto ranging

100 to 240
VAC
auto ranging

200 to 240
VAC
auto ranging

AC Operating Range

90 to 264
Vrms
47 to 63 Hz

90 to 264
Vrms
47 to 63 Hz

90 to 264
Vrms
47 to 63 Hz

90 to 264
Vrms
47 to 63 Hz

90 to 264
Vrms
47 to 63 Hz

180 to 264
Vrms
47 to 63 Hz

Max Current
AC RMS[5]

3.1A @
120 VAC

 

1.6A @
240 VAC

7.5A @
120 VAC

 

3.7A @
240 VAC

10.0A @ 120 VAC

 

5.0A @
240 VAC

12.0A @ 120 VAC

 

6.0A @
240 VAC

7.7A @ 120 VAC

 

3.65A @ 240 VAC

8.0 A @ 200 VAC

 

6.7 A @ 240 VAC

AC Power Consumption[6]

Min

Typ

Max

Nameplate

 

 

133W

224W

358W

600W

 

 

305W

418W

750W

890W

 

 

617W

1023W

1100W

1440W

 

 

1050W

1440W

2115W

2880W

 

 

360W

570W

650W

925W

 

 

1183W

1183W

2108W

3200W

Heat Dissipation and Cooling[7]

Min

Typ

Max

Nameplate

 

 

454 Btu/hr

765 Btu/hr

1222 Btu/hr

2048 Btu/hr

 

 

1041Btu/hr

1427 Btu/hr

2560 Btu/hr

3038 Btu/hr

 

 

2106 Btu/hr

3491 Btu/hr

3754 Btu/hr

4915 Btu/hr

 

 

3584Btu/hr

4778 Btu/hr

7218 Btu/hr

9829 Btu/hr

 

 

1229 Btu/hr

1945 Btu/hr

2218 Btu/hr

3157 Btu/hr

 

 

4037 Btu/hr

4037 Btu/hr

7194 Btu/hr

10,912 Btu/hr



Environmental Specifications

 

TABLE 5-5 Environmental Specifications for Sun Systems in Operation

250, V480, V880, V890

280R, V440

Temperature[8]

Allowable

 

 

Recommended

 

41 to 95 oF

5 to 35 oC

 

70 to 74 oF

21 to 23 oC

 

41 to 104 oF

5 to 40 oC

 

70 to 74 oF

21 to 23 oC

Relative Humidity (RH) Noncondensing

Allowable

 

 

  Recommended

 

20% to 80%
27 oC max wet bulb

 

45% to 50%

 

20% to 80%
27 oC max wet bulb

 

45% to 50%

Altitude

0 to 10,000 ft

0 to 3000 m

0 to 10,000 ft

0 to 3000 m


 

TABLE 5-6 Acoustic Specifications for Sun Systems in Operation

Acoustics Rating

250

6.5 bels

280R

6.9 bels

V480

6.7 bels

V880

6.7 bels

V440

6.2 bels

V890

6.7 bels


 

TABLE 5-7 Vibration Specifications for Sun Systems in Operation

Maximum Vibration Rating[9]

250

0.2 g peak (swept sine) 0.0002 g2/Hz (random);

vertical axis only (castered configuration);

vertical and horizontal axis (foot glide configuration)

280R

0.0002 g2/Hz (random), flat from Z-axis only

V480

0.0001 g2/Hz (random), flat from Z-axis only

V880

Deskside: 0.0002 g2/Hz (random)

Rackmounted: 0.00015 g2/Hz (random)

V440

0.0001 g2/Hz (random)

V890

Deskside: 0.0002 g2/Hz (random)

Rackmounted: 0.00015 g2/Hz (random)


 

TABLE 5-8 Shock Specifications for Sun Systems in Operation

Maximum Shock Rating[10]

250

4 g peak

280R

3 g peak

V480

3 g peak

V880

Deskside: 4 g peak

Rackmounted: 3 g peak

V440

3 g peak

V890

Deskside: 4 g peak

Rackmounted: 3 g peak



Rackmounting Specifications

 

TABLE 5-9 Rack Units Required by Sun Systems

Rack Units Required per System for Mounting

250

6U

280R

4U

V480

5U

V880

17U

V440

4U

V890

17U


TABLE 5-10 Typical Rack and Cabinet Depths Used by Sun Systems

System Depth[11]

Rackmounting
Depth Range[12]

Cabinet Depth

250

27.1 in[13]

68.8 cm

27.5 to 35.5 in

69.85 to 90.17 cm

34 in or greater

86 cm or greater

280R

27.25 in

69.21 cm

29.5 to 35.5 in

75.95 to 90.17 cm

34 in or greater

86 cm or greater

V480

24.0 in

61.0 cm

23 to 34.5 in

58.42 to 87.63 cm

28 in or greater

71 cm or greater

V880

32.90 in

83.60 cm

34 to 36 in

86.36 to 91.44 cm

39 in or greater

99 cm or greater

V440

24.0 in

61.0 cm

23 to 34.5 in

58.42 to 87.63 cm

28 in or greater

71 cm or greater

V890

32.90 in

83.60 cm

34 to 36 in

86.36 to 91.44 cm

39 in or greater

99 cm or greater



Sun Cabinet Physical Specifications

TABLE 5-11 Physical Specifications for Crated Cabinets

Sun StorEdge Expansion Cabinet

Sun Fire Cabinet

Sun Rack 900

Height

80 in

203 cm

80 in

203 cm

80 in

203 cm

Width

42 in

107 cm

43 in

109 cm

43 in

109 cm

Depth

47 in

120 cm

47 in

120 cm

48 in

122 cm

Weight

524 lb

238 kg

558 lb

253 kg

530 lb

240 kg


 

TABLE 5-12 Physical Specifications for Cabinets in Operation

Sun StorEdge Expansion Cabinet

Sun Fire Cabinet

Sun Rack 900

Height

73.5 in

186.7 cm

75 in

191 cm

73.75 in

187 cm

Width

24 in

61 cm

24 in

61 cm

23.6 in

60 cm

Nominal Rack Opening

17.72 in

45 cm

17.72 in

45 cm

17.72 in

45 cm

Depth

36 in

91 cm

36 in

91 cm

35.4 in

90 cm

Weight[14]

350 lb

159 kg

325 lb

147 kg

400 lb

181 kg

Load Capacity[15]

1300 lb

589 kg

1200 lb

544 kg

1200 lb

544 kg

Usable Rack Units

36

32

38


 

TABLE 5-13 Cabinet Power Sequencer Specifications

Sun StorEdge Expansion Cabinet

Sun Fire Cabinet

Sun Rack 900

AC Voltage Rating

200 to 240 VAC

200 to 240 VAC

200 to 240 VAC

Frequency Range

47 to 63 Hz

47 to 63 Hz

47 to 63 Hz

Max Current

24A @ 240 VAC

24A @ 240 VAC

32A @ 208 VAC

Max Power Capacity[16]

5.7 kW

5.7 kW

7.6 kW

Required Power Receptacles

2-NEMA L6-30R
(U.S.)

 

2-IEC309 32A
(International)

NEMA L6-30R
(U.S.)

 

IEC309 32A
(International)

4-NEMA L6-20R
(U.S.)

 

4-IEC309 16A
(International)


 

TABLE 5-14 Clearance Specifications for Servicing the Rackmounted Sun Systems [17]

250, 280R, V480 V440

V880, V890

Front

36 in

91.44 cm

48 in

121.92 cm

Rear

36 in

91.44 cm

36 in

91.44 cm

Right

36 in

91.44 cm

36 in

91.44 cm

Left

36 in

91.44 cm

36 in

91.44 cm

Top

36 in

91.44 cm

36 in

91.44 cm


 


1 (TableFootnote) The depth given does not include any I/O or power connectors, or any cable management features.
2 (TableFootnote) Weights are estimates based on fully configured systems, and are dependent on specific system configurations.
3 (TableFootnote) Three 2.75-m (9-ft) cords are provided in the Sun Fire V880 rackmounting kit, which extend the original 2.5-m (8.2-ft) power cord lengths to 5.25 m (17.2 ft).
4 (TableFootnote) Three 2.75-m (9-ft) cords are provided in the Sun Fire V890 rackmounting kit, which extend the original 2.5-m (8.2-ft) power cord lengths to 5.25 m (17.2 ft).
5 (TableFootnote) For the 250, 280R, V480, and V440 systems, the specifications refer to total input current required for a single AC inlet when
operating with a single power supply. The second power supply is the redundant element. For the V880 and V890 systems,
the specifications refer to total input current required for each AC inlet as two power supplies are required to operate the systems.
The third V880 and V890 power supplies are the redundant elements.
6 (TableFootnote) These specifications are calculated using the base system configurations listed in TABLE 5-3.
7 (TableFootnote) These specifications are calculated using the base system configurations listed in TABLE 5-3.
8 (TableFootnote) The front and back doors of the cabinet must be at least 63% open for adequate airflow. 
9 (TableFootnote) Measured at 5 to 500 Hz for swept sine.
10 (TableFootnote) Measured at 11 milliseconds half-sine pulse.
11 (TableFootnote) The depth given does not include any I/O or power connectors, or any cable management features.
12 (TableFootnote) The rack depth range is for systems using Sun rackmounting equipment.
(Rackmounting hardware is designed to fit a range of different cabinet depths.)
13 (TableFootnote) Depth is 28.8 in (73.2 cm) including the power supply handle.
14 (TableFootnote) This specification is the weight of the cabinet and two power sequencers only. The total weight of the cabinet also includes the systems and other equipment it houses.
15 (TableFootnote) This capacity is for a fully configured cabinet.
16 (TableFootnote) This is the theoretical maximum power capacity of the cabinet. This number should not be used
to calculate power and cooling requirements for your installation. Use the combined power
consumption figures of the equipment installed in the cabinet instead. See TABLE 5-4.
17 (TableFootnote) These specifications refer to systems that are fully
extended from the rack.